nut-debian/drivers/xppc-mib.c
2014-04-22 20:39:47 +02:00

127 lines
4.8 KiB
C

/* xppc-mib.c - subdriver to monitor XPPC SNMP devices with NUT
*
* Copyright (C)
* 2011 - 2012 Arnaud Quette <arnaud.quette@free.fr>
* 2014 Charles Lepple <clepple+nut@gmail.com>
*
* Note: this subdriver was initially generated as a "stub" by the
* scripts/subdriver/gen-snmp-subdriver.sh script.
*
* This program is free software; you can redistribute it and/or modify
* it under the terms of the GNU General Public License as published by
* the Free Software Foundation; either version 2 of the License, or
* (at your option) any later version.
*
* This program is distributed in the hope that it will be useful,
* but WITHOUT ANY WARRANTY; without even the implied warranty of
* MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
* GNU General Public License for more details.
*
* You should have received a copy of the GNU General Public License
* along with this program; if not, write to the Free Software
* Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
*/
#include "xppc-mib.h"
#define XPPC_MIB_VERSION "0.2"
#define XPPC_SYSOID ".1.3.6.1.4.1.935"
/* To create a value lookup structure (as needed on the 2nd line of the example
* below), use the following kind of declaration, outside of the present snmp_info_t[]:
* static info_lkp_t onbatt_info[] = {
* { 1, "OB" },
* { 2, "OL" },
* { 0, "NULL" }
* };
*/
/* upsBaseBatteryStatus */
static info_lkp_t xpcc_onbatt_info[] = {
{ 1, "" }, /* unknown */
{ 2, "" }, /* batteryNormal */
{ 3, "LB" } /* batteryLow */
};
/*
upsBaseOutputStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
onLine(2),
onBattery(3),
onBoost(4),
sleeping(5),
onBypass(6),
rebooting(7),
standBy(8),
onBuck(9) }
*/
static info_lkp_t xpcc_power_info[] = {
{ 1, "" }, /* unknown */
{ 2, "OL" }, /* onLine */
{ 3, "OB" }, /* onBattery */
{ 4, "OL BOOST" }, /* onBoost */
{ 5, "OFF" }, /* sleeping */
{ 6, "BYPASS"}, /* onBypass */
{ 7, "" }, /* rebooting */
{ 8, "OFF" }, /* standBy */
{ 9, "OL TRIM"} /* onBuck */
};
/* XPPC Snmp2NUT lookup table */
static snmp_info_t xppc_mib[] = {
/* Data format:
* { info_type, info_flags, info_len, OID, dfl, flags, oid2info, setvar },
*
* info_type: NUT INFO_ or CMD_ element name
* info_flags: flags to set in addinfo
* info_len: length of strings if STR
* cmd value if CMD, multiplier otherwise
* OID: SNMP OID or NULL
* dfl: default value
* flags: snmp-ups internal flags (FIXME: ...)
* oid2info: lookup table between OID and NUT values
* setvar: variable to set for SU_FLAG_SETINT
*
* Example:
* { "input.voltage", 0, 0.1, ".1.3.6.1.4.1.705.1.6.2.1.2.1", "", SU_INPUT_1, NULL },
* { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.705.1.7.3.0", "", SU_FLAG_OK | SU_STATUS_BATT, onbatt_info },
*
* To create a value lookup structure (as needed on the 2nd line), use the
* following kind of declaration, outside of the present snmp_info_t[]:
* static info_lkp_t onbatt_info[] = {
* { 1, "OB" },
* { 2, "OL" },
* { 0, "NULL" }
* };
*/
{ "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "Tripp Lite / Phoenixtec",
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
/* upsBaseIdentModel.0 = STRING: "Intelligent" */
{ "ups.model", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.935.1.1.1.1.1.1.0", "Generic Phoenixtec SNMP device", SU_FLAG_OK, NULL },
/* upsBaseBatteryStatus.0 = INTEGER: batteryNormal(2) */
{ "ups.status", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.935.1.1.1.2.1.1.0", "", SU_STATUS_BATT | SU_TYPE_INT | SU_FLAG_OK, xpcc_onbatt_info },
/* upsSmartBatteryCapacity.0 = INTEGER: 100 */
{ "battery.charge", 0, 1, ".1.3.6.1.4.1.935.1.1.1.2.2.1.0", NULL, SU_TYPE_INT | SU_FLAG_OK, NULL },
/* upsSmartBatteryTemperature.0 = INTEGER: 260 */
{ "ups.temperature", 0, 0.1, ".1.3.6.1.4.1.935.1.1.1.2.2.3.0", NULL, SU_TYPE_INT | SU_FLAG_OK, NULL },
/* upsSmartInputLineVoltage.0 = INTEGER: 1998 */
{ "input.voltage", 0, 0.1, ".1.3.6.1.4.1.935.1.1.1.3.2.1.0", NULL, SU_TYPE_INT | SU_FLAG_OK, NULL },
/* upsBaseOutputStatus.0 = INTEGER: onLine(2) */
{ "ups.status", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.935.1.1.1.4.1.1.0", "", SU_TYPE_INT | SU_STATUS_PWR, xpcc_power_info },
/* upsSmartOutputVoltage.0 = INTEGER: 2309 */
{ "output.voltage", 0, 0.1, ".1.3.6.1.4.1.935.1.1.1.4.2.1.0", NULL, SU_TYPE_INT | SU_FLAG_OK, NULL },
/* upsSmartOutputFrequency.0 = INTEGER: 500 */
{ "output.frequency", 0, 0.1, ".1.3.6.1.4.1.935.1.1.1.4.2.2.0", NULL, SU_TYPE_INT | SU_FLAG_OK, NULL },
/* upsSmartOutputLoad.0 = INTEGER: 7 */
{ "ups.load", 0, 1, ".1.3.6.1.4.1.935.1.1.1.4.2.3.0", NULL, SU_TYPE_INT | SU_FLAG_OK, NULL },
/* end of structure. */
{ NULL, 0, 0, NULL, NULL, 0, NULL }
};