.TH mge\-shut 8 "Thu Nov 19 2009" "" "Network UPS Tools (NUT)"
|
|
.SH NAME
|
|
mge\(hyshut, newmge\(hyshut \- Driver for SHUT Protocol UPS equipment
|
|
.SH NOTE
|
|
This man page only documents the hardware\(hyspecific features of the
|
|
mge\(hyshut driver. For information about the core driver, see
|
|
\fBnutupsdrv\fR(8).
|
|
|
|
.SH SUPPORTED HARDWARE
|
|
mge\(hyshut support all recent Eaton, MGE and Dell UPS models which use the SHUT
|
|
(Serial HID UPS Transfer) protocol.
|
|
|
|
Older MGE models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U\(hyTalk
|
|
protocol and should use the mge\(hyutalk driver.
|
|
|
|
.SH EXTRA ARGUMENTS
|
|
This driver supports the following optional settings in the
|
|
\fBups.conf\fR(5):
|
|
|
|
.IP "lowbatt=\fInum\fR"
|
|
Set the low battery warning threshold at which shutdown is initiated by
|
|
\fBupsmon\fR(8).
|
|
The factory default value is 30 (in percentage), and only be settable
|
|
depending on the exact model.
|
|
|
|
.IP "offdelay=\fInum\fR"
|
|
Set the timer before the UPS is turned off after the kill power command is
|
|
sent (via the \fI\-k\fR switch).
|
|
The default value is 20 (in seconds), and MUST BE LOWER than ondelay.
|
|
|
|
.IP "ondelay=\fInum\fR"
|
|
Set the timer for the UPS to switch on in case the power returns after the
|
|
kill power command had been sent but before the actual switch off. This
|
|
ensures the machines connected to the UPS are, in all cases, rebooted after
|
|
a power failure.
|
|
The default value is 3 (in 10 seconds units, which means 30 seconds),
|
|
and MUST BE GREATER than offdelay.
|
|
|
|
.IP "notification=\fInum\fR"
|
|
Set notification type to 1 (no), 2 (light) or 3 (yes).
|
|
The default value is 3 (yes) because of some early Ellipse models which
|
|
need it.
|
|
|
|
.SH KNOWN ISSUES
|
|
.SS "Pulsar Ellipse S: Repetitive stale status \(hy Loss of communication"
|
|
|
|
Several users have reported "data stale" errors with Pulsar Ellipse
|
|
equipment. This lasts around 10 seconds and happens once every few hours.
|
|
This is due to the fact that the SHUT protocol is verbose, and the driver
|
|
sometimes does not handle all of it during the usual polling interval in
|
|
upsd. To solve this problem, change the value of MAXAGE to 25 in
|
|
upsd.conf. Also add "notification=3" in ups.conf (thanks to Julien
|
|
Lesaint and Fabien).
|
|
|
|
|
|
.SH AUTHOR
|
|
Arnaud Quette <arnaud.quette@free.fr> or <arnaud.quette@mgeups.com>
|
|
|
|
Philippe Marzouk <philm@users.sourceforge.net>
|
|
|
|
.SH SEE ALSO
|
|
|
|
.SS The core driver:
|
|
\fBnutupsdrv\fR(8)
|
|
|
|
.SS Internet resources:
|
|
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|
|
|
|
MGE UPS SYSTEMS SHUT protocol information:
|
|
http://random.networkupstools.org/protocols/mge/
|