205 lines
10 KiB
C
205 lines
10 KiB
C
/* eaton-mib.c - data to monitor Eaton Aphel PDUs (Basic and Complex)
|
|
*
|
|
* Copyright (C) 2008
|
|
* Arnaud Quette <ArnaudQuette@Eaton.com>
|
|
*
|
|
* Sponsored by Eaton <http://www.eaton.com>
|
|
* and MGE Office Protection Systems <http://www.mgeops.com>
|
|
*
|
|
* This program is free software; you can redistribute it and/or modify
|
|
* it under the terms of the GNU General Public License as published by
|
|
* the Free Software Foundation; either version 2 of the License, or
|
|
* (at your option) any later version.
|
|
*
|
|
* This program is distributed in the hope that it will be useful,
|
|
* but WITHOUT ANY WARRANTY; without even the implied warranty of
|
|
* MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
|
|
* GNU General Public License for more details.
|
|
*
|
|
*
|
|
* You should have received a copy of the GNU General Public License
|
|
* along with this program; if not, write to the Free Software
|
|
* Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
|
|
*
|
|
*/
|
|
|
|
#include "eaton-mib.h"
|
|
|
|
#define EATON_APHEL_MIB_VERSION "0.4"
|
|
|
|
/* APHEL-GENESIS-II-MIB (monitored ePDU)
|
|
* *************************************
|
|
* Note: we should also be able to support this one using netxml-ups!
|
|
*/
|
|
|
|
#define APHEL1_OID_MIB ".1.3.6.1.4.1.17373"
|
|
#define APHEL1_OID_MODEL_NAME ".1.3.6.1.4.1.17373.3.1.1.0"
|
|
#define APHEL1_OID_FIRMREV ".1.3.6.1.4.1.17373.3.1.2.0"
|
|
#define APHEL1_OID_DEVICE_NAME ".1.3.6.1.4.1.17373.3.1.3.0"
|
|
#define APHEL1_OID_UNIT_MACADDR ".1.3.6.1.4.1.17373.3.1.4.0"
|
|
/* needs concat .<outlet-index>.0 */
|
|
#define APHEL1_OID_OUTLET_CURRENT ".1.3.6.1.4.1.17373.3.2"
|
|
|
|
/* Snmp2NUT lookup table for GenesisII MIB */
|
|
static snmp_info_t eaton_aphel_genesisII_mib[] = {
|
|
/* Device page */
|
|
{ "device.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
|
|
{ "device.model", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_MODEL_NAME,
|
|
"Eaton Powerware ePDU Monitored", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "device.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
|
|
|
|
/* UPS page */
|
|
{ "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.model", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_MODEL_NAME,
|
|
"Generic SNMP PDU", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.id", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_DEVICE_NAME,
|
|
"unknown", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.firmware", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_FIRMREV, "",
|
|
SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.macaddr", ST_FLAG_STRING, SU_INFOSIZE, APHEL1_OID_UNIT_MACADDR, "unknown",
|
|
0, NULL, NULL },
|
|
|
|
/* Outlet page */
|
|
/* we can't use template since there is no counterpart to outlet.count */
|
|
{ "outlet.1.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".1.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
|
|
{ "outlet.2.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".2.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
|
|
{ "outlet.3.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".3.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
|
|
{ "outlet.4.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".4.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
|
|
{ "outlet.5.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".5.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
|
|
{ "outlet.6.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".6.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
|
|
{ "outlet.7.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".7.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
|
|
{ "outlet.8.current", 0, 0.001, APHEL1_OID_OUTLET_CURRENT ".8.0", NULL, SU_FLAG_NEGINVALID, NULL, NULL },
|
|
|
|
/* end of structure. */
|
|
{ NULL, 0, 0, NULL, NULL, 0, NULL, NULL }
|
|
};
|
|
|
|
|
|
/* APHEL PDU-MIB - Revelation MIB (Managed ePDU)
|
|
* ********************************************* */
|
|
|
|
#define AR_BASE_OID ".1.3.6.1.4.1.534.6.6.6"
|
|
|
|
#define APHEL2_OID_MODEL_NAME AR_OID_MODEL_NAME
|
|
|
|
/* Common Aphel / Raritan declaration */
|
|
|
|
#define AR_OID_MODEL_NAME AR_BASE_OID ".1.1.12.0"
|
|
#define AR_OID_DEVICE_NAME AR_BASE_OID ".1.1.13.0"
|
|
#define AR_OID_FIRMREV AR_BASE_OID ".1.1.1.0"
|
|
#define AR_OID_SERIAL AR_BASE_OID ".1.1.2.0"
|
|
#define AR_OID_UNIT_MACADDR AR_BASE_OID ".1.1.6.0"
|
|
|
|
#define AR_OID_UNIT_CURRENT AR_BASE_OID ".1.3.1.1"
|
|
#define AR_OID_UNIT_VOLTAGE AR_BASE_OID ".1.3.1.2"
|
|
#define AR_OID_UNIT_ACTIVEPOWER AR_BASE_OID ".1.3.1.3"
|
|
#define AR_OID_UNIT_APPARENTPOWER AR_BASE_OID ".1.3.1.4"
|
|
#define AR_OID_UNIT_CPUTEMPERATURE AR_BASE_OID ".1.3.1.5.0"
|
|
|
|
#define AR_OID_OUTLET_INDEX AR_BASE_OID ".1.2.2.1.1"
|
|
#define AR_OID_OUTLET_NAME AR_BASE_OID ".1.2.2.1.2"
|
|
#define AR_OID_OUTLET_STATUS AR_BASE_OID ".1.2.2.1.3"
|
|
|
|
static info_lkp_t outlet_status_info[] = {
|
|
{ -1, "error" },
|
|
{ 0, "off" },
|
|
{ 1, "on" },
|
|
{ 2, "cycling" }, /* transitional status */
|
|
{ 0, NULL }
|
|
};
|
|
|
|
#define DO_OFF 0
|
|
#define DO_ON 1
|
|
#define DO_CYCLE 2
|
|
|
|
#define AR_OID_OUTLET_COUNT AR_BASE_OID ".1.2.1.0"
|
|
#define AR_OID_OUTLET_CURRENT AR_BASE_OID ".1.2.2.1.4"
|
|
#define AR_OID_OUTLET_MAXCURRENT AR_BASE_OID ".1.2.2.1.5"
|
|
#define AR_OID_OUTLET_VOLTAGE AR_BASE_OID ".1.2.2.1.6"
|
|
#define AR_OID_OUTLET_ACTIVEPOWER AR_BASE_OID ".1.2.2.1.7"
|
|
#define AR_OID_OUTLET_APPARENTPOWER AR_BASE_OID ".1.2.2.1.8"
|
|
#define AR_OID_OUTLET_POWERFACTOR AR_BASE_OID ".1.2.2.1.9"
|
|
|
|
/* Snmp2NUT lookup table for Eaton Revelation MIB */
|
|
static snmp_info_t eaton_aphel_revelation_mib[] = {
|
|
/* Device page */
|
|
{ "device.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
|
|
{ "device.model", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_MODEL_NAME,
|
|
"Eaton Powerware ePDU Managed", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "device.serial", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_SERIAL, "",
|
|
SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "device.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
|
|
|
|
/* UPS page */
|
|
{ "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.model", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_MODEL_NAME,
|
|
"Generic SNMP PDU", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.id", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_DEVICE_NAME,
|
|
"unknown", SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.serial", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_SERIAL, "",
|
|
SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.firmware", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_FIRMREV, "",
|
|
SU_FLAG_STATIC | SU_FLAG_OK, NULL },
|
|
{ "ups.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.macaddr", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_UNIT_MACADDR, "",
|
|
SU_FLAG_STATIC | SU_FLAG_OK, NULL, NULL },
|
|
{ "ups.temperature", 0, 1, AR_OID_UNIT_CPUTEMPERATURE, NULL, 0, NULL, NULL },
|
|
|
|
/* Outlet page */
|
|
{ "outlet.id", 0, 1, NULL, "0", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
|
|
{ "outlet.desc", ST_FLAG_RW | ST_FLAG_STRING, 20, NULL, "All outlets",
|
|
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
|
|
{ "outlet.count", 0, 1, AR_OID_OUTLET_COUNT, "0", 0, NULL },
|
|
{ "outlet.current", 0, 0.001, AR_OID_UNIT_CURRENT ".0", NULL, 0, NULL, NULL },
|
|
{ "outlet.voltage", 0, 0.001, AR_OID_UNIT_VOLTAGE ".0", NULL, 0, NULL, NULL },
|
|
{ "outlet.realpower", 0, 1.0, AR_OID_UNIT_ACTIVEPOWER ".0", NULL, 0, NULL, NULL },
|
|
{ "outlet.power", 0, 1.0, AR_OID_UNIT_APPARENTPOWER ".0", NULL, 0, NULL, NULL },
|
|
|
|
/* outlet template definition
|
|
* Caution: the index of the data start at 0, while the name is +1
|
|
* ie outlet.1 => <OID>.0 */
|
|
{ "outlet.%i.switchable", 0, 1, AR_OID_OUTLET_INDEX ".%i", "yes", SU_FLAG_STATIC | SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.id", 0, 1, NULL, "%i", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK | SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.desc", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE, AR_OID_OUTLET_NAME ".%i", NULL, SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.status", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_OUTLET_STATUS ".%i", NULL, SU_FLAG_OK | SU_OUTLET, &outlet_status_info[0], NULL },
|
|
{ "outlet.%i.current", 0, 0.001, AR_OID_OUTLET_CURRENT ".%i", NULL, SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.current.maximum", 0, 0.001, AR_OID_OUTLET_MAXCURRENT ".%i", NULL, SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.realpower", 0, 1.0, AR_OID_OUTLET_ACTIVEPOWER ".%i", NULL, SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.voltage", 0, 1.0, AR_OID_OUTLET_VOLTAGE ".%i", NULL, SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.powerfactor", 0, 0.01, AR_OID_OUTLET_POWERFACTOR ".%i", NULL, SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.power", 0, 1.0, AR_OID_OUTLET_APPARENTPOWER ".%i", NULL, SU_OUTLET, NULL, NULL },
|
|
|
|
/* FIXME:
|
|
* - delay for startup/shutdown sequence
|
|
* - support for Ambient page
|
|
temperatureSensorCount" src="snmp:$sysoid.2.1.0
|
|
ambient.temperature src="snmp:$sysoid.2.2.1.3.$indiceSensor => seems dumb!
|
|
ambient.humidity src="snmp:$sysoid.2.4.1.3.$indiceSensor
|
|
*/
|
|
|
|
/* instant commands. */
|
|
/* Note that load.cycle might be replaced by / mapped on shutdown.reboot */
|
|
/* no counterpart found!
|
|
{ "outlet.load.off", 0, DO_OFF, AR_OID_OUTLET_STATUS ".0", NULL, SU_TYPE_CMD, NULL, NULL },
|
|
{ "outlet.load.on", 0, DO_ON, AR_OID_OUTLET_STATUS ".0", NULL, SU_TYPE_CMD, NULL, NULL },
|
|
{ "outlet.load.cycle", 0, DO_CYCLE, AR_OID_OUTLET_STATUS ".0", NULL, SU_TYPE_CMD, NULL, NULL }, */
|
|
{ "outlet.%i.load.off", 0, DO_OFF, AR_OID_OUTLET_STATUS ".%i", NULL, SU_TYPE_CMD | SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.load.on", 0, DO_ON, AR_OID_OUTLET_STATUS ".%i", NULL, SU_TYPE_CMD | SU_OUTLET, NULL, NULL },
|
|
{ "outlet.%i.load.cycle", 0, DO_CYCLE, AR_OID_OUTLET_STATUS ".%i", NULL, SU_TYPE_CMD | SU_OUTLET, NULL, NULL },
|
|
|
|
/* end of structure. */
|
|
{ NULL, 0, 0, NULL, NULL, 0, NULL, NULL }
|
|
};
|
|
|
|
mib2nut_info_t aphel_genesisII = { "aphel_genesisII", EATON_APHEL_MIB_VERSION, "", APHEL1_OID_MODEL_NAME, eaton_aphel_genesisII_mib };
|
|
mib2nut_info_t aphel_revelation = { "aphel_revelation", EATON_APHEL_MIB_VERSION, "", APHEL2_OID_MODEL_NAME, eaton_aphel_revelation_mib };
|