.TH MEGATEC_USB 8 "Sun Mar 4 2007" "" "Network UPS Tools (NUT)"
|
|
.SH NAME
|
|
megatec_usb \- Driver for Megatec protocol based USB UPS equipment
|
|
.SH NOTE
|
|
This man page only documents the hardware\(hyspecific features of the
|
|
megatec_usb driver. For information about the core driver, see
|
|
\fBnutupsdrv\fR(8).
|
|
|
|
\fBNote.\fR This driver is experimental at the moment. It is currently being
|
|
worked on and may change over time. However, it is stable in execution and
|
|
does what is needed.
|
|
|
|
.SH SUPPORTED HARDWARE
|
|
|
|
The megatec_usb driver is known to work with various UPSes from Krauler, Agiler,
|
|
and Upsonic (Ablerex interface). Others that use the Megatec protocol
|
|
may work, but haven't been tested.
|
|
|
|
This driver supports the USB versions of UPSs, if you have only serial interface then use the
|
|
straight \fBmegatec\fR(8) driver.
|
|
|
|
If you find that this driver does not work, and you are sure that your hardware speaks megatec protocol,
|
|
then you can easily extend this driver. However, you will need to do some analysis of the
|
|
commands that are sent to the UPS. Please see the forums for discussions on this and how
|
|
to extend this driver.
|
|
|
|
.SH EXTENSIONS TO MEGATEC
|
|
|
|
This driver extends the standard \fBmegatec\fR(8) driver to work with certain UPSes that have
|
|
a USB interface. These devices do not obey the normal rules for HID USB devices and therefore the
|
|
\fBnewhidups\fR(8) driver will not work for them.
|
|
|
|
This driver takes the standard serial interface and passes this over USB to the UPS.
|
|
This means that most, but not all, commands available for the serial driver will
|
|
work. For Krauler, Agiler, and Upsonic (with Ablerex interface) UPSes
|
|
it appears to give very similar results to the serial interface. The
|
|
driver supports monitoring most of the usual UPS variables, and also
|
|
supports automatic shutdown.
|
|
|
|
.SH EXTRA ARGUMENTS
|
|
|
|
.IP "mfr=\fIstring\fR"
|
|
|
|
Optional. Specify the UPS manufacturer name.
|
|
|
|
.IP "model=\fIstring\fR"
|
|
|
|
Optional. Specify the UPS model name.
|
|
|
|
.IP "serial=\fIstring\fR"
|
|
|
|
Optional. Specify the UPS serial number.
|
|
|
|
.IP "lowbatt=\fIfloat\fR"
|
|
|
|
Optional. Low battery level (%). Overrides the hardware default level.
|
|
|
|
.IP "ondelay=\fIint\fR"
|
|
|
|
Optional. Delay before the UPS is turned back on (minutes).
|
|
|
|
.IP "offdelay=\fIint\fR"
|
|
|
|
Optional. Delay before the UPS is turned off (minutes).
|
|
|
|
.IP "battvolts=\fIfloat\fR:\fIfloat\fR"
|
|
|
|
Optional. The battery voltage interval <empty:full> (volts).
|
|
|
|
.IP "vendor=\fIregex\fR"
|
|
.IP "product=\fIregex\fR"
|
|
.IP "vendorid=\fIregex\fR"
|
|
.IP "productid=\fIregex\fR"
|
|
|
|
Select a specific UPS, in case there is more than one connected via
|
|
USB. Each option specifies an extended regular expression (see
|
|
\fBregex(7)\fR) that must match the UPS's entire vendor/product/serial
|
|
string (minus any surrounding whitespace), or the whole 4-digit
|
|
hexadecimal code for vendorid and productid. Try \fB-DD\fR for
|
|
finding out the strings to match.
|
|
|
|
Examples:
|
|
|
|
\fB-x vendor="Foo.Corporation.*"\fR
|
|
|
|
\fB-x vendorid=05b8\fR (Agiler)
|
|
|
|
\fB-x product=".*(Smart|Back)-?UPS.*"\fR
|
|
|
|
.IP "bus=\fIregex\fR"
|
|
|
|
Select a UPS on a specific USB bus or group of busses. The argument is
|
|
a regular expression that must match the bus name where the UPS is
|
|
connected (e.g. bus="002", bus="00[2-3]").
|
|
|
|
.IP "subdriver=\fIstring\fR"
|
|
|
|
Select a serial-over-USB subdriver to use. You have a choice between "agiler" and "krauler" subdrivers currently.
|
|
|
|
.SH UPS COMMANDS
|
|
|
|
This driver supports some extra commands (see \fBupscmd\fR(8)):
|
|
|
|
.IP beeper.toggle
|
|
Toggle the UPS beeper. (Not available on some hardware.)
|
|
|
|
.IP load.on
|
|
Turn on the load immediately.
|
|
|
|
.IP load.off
|
|
Turn off the load immediately. (Not yet supported)
|
|
|
|
.IP reset.input.minmax
|
|
Reset minimum and maximum input voltage status. (Not yet supported)
|
|
|
|
.IP reset.watchdog
|
|
Restarts the UPS watchdog timeout. The watchdog is started if it isn't running,
|
|
which means the UPS shuts down one minute after this command is executed for
|
|
the last time, restarting one minute afterwards. To cancel the watchdog, run
|
|
the "shutdown.stop" command.
|
|
|
|
.IP shutdown.return
|
|
Turn off the load and return when power is back. (Not yet supported)
|
|
|
|
.IP shutdown.stayoff
|
|
Turn off the load and remain off. (Not yet supported)
|
|
|
|
.IP shutdown.stop
|
|
Stop a shutdown in progress.
|
|
|
|
.IP test.battery.start.deep
|
|
Perform a long battery test (Not available on some hardware.)
|
|
|
|
.IP test.battery.start
|
|
Perform a (10 second) battery test.
|
|
|
|
.IP test.battery.stop
|
|
Stop a running battery test. (Not available on some hardware.)
|
|
|
|
.SH USER VARIABLES
|
|
|
|
The behavior of the driver can be controlled by some user definable
|
|
variables (see \fBupsrw\fR(8)):
|
|
|
|
.IP ups.delay.shutdown
|
|
Interval to wait after shutdown with delay command (seconds)
|
|
|
|
.IP ups.delay.start
|
|
Interval to wait before (re)starting the load (seconds)
|
|
|
|
.SH KNOWN PROBLEMS
|
|
|
|
The battery charge (%) value is only a best-effort calculation and may be
|
|
incorrect, or non-existant, for some UPS models. In any case, you can always
|
|
resort to finding the voltages at which the battery becomes fully discharged
|
|
and fully charged, and specify them manually using the "battvolts" option.
|
|
If you do this, please notify the author of this driver.
|
|
|
|
Some UPS commands aren't supported by all models. In most cases, the driver
|
|
will send a message to the system log when the user tries to execute an
|
|
unsupported command. Unfortunately, some models don't even provide a way for
|
|
the driver to check for this, so the unsupported commands will silently
|
|
fail.
|
|
|
|
Some models report a bogus value for the beeper status (will always be
|
|
"enabled" or "disabled"). So, the "beeper.toggle" command may appear to have
|
|
no effect in the status reported by the driver when, in fact, it is working
|
|
fine.
|
|
|
|
The temperature value is also known to be bogus in some models.
|
|
|
|
|
|
.SH AUTHORS
|
|
Carlos Rodrigues <carlos.efr at mail.telepac.pt>
|
|
.br
|
|
Andrey Lelikov <nut-driver at lelik.org>
|
|
.br
|
|
Alexander Gordeev <lasaine at lvk.cs.msu.su>
|
|
.br
|
|
Jon Gough <jon.gough at eclipsesystems.com.au>
|
|
|
|
.SH SEE ALSO
|
|
|
|
\fBmegatec\fR(8), \fBnutupsdrv\fR(8), \fBupsc\fR(8), \fBupscmd\fR(8), \fBupsrw\fR(8)
|
|
|
|
.SS Internet resources:
|
|
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|