125 lines
4.3 KiB
Groff
125 lines
4.3 KiB
Groff
'\" t
|
|
.\" Title: apcsmart-old
|
|
.\" Author: [see the "AUTHOR" section]
|
|
.\" Generator: DocBook XSL Stylesheets v1.76.1 <http://docbook.sf.net/>
|
|
.\" Date: 02/15/2014
|
|
.\" Manual: NUT Manual
|
|
.\" Source: Network UPS Tools 2.7.1.5
|
|
.\" Language: English
|
|
.\"
|
|
.TH "APCSMART\-OLD" "8" "02/15/2014" "Network UPS Tools 2\&.7\&.1\&." "NUT Manual"
|
|
.\" -----------------------------------------------------------------
|
|
.\" * Define some portability stuff
|
|
.\" -----------------------------------------------------------------
|
|
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
.\" http://bugs.debian.org/507673
|
|
.\" http://lists.gnu.org/archive/html/groff/2009-02/msg00013.html
|
|
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
.ie \n(.g .ds Aq \(aq
|
|
.el .ds Aq '
|
|
.\" -----------------------------------------------------------------
|
|
.\" * set default formatting
|
|
.\" -----------------------------------------------------------------
|
|
.\" disable hyphenation
|
|
.nh
|
|
.\" disable justification (adjust text to left margin only)
|
|
.ad l
|
|
.\" -----------------------------------------------------------------
|
|
.\" * MAIN CONTENT STARTS HERE *
|
|
.\" -----------------------------------------------------------------
|
|
.SH "NAME"
|
|
apcsmart-old \- Driver for American Power Conversion Smart Protocol UPS equipment
|
|
.SH "SYNOPSIS"
|
|
.sp
|
|
\fBapcsmart\-old\fR \-h
|
|
.sp
|
|
\fBapcsmart\-old\fR \-a \fIUPS_NAME\fR [\fIOPTIONS\fR]
|
|
.if n \{\
|
|
.sp
|
|
.\}
|
|
.RS 4
|
|
.it 1 an-trap
|
|
.nr an-no-space-flag 1
|
|
.nr an-break-flag 1
|
|
.br
|
|
.ps +1
|
|
\fBNote\fR
|
|
.ps -1
|
|
.br
|
|
.sp
|
|
This man page only documents the hardware\-specific features of the apcsmart\-old driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&.
|
|
.sp .5v
|
|
.RE
|
|
.SH "SUPPORTED HARDWARE"
|
|
.sp
|
|
apcsmart\-old should recognize all recent APC models that use a serial protocol at 2400 bps\&. This is primarily the Smart\-UPS, Matrix\-UPS and Back\-UPS Pro lines\&.
|
|
.sp
|
|
The driver attempts to support every bell and whistle of the APC reporting interface, whether or not this is strictly sensible\&.
|
|
.sp
|
|
Some older hardware may only report a handful of variables\&. This is usually not a bug\(emthey just don\(cqt support anything else\&.
|
|
.SH "CABLING"
|
|
.sp
|
|
This driver expects to see a 940\-0024C cable or a clone by default\&. You can switch to the 940\-0095B dual\-mode cable support with the cable= definition described below\&.
|
|
.sp
|
|
If your 940\-0024C cable is broken or missing, use this diagram to build a clone:
|
|
.sp
|
|
http://www\&.networkupstools\&.org/cables/940\-0024C\&.jpg
|
|
.SH "EXTRA ARGUMENTS"
|
|
.sp
|
|
This driver supports the following optional settings in the \fBups.conf\fR(5):
|
|
.PP
|
|
\fBcable=940\-0095B\fR
|
|
.RS 4
|
|
Configure the serial port for the APC 940\-0095B dual\-mode cable\&.
|
|
.RE
|
|
.PP
|
|
\fBsdtype=\fR\fInum\fR
|
|
.RS 4
|
|
Use shutdown type
|
|
\fInum\fR, according to this table:
|
|
.PP
|
|
0
|
|
.RS 4
|
|
soft shutdown or powerdown, depending on battery status
|
|
.RE
|
|
.PP
|
|
1
|
|
.RS 4
|
|
soft shutdown followed by powerdown
|
|
.RE
|
|
.PP
|
|
2
|
|
.RS 4
|
|
instant power off
|
|
.RE
|
|
.PP
|
|
3
|
|
.RS 4
|
|
power off with grace period
|
|
.RE
|
|
.PP
|
|
4
|
|
.RS 4
|
|
"force OB" hack method for CS 350
|
|
.RE
|
|
.RE
|
|
.sp
|
|
Modes 0 and 1 will power up the load when power returns\&. Modes 2 and 3 will keep the load turned off when the power returns\&.
|
|
.sp
|
|
Mode 4 exploits an oddity in the CS 350 models since they only seem to support the S command, but then only when running on battery\&. As a result, the driver will force the UPS to go on battery if necessary before sending the shutdown command\&. This ensures that the load gets reset\&.
|
|
.SH "BUGS"
|
|
.sp
|
|
Some older APC UPS models return bogus data in the status register during a front panel test\&. This is usually detected and discarded, but some other unexpected values have occasionally slipped through\&.
|
|
.sp
|
|
APC UPS models with both USB and serial ports require a power cycle when switching from USB communication to serial, and perhaps vice versa\&.
|
|
.SH "AUTHOR"
|
|
.sp
|
|
Nigel Metheringham <Nigel\&.Metheringham@Intechnology\&.co\&.uk> (drawing heavily on the original apcsmart driver by Russell Kroll)\&. This driver was called newapc for a time and was renamed in the 1\&.5 series\&. In 2\&.6\&.2 the driver was renamed to apcsmart\-old, being superseded by updated version with new features\&.
|
|
.SH "SEE ALSO"
|
|
.SS "The core driver:"
|
|
.sp
|
|
\fBnutupsdrv\fR(8)
|
|
.SS "Internet resources:"
|
|
.sp
|
|
The NUT (Network UPS Tools) home page: http://www\&.networkupstools\&.org/
|