GENERIC_MODBUS(8)
|
|
=================
|
|
|
|
NAME
|
|
----
|
|
|
|
generic_modbus - Driver for contact (direct) signal UPS devices connected via modbus remote I/O gateways
|
|
|
|
SYNOPSIS
|
|
--------
|
|
|
|
*generic_modbus* -h
|
|
|
|
*generic_modbus* -a 'DEVICE_NAME' ['OPTIONS']
|
|
|
|
NOTE: This man page only documents the specific features of the *generic_modbus*
|
|
driver. For information about the core driver, see linkman:nutupsdrv[8].
|
|
|
|
SUPPORTED HARDWARE
|
|
------------------
|
|
|
|
This is a generic modbus driver expected to work with contact (direct) signal
|
|
UPS devices, connected via modbus RIO (remote I/O) either serial or TCP/IP.
|
|
|
|
The driver has been tested against PULS UPS (model UB40.241)
|
|
via MOXA ioLogikR1212 (RS485) and ioLogikE1212 (TCP/IP).
|
|
|
|
More information about this UPS can be found here: ::
|
|
https://products.pulspower.com/ca/ubc10-241-n1.html
|
|
|
|
More information about Moxa ioLogik R1212, E1212 can be found here: ::
|
|
https://www.moxa.com/en/products/industrial-edge-connectivity/controllers-and-ios
|
|
|
|
The PULS UPS UB40.241 supports the following signals:
|
|
----
|
|
Ready contact (DO) <--> HB
|
|
Buffering contact (DO) <--> OL | OB
|
|
Battery-low (DO) <--> LB
|
|
Replace Battery (DO) <--> RB
|
|
Inhibit (DI) <--> FSD
|
|
----
|
|
|
|
Digital port direction (DI/DO) assumes the device perspective
|
|
|
|
The driver's concept is to map the UPS states (as defined in NUT) onto
|
|
UPS contacts' states. The driver has an extended configuration interface
|
|
implemented using variables defined in ups.conf.
|
|
|
|
HARDWARE INTERCONNECTION
|
|
------------------------
|
|
|
|
The commission of modbus remote I/O server as well as UPS device is carried
|
|
out following the corresponding instruction manuals. The following figure
|
|
depicts the anticipated communication path and hardware interconnection:
|
|
----
|
|
+------+ +----------------+ +------------+ +------------+
|
|
| UPSD | <---> | GENERIC_MODBUS | <---> | MODBUS RIO | <---> | UPS DEVICE |
|
|
+------+ (1) +----------------+ (2) +------------+ (3) +------------+
|
|
| |
|
|
+-------------------+
|
|
HOST CONTROLLER
|
|
|
|
(1) Unix IPC
|
|
(2) RS232 | TCP/IP
|
|
(3) contacts
|
|
----
|
|
|
|
EXTRA ARGUMENTS
|
|
---------------
|
|
|
|
This driver supports the following optional settings in the
|
|
linkman:ups.conf[5] file:
|
|
|
|
Generic:
|
|
~~~~~~~
|
|
|
|
*device_mfr*='value'::
|
|
A string specifying the manufacturer of the UPS device (default UNKNOWN).
|
|
|
|
*device_model*='value'::
|
|
A string specifying the model of the UPS device (default UNKNOWN).
|
|
|
|
Serial:
|
|
~~~~~~
|
|
|
|
*ser_baud_rate*='value'::
|
|
A integer specifying the serial port baud rate (default 9600).
|
|
|
|
*ser_data_bit*='value'::
|
|
A integer specifying the serial port data bit (default 8).
|
|
|
|
*ser_parity*='value'::
|
|
A character specifying the serial port parity (default N).
|
|
|
|
*ser_stop_bit*='value'::
|
|
An integer specifying the serial port stop bit (default 1).
|
|
|
|
Modbus:
|
|
~~~~~~
|
|
|
|
*rio_slave_id*='value'::
|
|
An integer specifying the RIO modbus slave ID (default 1).
|
|
|
|
States (X = OL, OB, LB, HB, RB, CHRG, DISCHRG, FSD)
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
*<X>_addr*='value'::
|
|
A number specifying the modbus address for the X state.
|
|
|
|
*<X>_regtype*='value'::
|
|
A number specifying the modbus register type for the X state
|
|
Default values: ::
|
|
+
|
|
----
|
|
1 for X = OL, OB, LB ,HB, RB, CHRG, DISCHRG
|
|
0 for X = FSD
|
|
----
|
|
Valid values: ::
|
|
+
|
|
----
|
|
0:COIL, 1:INPUT_B, 2:INPUT_R, 3:HOLDING
|
|
----
|
|
|
|
*<X>_noro*='value'::
|
|
A number specifying the contact configuration for the X state (default 1).
|
|
Valid values: ::
|
|
+
|
|
----
|
|
0:NC, 1:NO
|
|
----
|
|
+
|
|
NOTE: NO stands for normally open and NC for normally closed contact
|
|
|
|
Shutdown
|
|
~~~~~~~~
|
|
|
|
*FSD_pulse_duration*='value'::
|
|
A number specifying the duration in ms for the inhibit pulse.
|
|
If it's not defined, signal has only one transition depending
|
|
on FSD_noro configuration.
|
|
+
|
|
Examples for FSD signal configuration:
|
|
----
|
|
FSD_noro = 1
|
|
FSD_pulse_duration = 150
|
|
|
|
+-----+
|
|
| |
|
|
inhibit pulse >-----+ +------------------>
|
|
<--->
|
|
150ms
|
|
|
|
|
|
FSD_noro = 0
|
|
|
|
inhibit pulse >-----+
|
|
|
|
|
+------------------------>
|
|
|
|
----
|
|
|
|
CONFIGURATION
|
|
-------------
|
|
|
|
Here is an example of generic_modbus driver configuration in *ups.conf* file:
|
|
----
|
|
[generic_modbus]
|
|
driver = generic_modbus
|
|
port = /dev/ttyUSB0
|
|
desc = "generic ups driver"
|
|
# device info
|
|
device_mfr = "PULS"
|
|
device_model = "UB40.241"
|
|
# serial settings
|
|
ser_baud_rate = 9600
|
|
ser_parity = N
|
|
ser_data_bit = 8
|
|
ser_stop_bit = 1
|
|
# modbus slave id
|
|
rio_slave_id = 5
|
|
# UPS signal state attributes
|
|
OB_addr = 0x0
|
|
OB_regtype = 1
|
|
OB_noro = 0
|
|
LB_addr = 0x1
|
|
LB_regtype = 1
|
|
HB_addr = 0x2
|
|
HB_regtype = 1
|
|
RB_addr = 0x3
|
|
RB_regtype = 1
|
|
FSD_addr = 0x0
|
|
FSD_regtype = 0
|
|
FSD_pulse_duration = 150
|
|
----
|
|
|
|
INSTANT COMMANDS
|
|
----------------
|
|
|
|
This driver support the following instant commands:
|
|
|
|
load.off::
|
|
executes "instant poweroff"
|
|
|
|
INSTALLATION
|
|
------------
|
|
|
|
This driver is not built by default. You can build it by installing
|
|
libmodbus and running `configure --with-modbus=yes`.
|
|
|
|
You also need to give proper permissions on the local serial device
|
|
file (/dev/ttyUSB0 for example) to allow the run-time NUT driver user
|
|
account to access it.
|
|
|
|
OTHER NOTES
|
|
-----------
|
|
|
|
The `generic_modbus` driver intends to support generic UPS devices with
|
|
contact signals through modbus TCP/RTU gateways (also known as RIO --
|
|
remote I/Os). The data and signal path looks like this:
|
|
|
|
----
|
|
[UPSD] <--- IPC ---> [GENERIC_UPS] <--- modbus TCP/RTU ---> MODBUS-RIO <--- contacts ---> [UPS DEVICE]
|
|
----
|
|
|
|
On the other hand, you can setup any kind of modbus server, and configure
|
|
the `generic_modbus` driver to connect and read or write specific registers.
|
|
Your application / modbus server could then drive NUT statuses (e.g. OL, OB,
|
|
HB etc) by writing over those registers.
|
|
|
|
AUTHOR
|
|
------
|
|
|
|
Dimitris Economou <dimitris.s.economou@gmail.com>
|
|
|
|
SEE ALSO
|
|
--------
|
|
|
|
The core driver:
|
|
~~~~~~~~~~~~~~~~
|
|
|
|
linkman:nutupsdrv[8], linkman:ups.conf[5]
|
|
|
|
Internet resources:
|
|
~~~~~~~~~~~~~~~~~~~
|
|
|
|
* The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|
|
* libmodbus home page: http://libmodbus.org
|