/* compaq-mib.c - data to monitor SNMP UPS with NUT
|
|
*
|
|
* Copyright (C)
|
|
* 2002-2012 Arnaud Quette <arnaud.quette@free.fr>
|
|
* 2002-2006 Niels Baggesen <niels@baggesen.net>
|
|
* 2002-2006 Philip Ward <p.g.ward@stir.ac.uk>
|
|
*
|
|
* This program was sponsored by MGE UPS SYSTEMS, and now Eaton
|
|
*
|
|
* This version has been tested using:
|
|
* HP R5500XR UPS with management card AF401A and a single phase input
|
|
* HP R/T3000 UPS with management card AF465A and a single phase input
|
|
*
|
|
* This program is free software; you can redistribute it and/or modify
|
|
* it under the terms of the GNU General Public License as published by
|
|
* the Free Software Foundation; either version 2 of the License, or
|
|
* (at your option) any later version.
|
|
*
|
|
* This program is distributed in the hope that it will be useful,
|
|
* but WITHOUT ANY WARRANTY; without even the implied warranty of
|
|
* MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
|
|
* GNU General Public License for more details.
|
|
*
|
|
*
|
|
* You should have received a copy of the GNU General Public License
|
|
* along with this program; if not, write to the Free Software
|
|
* Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
|
|
*
|
|
*/
|
|
|
|
#include "compaq-mib.h"
|
|
|
|
#define CPQPOWER_MIB_VERSION "1.66"
|
|
|
|
#define DEFAULT_ONDELAY "30"
|
|
#define DEFAULT_OFFDELAY "20"
|
|
|
|
/* Note: RFC-1628 (UPS MIB) is also supported on these devices! */
|
|
|
|
/* SNMP OIDs set */
|
|
#define CPQPOWER_OID_UPS_MIB ".1.3.6.1.4.1.232.165.3"
|
|
/* FIXME: to be verified */
|
|
#define CPQPOWER_SYSOID CPQPOWER_OID_UPS_MIB
|
|
|
|
#define CPQPOWER_OID_MFR_NAME ".1.3.6.1.4.1.232.165.3.1.1.0" /* UPS-MIB::upsIdentManufacturer */
|
|
#define CPQPOWER_OID_MODEL_NAME ".1.3.6.1.4.1.232.165.3.1.2.0" /* UPS-MIB::upsIdentModel */
|
|
#define CPQPOWER_OID_FIRMREV ".1.3.6.1.4.1.232.165.3.1.3.0" /* UPS-MIB::upsIdentUPSSoftwareVersion */
|
|
#define CPQPOWER_OID_OEMCODE ".1.3.6.1.4.1.232.165.3.1.4.0" /* UPS-MIB::upsIdentAgentSoftwareVersion */
|
|
|
|
#define CPQPOWER_OID_BATT_RUNTIME ".1.3.6.1.4.1.232.165.3.2.1.0" /* UPS-MIB::upsEstimatedMinutesRemaining */
|
|
#define CPQPOWER_OID_BATT_VOLTAGE ".1.3.6.1.4.1.232.165.3.2.2.0" /* UPS-MIB::upsBatteryVoltage */
|
|
#define CPQPOWER_OID_BATT_CURRENT ".1.3.6.1.4.1.232.165.3.2.3.0" /* UPS-MIB::upsBatteryCurrent */
|
|
#define CPQPOWER_OID_BATT_CHARGE ".1.3.6.1.4.1.232.165.3.2.4.0" /* UPS-MIB::upsBattCapacity */
|
|
#define CPQPOWER_OID_BATT_STATUS ".1.3.6.1.4.1.232.165.3.2.5.0" /* UPS-MIB::upsBatteryAbmStatus */
|
|
|
|
#define CPQPOWER_OID_IN_FREQ ".1.3.6.1.4.1.232.165.3.3.1.0" /* UPS-MIB::upsInputFrequency */
|
|
#define CPQPOWER_OID_IN_LINEBADS ".1.3.6.1.4.1.232.165.3.3.2.0" /* UPS-MIB::upsInputLineBads */
|
|
#define CPQPOWER_OID_IN_LINES ".1.3.6.1.4.1.232.165.3.3.3.0" /* UPS-MIB::upsInputNumPhases */
|
|
|
|
#define CPQPOWER_OID_IN_PHASE ".1.3.6.1.4.1.232.165.3.3.4.1.1" /* UPS-MIB::upsInputPhase */
|
|
#define CPQPOWER_OID_IN_VOLTAGE ".1.3.6.1.4.1.232.165.3.3.4.1.2" /* UPS-MIB::upsInputVoltage */
|
|
#define CPQPOWER_OID_IN_CURRENT ".1.3.6.1.4.1.232.165.3.3.4.1.3" /* UPS-MIB::upsInputCurrent */
|
|
#define CPQPOWER_OID_IN_POWER ".1.3.6.1.4.1.232.165.3.3.4.1.4" /* UPS-MIB::upsInputWatts */
|
|
|
|
#define CPQPOWER_OID_LOAD_LEVEL ".1.3.6.1.4.1.232.165.3.4.1.0" /* UPS-MIB::upsOutputLoad */
|
|
#define CPQPOWER_OID_OUT_FREQUENCY ".1.3.6.1.4.1.232.165.3.4.2.0" /* UPS-MIB::upsOutputFrequency */
|
|
#define CPQPOWER_OID_OUT_LINES ".1.3.6.1.4.1.232.165.3.4.3.0" /* UPS-MIB::upsOutputNumPhases */
|
|
|
|
#define CPQPOWER_OID_OUT_PHASE ".1.3.6.1.4.1.232.165.3.4.4.1.1" /* UPS-MIB::upsOutputPhase */
|
|
#define CPQPOWER_OID_OUT_VOLTAGE ".1.3.6.1.4.1.232.165.3.4.4.1.2" /* UPS-MIB::upsOutputVoltage */
|
|
#define CPQPOWER_OID_OUT_CURRENT ".1.3.6.1.4.1.232.165.3.4.4.1.3" /* UPS-MIB::upsOutputCurrent */
|
|
#define CPQPOWER_OID_OUT_POWER ".1.3.6.1.4.1.232.165.3.4.4.1.4" /* UPS-MIB::upsOutputWatts */
|
|
|
|
#define CPQPOWER_OID_POWER_STATUS ".1.3.6.1.4.1.232.165.3.4.5.0" /* UPS-MIB::upsOutputSource */
|
|
|
|
#define CPQPOWER_OID_AMBIENT_TEMP ".1.3.6.1.4.1.232.165.3.6.1.0" /* UPS-MIB::upsEnvAmbientTemp */
|
|
|
|
#define CPQPOWER_OID_UPS_TEST_BATT ".1.3.6.1.4.1.232.165.3.7.1.0" /* UPS-MIB::upsTestBattery */
|
|
#define CPQPOWER_OID_UPS_TEST_RES ".1.3.6.1.4.1.232.165.3.7.2.0" /* UPS-MIB::upsTestBatteryStatus */
|
|
#define CPQPOWER_OID_ALARM_OB ".1.3.6.1.4.1.232.165.3.7.3.0" /* UPS-MIB::upsOnBattery */
|
|
#define CPQPOWER_OID_ALARM_LB ".1.3.6.1.4.1.232.165.3.7.4.0" /* UPS-MIB::upsLowBattery */
|
|
|
|
#define IETF_OID_AGENTREV ".1.3.6.1.2.1.33.1.1.4.0" /* UPS-MIB::upsIdentAgentSoftwareVersion.0 */
|
|
|
|
/* Not used, as no longer supported by MIB ver. 1.76 (Github issue 118)
|
|
static info_lkp_t cpqpower_alarm_ob[] = {
|
|
{ 1, "OB", NULL, NULL },
|
|
{ 0, NULL, NULL, NULL }
|
|
};
|
|
*/
|
|
|
|
/* Not used, as no longer supported by MIB ver. 1.76 (Github issue 118)
|
|
static info_lkp_t cpqpower_alarm_lb[] = {
|
|
{ 1, "LB", NULL, NULL },
|
|
{ 0, NULL, NULL, NULL }
|
|
};
|
|
*/
|
|
|
|
/* Defines for CPQPOWER_OID_POWER_STATUS (1) */
|
|
static info_lkp_t cpqpower_pwr_info[] = {
|
|
{ 1, "" /* other */, NULL, NULL },
|
|
{ 2, "OFF" /* none */, NULL, NULL },
|
|
{ 3, "OL" /* normal */, NULL, NULL },
|
|
{ 4, "OL BYPASS" /* bypass */, NULL, NULL },
|
|
{ 5, "OB" /* battery */, NULL, NULL },
|
|
{ 6, "OL BOOST" /* booster */, NULL, NULL },
|
|
{ 7, "OL TRIM" /* reducer */, NULL, NULL },
|
|
{ 8, "OL" /* parallelCapacity */, NULL, NULL },
|
|
{ 9, "OL" /* parallelRedundant */, NULL, NULL },
|
|
{ 10, "OL" /* HighEfficiencyMode */, NULL, NULL },
|
|
{ 0, NULL, NULL, NULL }
|
|
} ;
|
|
|
|
static info_lkp_t cpqpower_mode_info[] = {
|
|
{ 1, "", NULL, NULL },
|
|
{ 2, "", NULL, NULL },
|
|
{ 3, "normal", NULL, NULL },
|
|
{ 4, "", NULL, NULL },
|
|
{ 5, "", NULL, NULL },
|
|
{ 6, "", NULL, NULL },
|
|
{ 7, "", NULL, NULL },
|
|
{ 8, "parallel capacity", NULL, NULL },
|
|
{ 9, "parallel redundancy", NULL, NULL },
|
|
{10, "high efficiency", NULL, NULL },
|
|
{ 0, NULL, NULL, NULL }
|
|
};
|
|
|
|
static info_lkp_t cpqpower_battery_abm_status[] = {
|
|
{ 1, "CHRG", NULL, NULL },
|
|
{ 2, "DISCHRG", NULL, NULL },
|
|
/* { 3, "Floating", NULL, NULL }, */
|
|
/* { 4, "Resting", NULL, NULL }, */
|
|
/* { 5, "Unknown", NULL, NULL }, */
|
|
{ 0, NULL, NULL, NULL }
|
|
} ;
|
|
|
|
/* Defines for CPQPOWER_OID_UPS_TEST_RES */
|
|
static info_lkp_t cpqpower_test_res_info[] = {
|
|
{ 1, "Unknown", NULL, NULL },
|
|
{ 2, "Done and passed", NULL, NULL },
|
|
{ 3, "Done and error", NULL, NULL },
|
|
{ 4, "In progress", NULL, NULL },
|
|
{ 5, "Not supported", NULL, NULL },
|
|
{ 6, "Inhibited", NULL, NULL },
|
|
{ 7, "Scheduled", NULL, NULL },
|
|
{ 0, NULL, NULL, NULL }
|
|
} ;
|
|
|
|
#define CPQPOWER_START_TEST "1"
|
|
|
|
static info_lkp_t cpqpower_outlet_status_info[] = {
|
|
{ 1, "on", NULL, NULL },
|
|
{ 2, "off", NULL, NULL },
|
|
{ 3, "pendingOff", NULL, NULL }, /* transitional status */
|
|
{ 4, "pendingOn", NULL, NULL }, /* transitional status */
|
|
{ 5, "unknown", NULL, NULL },
|
|
{ 0, NULL, NULL, NULL }
|
|
};
|
|
|
|
/* Ugly hack: having the matching OID present means that the outlet is
|
|
* switchable. So, it should not require this value lookup */
|
|
static info_lkp_t cpqpower_outlet_switchability_info[] = {
|
|
{ 1, "yes", NULL, NULL },
|
|
{ 2, "yes", NULL, NULL },
|
|
{ 3, "yes", NULL, NULL },
|
|
{ 4, "yes", NULL, NULL },
|
|
{ 0, NULL, NULL, NULL }
|
|
};
|
|
|
|
#define CPQPOWER_OID_SD_AFTER_DELAY ".1.3.6.1.4.1.232.165.3.8.1.0" /* UPS-MIB::upsControlOutputOffDelay */
|
|
#define CPQPOWER_OFF_DO 0
|
|
|
|
/* Snmp2NUT lookup table */
|
|
|
|
static snmp_info_t cpqpower_mib[] = {
|
|
|
|
/* standard MIB items */
|
|
{ "device.description", ST_FLAG_STRING | ST_FLAG_RW, SU_INFOSIZE, ".1.3.6.1.2.1.1.1.0", NULL, SU_FLAG_OK, NULL },
|
|
{ "device.contact", ST_FLAG_STRING | ST_FLAG_RW, SU_INFOSIZE, ".1.3.6.1.2.1.1.4.0", NULL, SU_FLAG_OK, NULL },
|
|
{ "device.location", ST_FLAG_STRING | ST_FLAG_RW, SU_INFOSIZE, ".1.3.6.1.2.1.1.6.0", NULL, SU_FLAG_OK, NULL },
|
|
|
|
/* UPS page */
|
|
/* info_type, info_flags, info_len, OID, dfl, flags, oid2info, setvar */
|
|
{ "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_MFR_NAME, "HP/Compaq", SU_FLAG_STATIC, NULL },
|
|
{ "ups.model", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_MODEL_NAME, "SNMP UPS", SU_FLAG_STATIC, NULL },
|
|
/* { "ups.model.aux", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_OEMCODE, "", SU_FLAG_STATIC, NULL },*/
|
|
{ "ups.serial", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.232.165.1.2.7.0", "", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
|
|
/* FIXME: split between firmware and firmware.aux ("00.01.0019;00.01.0004")
|
|
* UPS Firmware Revision : 00.01.0004
|
|
* Communication Board Firmware Revision : 00.01.0019 */
|
|
/* FIXME: the 2 "firmware" entries below should be SU_FLAG_SEMI_STATIC */
|
|
{ "ups.firmware", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_FIRMREV, "", 0, NULL },
|
|
{ "ups.firmware.aux", ST_FLAG_STRING, SU_INFOSIZE, IETF_OID_AGENTREV, "", 0, NULL },
|
|
{ "ups.load", 0, 1.0, CPQPOWER_OID_LOAD_LEVEL, "", 0, NULL },
|
|
{ "ups.realpower", 0, 1.0, CPQPOWER_OID_OUT_POWER, "", SU_OUTPUT_1, NULL },
|
|
{ "ups.realpower", 0, 1.0, ".1.3.6.1.4.1.232.165.3.9.3.0", "", SU_OUTPUT_1, NULL },
|
|
{ "ups.L1.realpower", 0, 0.1, CPQPOWER_OID_OUT_POWER ".1", "", SU_OUTPUT_3, NULL },
|
|
{ "ups.L2.realpower", 0, 0.1, CPQPOWER_OID_OUT_POWER ".2", "", SU_OUTPUT_3, NULL },
|
|
{ "ups.L3.realpower", 0, 0.1, CPQPOWER_OID_OUT_POWER ".3", "", SU_OUTPUT_3, NULL },
|
|
{ "ups.status", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_POWER_STATUS, "OFF", SU_STATUS_PWR, cpqpower_pwr_info },
|
|
{ "ups.status", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_BATT_STATUS, "", SU_STATUS_PWR, cpqpower_battery_abm_status },
|
|
/* The next two lines are no longer supported by MIB ver. 1.76 (Github issue 118)
|
|
* { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_ALARM_OB, "", SU_STATUS_BATT, cpqpower_alarm_ob },
|
|
* { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_ALARM_LB, "", SU_STATUS_BATT, cpqpower_alarm_lb }, */
|
|
/* { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, IETF_OID_BATT_STATUS, "", SU_STATUS_BATT, ietf_batt_info }, */
|
|
/* FIXME: this should use either .1.3.6.1.4.1.232.165.3.11.1.0 (upsTopologyType)
|
|
* or .1.3.6.1.4.1.232.165.3.11.2.0 (upsTopoMachineCode) */
|
|
{ "ups.type", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_POWER_STATUS, "", SU_STATUS_PWR, cpqpower_mode_info },
|
|
{ "ups.test.result", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_UPS_TEST_RES, "", 0, cpqpower_test_res_info },
|
|
/* FIXME: handle ups.date and ups.time
|
|
* - OID: .1.3.6.1.4.1.232.165.3.9.5.0
|
|
* - format MM/DD/YYYY HH:MM:SS */
|
|
/* FIXME: handle upsInputSource.0 (".1.3.6.1.4.1.232.165.3.3.5.0")
|
|
* other(1)
|
|
* none(2)
|
|
* primaryUtility(3)
|
|
* bypassFeed(4)
|
|
* secondaryUtility(5)
|
|
* generator(6)
|
|
* flywheel(7)
|
|
* fuelcell(8) */
|
|
|
|
{ "ups.delay.shutdown", ST_FLAG_STRING | ST_FLAG_RW, 6, ".1.3.6.1.4.1.232.165.3.8.1.0", DEFAULT_OFFDELAY, SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
|
|
{ "ups.delay.start", ST_FLAG_STRING | ST_FLAG_RW, 6, ".1.3.6.1.4.1.232.165.3.8.2.0", DEFAULT_ONDELAY, SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
|
|
{ "ups.timer.shutdown", 0, 1, ".1.3.6.1.4.1.232.165.3.8.1.0", "", SU_FLAG_OK, NULL },
|
|
{ "ups.timer.start", 0, 1, ".1.3.6.1.4.1.232.165.3.8.2.0", "", SU_FLAG_OK, NULL },
|
|
|
|
/* Ambient page */
|
|
{ "ambient.temperature", 0, 1.0, CPQPOWER_OID_AMBIENT_TEMP, "", 0, NULL },
|
|
{ "ambient.temperature.low", 0, 1.0, ".1.3.6.1.4.1.232.165.3.6.2.0", "", 0, NULL },
|
|
{ "ambient.temperature.high", 0, 1.0, ".1.3.6.1.4.1.232.165.3.6.3.0", "", 0, NULL },
|
|
|
|
/* Battery page */
|
|
{ "battery.charge", 0, 1.0, CPQPOWER_OID_BATT_CHARGE, "", 0, NULL },
|
|
{ "battery.runtime", 0, 1.0, CPQPOWER_OID_BATT_RUNTIME, "", 0, NULL },
|
|
{ "battery.voltage", 0, 0.1, CPQPOWER_OID_BATT_VOLTAGE, "", 0, NULL },
|
|
{ "battery.current", 0, 0.1, CPQPOWER_OID_BATT_CURRENT, "", 0, NULL },
|
|
/* FIXME: need the new variable (for ABM)
|
|
{ "battery.status", 0, 0.1, ".1.3.6.1.4.1.232.165.3.2.5.0", "", 0, NULL }, */
|
|
|
|
/* Input page */
|
|
{ "input.phases", 0, 1.0, CPQPOWER_OID_IN_LINES, "", 0, NULL },
|
|
/* { "input.phase", 0, 1.0, CPQPOWER_OID_IN_PHASE, "", SU_OUTPUT_1, NULL }, */
|
|
{ "input.frequency", 0, 0.1, CPQPOWER_OID_IN_FREQ , "", 0, NULL },
|
|
{ "input.voltage", 0, 1.0, CPQPOWER_OID_IN_VOLTAGE, "", SU_OUTPUT_1, NULL },
|
|
{ "input.voltage", 0, 1.0, ".1.3.6.1.4.1.232.165.3.3.4.1.2.1", "", SU_OUTPUT_1, NULL },
|
|
{ "input.voltage.nominal", ST_FLAG_RW | ST_FLAG_STRING, 3, ".1.3.6.1.4.1.232.165.3.9.2.0", "", SU_OUTPUT_1, NULL },
|
|
{ "input.L1-N.voltage", 0, 1.0, CPQPOWER_OID_IN_VOLTAGE ".1", "", SU_INPUT_3, NULL },
|
|
{ "input.L2-N.voltage", 0, 1.0, CPQPOWER_OID_IN_VOLTAGE ".2", "", SU_INPUT_3, NULL },
|
|
{ "input.L3-N.voltage", 0, 1.0, CPQPOWER_OID_IN_VOLTAGE ".3", "", SU_INPUT_3, NULL },
|
|
{ "input.current", 0, 0.1, CPQPOWER_OID_IN_CURRENT, "", SU_OUTPUT_1, NULL },
|
|
{ "input.current", 0, 0.1, ".1.3.6.1.4.1.232.165.3.3.4.1.3.1", "", SU_OUTPUT_1, NULL },
|
|
|
|
{ "input.L1.current", 0, 0.1, CPQPOWER_OID_IN_CURRENT ".1", "", SU_INPUT_3, NULL },
|
|
{ "input.L2.current", 0, 0.1, CPQPOWER_OID_IN_CURRENT ".2", "", SU_INPUT_3, NULL },
|
|
{ "input.L3.current", 0, 0.1, CPQPOWER_OID_IN_CURRENT ".3", "", SU_INPUT_3, NULL },
|
|
{ "input.realpower", 0, 0.1, CPQPOWER_OID_IN_POWER, "", SU_OUTPUT_1, NULL },
|
|
{ "input.L1.realpower", 0, 0.1, CPQPOWER_OID_IN_POWER ".1", "", SU_INPUT_3, NULL },
|
|
{ "input.L2.realpower", 0, 0.1, CPQPOWER_OID_IN_POWER ".2", "", SU_INPUT_3, NULL },
|
|
{ "input.L3.realpower", 0, 0.1, CPQPOWER_OID_IN_POWER ".3", "", SU_INPUT_3, NULL },
|
|
{ "input.quality", 0, 1.0, CPQPOWER_OID_IN_LINEBADS, "", 0, NULL },
|
|
|
|
/* Output page */
|
|
{ "output.phases", 0, 1.0, CPQPOWER_OID_OUT_LINES, "", 0, NULL },
|
|
/* { "output.phase", 0, 1.0, CPQPOWER_OID_OUT_PHASE, "", SU_OUTPUT_1, NULL }, */
|
|
{ "output.frequency", 0, 0.1, CPQPOWER_OID_OUT_FREQUENCY, "", 0, NULL },
|
|
/* FIXME: handle multiplier (0.1 there) */
|
|
{ "output.frequency.nominal", ST_FLAG_RW | ST_FLAG_STRING, 3, ".1.3.6.1.4.1.232.165.3.9.4.0", "", SU_OUTPUT_1, NULL },
|
|
{ "output.voltage", 0, 1.0, CPQPOWER_OID_OUT_VOLTAGE, "", SU_OUTPUT_1, NULL },
|
|
{ "output.voltage", 0, 1.0, ".1.3.6.1.4.1.232.165.3.4.4.1.2.1", "", SU_OUTPUT_1, NULL },
|
|
{ "output.voltage.nominal", ST_FLAG_RW | ST_FLAG_STRING, 3, ".1.3.6.1.4.1.232.165.3.9.1.0", "", SU_OUTPUT_1, NULL },
|
|
{ "output.L1-N.voltage", 0, 1.0, CPQPOWER_OID_OUT_VOLTAGE ".1", "", SU_OUTPUT_3, NULL },
|
|
{ "output.L2-N.voltage", 0, 1.0, CPQPOWER_OID_OUT_VOLTAGE ".2", "", SU_OUTPUT_3, NULL },
|
|
{ "output.L3-N.voltage", 0, 1.0, CPQPOWER_OID_OUT_VOLTAGE ".3", "", SU_OUTPUT_3, NULL },
|
|
{ "output.current", 0, 0.1, CPQPOWER_OID_OUT_CURRENT, "", SU_OUTPUT_1, NULL },
|
|
{ "output.current", 0, 0.1, ".1.3.6.1.4.1.232.165.3.4.4.1.3.1", "", SU_OUTPUT_1, NULL },
|
|
/* { "output.realpower", 0, 1.0, ".1.3.6.1.4.1.232.165.3.4.4.1.4", "", SU_OUTPUT_1, NULL }, */
|
|
{ "output.L1.current", 0, 0.1, CPQPOWER_OID_OUT_CURRENT ".1", "", SU_OUTPUT_3, NULL },
|
|
{ "output.L2.current", 0, 0.1, CPQPOWER_OID_OUT_CURRENT ".2", "", SU_OUTPUT_3, NULL },
|
|
{ "output.L3.current", 0, 0.1, CPQPOWER_OID_OUT_CURRENT ".3", "", SU_OUTPUT_3, NULL },
|
|
|
|
/* FIXME: what to map with these?
|
|
* Name/OID: upsConfigLowOutputVoltageLimit.0; Value (Integer): 160
|
|
* => input.transfer.low?
|
|
* Name/OID: upsConfigHighOutputVoltageLimit.0; Value (Integer): 288
|
|
* => input.transfer.high? */
|
|
|
|
/* Outlet page */
|
|
{ "outlet.id", 0, 1, NULL, "0", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
|
|
{ "outlet.desc", ST_FLAG_RW | ST_FLAG_STRING, 20, NULL, "All outlets",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
|
|
{ "outlet.count", 0, 1, ".1.3.6.1.4.1.232.165.3.10.1.0", "0", 0, NULL }, /* upsNumReceptacles */
|
|
|
|
/* { "outlet.current", 0, 0.001, AR_OID_UNIT_CURRENT ".0", NULL, 0, NULL, NULL },
|
|
{ "outlet.voltage", 0, 0.001, AR_OID_UNIT_VOLTAGE ".0", NULL, 0, NULL, NULL },
|
|
{ "outlet.realpower", 0, 1.0, AR_OID_UNIT_ACTIVEPOWER ".0", NULL, 0, NULL, NULL },
|
|
{ "outlet.power", 0, 1.0, AR_OID_UNIT_APPARENTPOWER ".0", NULL, 0, NULL, NULL }, */
|
|
|
|
/* outlet template definition */
|
|
/* FIXME always true? */
|
|
{ "outlet.%i.switchable", ST_FLAG_STRING, 3, ".1.3.6.1.4.1.232.165.3.10.2.1.1.%i", "yes", SU_FLAG_STATIC | SU_OUTLET, &cpqpower_outlet_switchability_info[0] },
|
|
{ "outlet.%i.id", 0, 1, ".1.3.6.1.4.1.232.165.3.10.2.1.1.%i", "%i", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK | SU_OUTLET, NULL },
|
|
/* { "outlet.%i.desc", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE, AR_OID_OUTLET_NAME ".%i", NULL, SU_OUTLET, NULL }, */
|
|
{ "outlet.%i.status", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.232.165.3.10.2.1.2.%i", NULL, SU_FLAG_OK | SU_OUTLET, &cpqpower_outlet_status_info[0] },
|
|
/* FIXME: come up with a suitable varname!
|
|
* - The delay after going On Battery until the Receptacle is automatically turned Off.
|
|
* A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command.
|
|
* { "outlet.%i.autoswitch.delay.shutdown", ST_FLAG_STRING | ST_FLAG_RW, 6, ".1.3.6.1.4.1.232.165.3.10.2.1.5.%i", DEFAULT_OFFDELAY, SU_FLAG_ABSENT | SU_FLAG_OK, NULL }, // upsRecepAutoOffDelay
|
|
* - Seconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON.
|
|
* A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to do so.
|
|
* { "outlet.%i.autoswitch.delay.start", ST_FLAG_STRING | ST_FLAG_RW, 6, ".1.3.6.1.4.1.232.165.3.10.2.1.5.%i", DEFAULT_OFFDELAY, SU_FLAG_ABSENT | SU_FLAG_OK, NULL }, // upsRecepAutoOnDelay
|
|
*/
|
|
/* FIXME: also define .stop (as for 'shutdown.reboot')
|
|
* and .delay */
|
|
{ "outlet.%i.load.off", 0, 1, ".1.3.6.1.4.1.232.165.3.10.2.1.3.%i", "0", SU_TYPE_CMD | SU_OUTLET, NULL },
|
|
{ "outlet.%i.load.on", 0, 1, ".1.3.6.1.4.1.232.165.3.10.2.1.4.%i", "0", SU_TYPE_CMD | SU_OUTLET, NULL },
|
|
/* FIXME: also define a .delay or map to "outlet.%i.delay.shutdown" */
|
|
{ "outlet.%i.load.cycle", 0, 1, ".1.3.6.1.4.1.232.165.3.10.2.1.7.%i", "0", SU_TYPE_CMD | SU_OUTLET, NULL },
|
|
|
|
/* instant commands. */
|
|
/* We need to duplicate load.{on,off} Vs load.{on,off}.delay, since
|
|
* "0" cancels the shutdown, so we put "1" (second) for immediate off! */
|
|
{ "load.off", 0, 1, ".1.3.6.1.4.1.232.165.3.8.1.0", "1", SU_TYPE_CMD, NULL },
|
|
{ "load.on", 0, 1, ".1.3.6.1.4.1.232.165.3.8.2.0", "1", SU_TYPE_CMD, NULL },
|
|
{ "shutdown.stop", 0, 1, ".1.3.6.1.4.1.232.165.3.8.1.0", "0", SU_TYPE_CMD | SU_FLAG_OK, NULL },
|
|
/* FIXME: need ups.{timer,delay}.{start,shutdown} param counterparts! */
|
|
|
|
{ "load.off.delay", 0, 1, ".1.3.6.1.4.1.232.165.3.8.1.0", DEFAULT_OFFDELAY, SU_TYPE_CMD, NULL },
|
|
{ "load.on.delay", 0, 1, ".1.3.6.1.4.1.232.165.3.8.2.0", DEFAULT_ONDELAY, SU_TYPE_CMD, NULL },
|
|
/* { CMD_SHUTDOWN, 0, CPQPOWER_OFF_GRACEFUL, CPQPOWER_OID_OFF, "", 0, NULL }, */
|
|
{ "shutdown.reboot", 0, 1, ".1.3.6.1.4.1.232.165.3.8.6.0", "0", SU_TYPE_CMD | SU_FLAG_OK, NULL },
|
|
{ "test.battery.start", 0, 1, ".1.3.6.1.4.1.232.165.3.7.1.0", CPQPOWER_START_TEST, SU_TYPE_CMD | SU_FLAG_OK, NULL },
|
|
|
|
/* end of structure. */
|
|
{ NULL, 0, 0, NULL, NULL, 0, NULL }
|
|
};
|
|
|
|
mib2nut_info_t compaq = { "cpqpower", CPQPOWER_MIB_VERSION, NULL, CPQPOWER_OID_MFR_NAME, cpqpower_mib, CPQPOWER_SYSOID, NULL };
|
|
|