ifndef::external_title[]
|
|
NUT command and variable naming scheme
|
|
======================================
|
|
endif::external_title[]
|
|
|
|
This is a dump of the standard variables and command names used in NUT.
|
|
Don't use a name with any of the dstate functions unless it exists here.
|
|
|
|
If you need a new variable or command name, contact the Development Team
|
|
first.
|
|
|
|
Put another way: if you make up a name that's not in this list and it
|
|
gets into the tree, and then we come up with a better name later, clients
|
|
that use the undocumented variable will break when it is changed.
|
|
|
|
NOTE: "opaque" means programs should not attempt to parse the value for
|
|
that variable as it may vary greatly from one UPS to the next. These
|
|
strings are best handled directly by the user.
|
|
|
|
Variables
|
|
---------
|
|
|
|
device: General unit information
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
NOTE: some of these data will be redundant with ups.* information
|
|
during a transition period. The ups.* data will then be removed.
|
|
|
|
[options="header"]
|
|
|====================================================================================
|
|
| Name | Description | Example value
|
|
| device.model | Device model | BladeUPS
|
|
| device.mfr | Device manufacturer | Eaton
|
|
| device.serial | Device serial number (opaque string) | WS9643050926
|
|
| device.type | Device type (ups, pdu, scd, psu) | ups
|
|
| device.description | Device description (opaque string) | Some ups
|
|
| device.contact | Device administrator name (opaque string) | John Doe
|
|
| device.location | Device physical location (opaque string) | 1rst floor
|
|
| device.part | Device part number (opaque string) | 123456789
|
|
| device.macaddr | Physical network address of the device | 68:b5:99:f5:89:27
|
|
|=====================================================================================
|
|
|
|
ups: General unit information
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description | Example value
|
|
| ups.status | UPS status | linkdoc:developer-guide[OL,_status_data]
|
|
| ups.alarm | UPS alarms | OVERHEAT
|
|
| ups.time | Internal UPS clock time
|
|
(opaque string) | 12:34
|
|
| ups.date | Internal UPS clock date
|
|
(opaque string) | 01-02-03
|
|
| ups.model | UPS model | SMART-UPS 700
|
|
| ups.mfr | UPS manufacturer | APC
|
|
| ups.mfr.date | UPS manufacturing date
|
|
(opaque string) | 10/17/96
|
|
| ups.serial | UPS serial number (opaque
|
|
string) | WS9643050926
|
|
| ups.vendorid | Vendor ID for USB devices | 0463
|
|
| ups.productid | Product ID for USB devices | 0001
|
|
| ups.firmware | UPS firmware (opaque string) | 50.9.D
|
|
| ups.firmware.aux | Auxiliary device firmware | 4Kx
|
|
| ups.temperature | UPS temperature (degrees C) | 042.7
|
|
| ups.load | Load on UPS (percent) | 023.4
|
|
| ups.load.high | Load when UPS
|
|
switches to overload
|
|
condition ("OVER") (percent) | 100
|
|
| ups.id | UPS system identifier
|
|
(opaque string) | Sierra
|
|
| ups.delay.start | Interval to wait before
|
|
restarting the load
|
|
(seconds) | 0
|
|
| ups.delay.reboot | Interval to wait before
|
|
rebooting the UPS (seconds) | 60
|
|
| ups.delay.shutdown | Interval to wait after
|
|
shutdown with delay command
|
|
(seconds) | 20
|
|
| ups.timer.start | Time before the load will be
|
|
started (seconds) | 30
|
|
| ups.timer.reboot | Time before the load will be
|
|
rebooted (seconds) | 10
|
|
| ups.timer.shutdown | Time before the load will be
|
|
shutdown (seconds) | 20
|
|
| ups.test.interval | Interval between self tests
|
|
(seconds) | 1209600 (two weeks)
|
|
| ups.test.result | Results of last self test
|
|
(opaque string) | Bad battery pack
|
|
| ups.display.language | Language to use on front
|
|
panel (*** opaque) | E
|
|
| ups.contacts | UPS external contact sensors
|
|
(*** opaque) | F0
|
|
| ups.efficiency | Efficiency of the UPS (ratio
|
|
of the output current on the
|
|
input current) (percent) | 95
|
|
| ups.power | Current value of apparent
|
|
power (Volt-Amps) | 500
|
|
| ups.power.nominal | Nominal value of apparent
|
|
power (Volt-Amps) | 500
|
|
| ups.realpower | Current value of real
|
|
power (Watts) | 300
|
|
| ups.realpower.nominal | Nominal value of real
|
|
power (Watts) | 300
|
|
| ups.beeper.status | UPS beeper status
|
|
(enabled, disabled or muted) | enabled
|
|
| ups.type | UPS type (*** opaque) | offline
|
|
| ups.watchdog.status | UPS watchdog status
|
|
(enabled or disabled) | disabled
|
|
| ups.start.auto | UPS starts when mains is
|
|
(re)applied | yes
|
|
| ups.start.battery | Allow to start UPS from
|
|
battery | yes
|
|
| ups.start.reboot | UPS coldstarts from battery
|
|
(enabled or disabled) | yes
|
|
|===============================================================================
|
|
|
|
NOTE: When present, the value of *ups.start.auto* has an impact on shutdown.*
|
|
commands. For the sake of coherence, shutdown commands will set *ups.start.auto*
|
|
to the right value before issuing the command. Ie, shutdown.stayoff will first
|
|
set *ups.start.auto* to *no*, while shutdown.return will set it to *yes*.
|
|
|
|
input: Incoming line/power information
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description | Example value
|
|
| input.voltage | Input voltage | 121.5
|
|
| input.voltage.maximum | Maximum incoming voltage seen | 130
|
|
| input.voltage.minimum | Minimum incoming voltage seen | 100
|
|
| input.voltage.nominal | Nominal input voltage | 120
|
|
| input.voltage.extended | Extended input voltage range | no
|
|
| input.transfer.reason | Reason for last transfer
|
|
to battery (*** opaque) | T
|
|
| input.transfer.low | Low voltage transfer point | 91
|
|
| input.transfer.high | High voltage transfer point | 132
|
|
| input.transfer.low.min | smallest settable low
|
|
voltage transfer point | 85
|
|
| input.transfer.low.max | greatest settable low
|
|
voltage transfer point | 95
|
|
| input.transfer.high.min | smallest settable high
|
|
voltage transfer point | 131
|
|
| input.transfer.high.max | greatest settable high
|
|
voltage transfer point | 136
|
|
| input.sensitivity | Input power sensitivity | H (high)
|
|
| input.quality | Input power quality (***
|
|
opaque) | FF
|
|
| input.current | Input current (A) | 4.25
|
|
| input.current.nominal | Nominal input current (A) | 5.0
|
|
| input.frequency | Input line frequency (Hz) | 60.00
|
|
| input.frequency.nominal | Nominal input line
|
|
frequency (Hz) | 60
|
|
| input.frequency.low | Input line frequency low (Hz) | 47
|
|
| input.frequency.high | Input line frequency high (Hz) | 63
|
|
| input.frequency.extended | Extended input frequency range | no
|
|
| input.transfer.boost.low | Low voltage boosting
|
|
transfer point | 190
|
|
| input.transfer.boost.high | High voltage boosting
|
|
transfer point | 210
|
|
| input.transfer.trim.low | Low voltage trimming
|
|
transfer point | 230
|
|
| input.transfer.trim.high | High voltage trimming
|
|
transfer point | 240
|
|
|===============================================================================
|
|
|
|
|
|
output: Outgoing power/inverter information
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description | Example value
|
|
| output.voltage | Output voltage (V) | 120.9
|
|
| output.voltage.nominal | Nominal output voltage (V) | 120
|
|
| output.frequency | Output frequency (Hz) | 59.9
|
|
| output.frequency.nominal | Nominal output frequency (Hz) | 60
|
|
| output.current | Output current (A) | 4.25
|
|
| output.current.nominal | Nominal output current (A) | 5.0
|
|
|===============================================================================
|
|
|
|
Three-phase additions
|
|
~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
The additions for three-phase measurements would produce a very long table
|
|
due to all the combinations that are possible, so these additions are
|
|
broken down to their base components.
|
|
|
|
Phase Count Determination
|
|
^^^^^^^^^^^^^^^^^^^^^^^^^
|
|
input.phases (3 for three-phase, absent or 1 for 1phase)
|
|
output.phases (as for input.phases)
|
|
|
|
DOMAINs
|
|
^^^^^^^
|
|
Any input or output is considered a valid DOMAIN.
|
|
|
|
input (should really be called input.mains, but keep this for compat)
|
|
input.bypass
|
|
input.servicebypass
|
|
|
|
output (should really be called output.load, but keep this for compat)
|
|
output.bypass
|
|
output.inverter
|
|
output.servicebypass
|
|
|
|
Specification (SPEC)
|
|
^^^^^^^^^^^^^^^^^^^^
|
|
|
|
Voltage, current, frequency, etc are considered to be a specification of
|
|
the measurement.
|
|
|
|
With this notation, the old 1phase naming scheme becomes DOMAIN.SPEC
|
|
Example: `input.current`
|
|
|
|
CONTEXT
|
|
^^^^^^^
|
|
|
|
When in three-phase mode, we need some way to specify the target for most
|
|
measurements in more detail. We call this the CONTEXT.
|
|
|
|
With this notation, the naming scheme becomes DOMAIN.CONTEXT.SPEC when
|
|
in three-phase mode.
|
|
Example: `input.L1.current`
|
|
|
|
Valid CONTEXTs
|
|
^^^^^^^^^^^^^^
|
|
|
|
L1-L2 \
|
|
L2-L3 \
|
|
L3-L1 for voltage measurements
|
|
L1-N /
|
|
L2-N /
|
|
L3-N /
|
|
|
|
L1 \
|
|
L2 for currrent and power measurements
|
|
L3 /
|
|
N - for current measurement
|
|
|
|
Valid SPECs
|
|
^^^^^^^^^^^
|
|
|
|
Valid with/without context (ie. per phase or aggregated/averaged)
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description
|
|
| current | Current (A)
|
|
| current.maximum | Maximum seen current (A)
|
|
| current.minimum | Minimum seen current (A)
|
|
| current.peak | Peak current
|
|
| voltage | Voltage (V)
|
|
| voltage.nominal | Nominal voltage (V)
|
|
| voltage.maximum | Maximum seen voltage (V)
|
|
| voltage.minimum | Minimum seen voltage (V)
|
|
| power | Apparent power (VA)
|
|
| power.maximum | Maximum seen apparent power (VA)
|
|
| power.minimum | Maximum seen apparent power (VA)
|
|
| power.percent | Percentage of apparent power related to maximum load
|
|
| power.maximum.percent | Max seen percentage of apparent power
|
|
| power.minimum.percent | Min seen percentage of apparent power
|
|
| realpower | Real power (W)
|
|
| powerfactor | Power Factor (dimensionless value between 0.00 and 1.00)
|
|
| crestfactor | Crest Factor (dimensionless value greater or equal to 1)
|
|
|===============================================================================
|
|
|
|
Valid without context (ie. aggregation of all phases):
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description
|
|
| frequency | Frequency (Hz)
|
|
| frequency.nominal | Nominal frequency (Hz)
|
|
|===============================================================================
|
|
|
|
EXAMPLES
|
|
~~~~~~~~
|
|
|
|
Partial Three phase - Three phase example:
|
|
|
|
input.phases: 3
|
|
input.frequency: 50.0
|
|
input.L1.current: 133.0
|
|
input.bypass.L1-L2.voltage: 398.3
|
|
output.phases: 3
|
|
output.L1.power: 35700
|
|
output.powerfactor: 0.82
|
|
|
|
Partial Three phase - One phase example:
|
|
|
|
input.phases: 3
|
|
input.L2.current: 48.2
|
|
input.N.current: 3.4
|
|
input.L3-L1.voltage: 405.4
|
|
input.frequency: 50.1
|
|
output.phases: 1
|
|
output.current: 244.2
|
|
output.voltage: 120
|
|
output.frequency.nominal: 60.0
|
|
|
|
battery: Any battery details
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description | Example value
|
|
| battery.charge | Battery charge (percent) | 100.0
|
|
| battery.charge.low | Remaining battery level when
|
|
UPS switches to LB (percent) | 20
|
|
| battery.charge.restart | Minimum battery level for
|
|
UPS restart after power-off | 20
|
|
| battery.charge.warning | Battery level when UPS switches
|
|
to "Warning" state (percent) | 50
|
|
| battery.voltage | Battery voltage (V) | 24.84
|
|
| battery.voltage.nominal | Nominal battery voltage (V) | 024
|
|
| battery.voltage.low | Minimum battery voltage, that
|
|
triggers FSD status | 21,52
|
|
| battery.voltage.high | Maximum battery voltage
|
|
(Ie battery.charge = 100) | 26,9
|
|
| battery.capacity | Battery capacity (Ah) | 7.2
|
|
| battery.current | Battery current (A) | 1.19
|
|
| battery.temperature | Battery temperature (degrees C) | 050.7
|
|
| battery.runtime | Battery runtime (seconds) | 1080
|
|
| battery.runtime.low | Remaining battery runtime when
|
|
UPS switches to LB (seconds) | 180
|
|
| battery.runtime.restart | Minimum battery runtime for UPS
|
|
restart after power-off (seconds) | 120
|
|
| battery.alarm.threshold | Battery alarm threshold | 0 (immediate)
|
|
| battery.date | Battery change date (opaque string) | 11/14/00
|
|
| battery.mfr.date | Battery manufacturing date
|
|
(opaque string) | 2005/04/02
|
|
| battery.packs | Number of battery packs | 001
|
|
| battery.packs.bad | Number of bad battery packs | 000
|
|
| battery.type | Battery chemistry (opaque
|
|
string) | PbAc
|
|
| battery.protection | Prevent deep discharge of
|
|
battery | yes
|
|
| battery.energysave | Switch off when running on
|
|
battery and no/low load | no
|
|
|===============================================================================
|
|
|
|
|
|
ambient: Conditions from external probe equipment
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description | Example value
|
|
| ambient.temperature | Ambient temperature
|
|
(degrees C) | 25.40
|
|
| ambient.temperature.alarm | Temperature alarm
|
|
(enabled/disabled) | enabled
|
|
| ambient.temperature.high | Temperature threshold high
|
|
(degrees C) | 40
|
|
| ambient.temperature.low | Temperature threshold low
|
|
(degrees C) | 5
|
|
| ambient.temperature.maximum | Maximum temperature seen
|
|
(degrees C) | 37.6
|
|
| ambient.temperature.minimum | Minimum temperature seen
|
|
(degrees C) | 18.1
|
|
| ambient.humidity | Ambient relative humidity
|
|
(percent) | 038.8
|
|
| ambient.humidity.alarm | Relative humidity alarm
|
|
(enabled/disabled) | enabled
|
|
| ambient.humidity.high | Relative humidity
|
|
threshold high (percent) | 80
|
|
| ambient.humidity.low | Relative humidity
|
|
threshold high (percent) | 10
|
|
| ambient.humidity.maximum | Maximum relative humidity
|
|
seen (percent) | 60
|
|
| ambient.humidity.minimum | Minimum relative humidity
|
|
seen (percent) | 13
|
|
|===============================================================================
|
|
|
|
|
|
outlet: Smart outlet management
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
NOTE: *n* stands for the outlet index. For more information, refer to the
|
|
NUT outlets management and PDU notes chapter of the user manual.
|
|
A special case is "outlet.0" which is equivalent to "outlet", and
|
|
represent the whole set of outlets of the device.
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description | Example value
|
|
| outlet.n.id | Outlet system identifier
|
|
(opaque string) | 1
|
|
| outlet.n.desc | Outlet description
|
|
(opaque string) | Main outlet
|
|
| outlet.n.switch | Outlet switch control
|
|
(on/off) | on
|
|
| outlet.n.status | Outlet switch status
|
|
(on/off) | on
|
|
| outlet.n.switchable | Outlet switch ability
|
|
(yes/no) | yes
|
|
| outlet.n.autoswitch.charge.low | Remaining battery level to
|
|
power off this outlet
|
|
(percent) | 80
|
|
| outlet.n.battery.charge.low | Remaining battery level to
|
|
power off this outlet
|
|
(percent) | 80
|
|
| outlet.n.delay.shutdown | Interval to wait before
|
|
shutting down this outlet
|
|
(seconds) | 180
|
|
| outlet.n.delay.start | Interval to wait before
|
|
restarting this outlet
|
|
(seconds) | 120
|
|
| outlet.n.timer.shutdown | Time before the outlet load
|
|
will be shutdown (seconds) | 20
|
|
| outlet.n.timer.start | Time before the outlet load
|
|
will be started (seconds) | 30
|
|
| outlet.n.current | Current (A) | 0.19
|
|
| outlet.n.current.maximum | Maximum seen current (A) | 0.56
|
|
| outlet.n.realpower | Current value of real
|
|
power (W) | 28
|
|
| outlet.n.voltage | Voltage (V) | 247.0
|
|
| outlet.n.powerfactor | Power Factor
|
|
(dimensionless value
|
|
between 0 and 1) | 0.85
|
|
| outlet.n.crestfactor | Crest Factor
|
|
(dimensionless, equal
|
|
to or greater than 1) | 1.41
|
|
| outlet.n.power | Apparent power (VA) | 46
|
|
|===============================================================================
|
|
|
|
driver: Internal driver information
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description | Example value
|
|
| driver.name | Driver name | usbhid-ups
|
|
| driver.version | Driver version (NUT release) | X.Y.Z
|
|
| driver.version.internal | Internal driver version
|
|
(if tracked separately) | 1.23.45
|
|
| driver.parameter.xxx | Parameter xxx (ups.conf or
|
|
cmdline -x) setting | (varies)
|
|
| driver.flag.xxx | Flag xxx (ups.conf or
|
|
cmdline -x) status | enabled (or absent)
|
|
|===============================================================================
|
|
|
|
server: Internal server information
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
[options="header"]
|
|
|===============================================================================
|
|
| Name | Description | Example value
|
|
| server.info | Server information | Network UPS Tools upsd vX.Y.Z -
|
|
http://www.networkupstools.org/
|
|
| server.version | Server version | X.Y.Z
|
|
|===============================================================================
|
|
|
|
Instant commands
|
|
----------------
|
|
|
|
[options="header"]
|
|
|========================================================================
|
|
| Name | Description
|
|
| load.off | Turn off the load immediately
|
|
| load.on | Turn on the load immediately
|
|
| load.off.delay | Turn off the load possibly after a delay
|
|
| load.on.delay | Turn on the load possibly after a delay
|
|
| shutdown.return | Turn off the load possibly after a delay
|
|
and return when power is back
|
|
| shutdown.stayoff | Turn off the load possibly after a delay
|
|
and remain off even if power returns
|
|
| shutdown.stop | Stop a shutdown in progress
|
|
| shutdown.reboot | Shut down the load briefly while rebooting the UPS
|
|
| shutdown.reboot.graceful | After a delay, shut down the load briefly
|
|
while rebooting the UPS
|
|
| test.panel.start | Start testing the UPS panel
|
|
| test.panel.stop | Stop a UPS panel test
|
|
| test.failure.start | Start a simulated power failure
|
|
| test.failure.stop | Stop simulating a power failure
|
|
| test.battery.start | Start a battery test
|
|
| test.battery.start.quick | Start a "quick" battery test
|
|
| test.battery.start.deep | Start a "deep" battery test
|
|
| test.battery.stop | Stop the battery test
|
|
| calibrate.start | Start runtime calibration
|
|
| calibrate.stop | Stop runtime calibration
|
|
| bypass.start | Put the UPS in bypass mode
|
|
| bypass.stop | Take the UPS out of bypass mode
|
|
| reset.input.minmax | Reset minimum and maximum input voltage status
|
|
| reset.watchdog | Reset watchdog timer (forced reboot of load)
|
|
| beeper.enable | Enable UPS beeper/buzzer
|
|
| beeper.disable | Disable UPS beeper/buzzer
|
|
| beeper.mute | Temporarily mute UPS beeper/buzzer
|
|
| beeper.toggle | Toggle UPS beeper/buzzer
|
|
| outlet.n.shutdown.return | Turn off the outlet possibly after a delay
|
|
and return when power is back
|
|
| outlet.n.load.off | Turn off the outlet immediately
|
|
| outlet.n.load.on | Turn on the outlet immediately
|
|
| outlet.n.load.cycle | Power cycle the outlet immediately
|
|
|========================================================================
|