.TH netxml\-ups 8 "Mon Aug 10 2009" "" "Network UPS Tools (NUT)"
|
|
.SH NAME
|
|
netxml\(hyups \- Driver for Eaton /MGE Network Management Card / Proxy
|
|
(XML/HTTP Protocol) equipment
|
|
.SH NOTE
|
|
This man page only documents the hardware\(hyspecific features of the
|
|
netxml\(hyups driver. For information about the core driver, see
|
|
\fBnutupsdrv\fR(8).
|
|
|
|
.SH SUPPORTED HARDWARE
|
|
netxml\(hyups support all recent Eaton / MGE models which use a Network
|
|
Management Card or Proxy (MGE XML/HTTP protocol based). This applies to both
|
|
Eaton (previously MGE Office Protection Systems) and to MGE UPS SYSTEMS.
|
|
Supported card and proxy models are:
|
|
|
|
NMC Minislot (Ref 66102, firmware EA or newer),
|
|
SNMP/Web Minislot card (Ref 66244)
|
|
NMC Transverse (Ref 66074),
|
|
NMC & Modbus/JBus (Ref 66103),
|
|
Network Management Proxy,
|
|
ePDU Monitored (newer version).
|
|
|
|
Older models, such as SNMP card (Ref 66062 and Ref 66045), use the SNMP
|
|
protocol and should use the snmp\(hyups driver with the "mibs=mge" parameter.
|
|
|
|
.SH EXTRA ARGUMENTS
|
|
This driver supports the following optional settings in the
|
|
\fBups.conf\fR(5):
|
|
|
|
.IP "timeout=\fIvalue\fR"
|
|
The timeout for connecting to and reading from the UPS. Defaults to 5 seconds.
|
|
Don't change this value unless you know exactly what you're doing.
|
|
|
|
This value \fBmust never\fR be higher than half the MAXAGE value specified in
|
|
\fBupsd.conf\fR(5), otherwise you risk that \fBupsd\fR(8) declares the driver
|
|
stale while it is waiting for a connection to timeout.
|
|
|
|
.IP "login=\fIvalue\fR"
|
|
Set the login value for authenticated mode. This feature also needs the
|
|
password argument, and allows value settings in the card.
|
|
This feature is not used yet.
|
|
|
|
.IP "password=\fIvalue\fR"
|
|
Set the password value, needed with the login for authenticated mode.
|
|
This feature is not used yet.
|
|
|
|
.SH IMPLEMENTATION
|
|
The hostname of the UPS is specified with the "port" value in
|
|
\fBups.conf\fR, i.e.:
|
|
|
|
.nf
|
|
[mgexml]
|
|
driver = netxml\-ups
|
|
port = http://netxml\-ups.example.com:80
|
|
.fi
|
|
|
|
Specifying the method how to connect to the UPS (http, https) is mandatory.
|
|
If the port is equal to the default for the method specified (80 for http,
|
|
443 for https) it may be omitted.
|
|
|
|
In order not to overload older NMCs by polling them too frequently, it is
|
|
recommended to increase the "pollinterval" (see \fBnutupsdrv\fR(8)) and
|
|
\fBups.conf\fR(5)) to at least 5 seconds.
|
|
|
|
.SH KNOWN ISSUES
|
|
Don't connect to the UPS through a proxy. Although it would be trivial to add
|
|
support for proxies, this is not recommended and don't ask for it. Not only
|
|
because it will prevent the driver to make a persistent connection to the UPS,
|
|
but also it adds an additional failure mode. If the proxy goes down (for
|
|
whatever reason), the driver will no longer be able to reach the UPS.
|
|
|
|
.SH AUTHORS
|
|
Arjen de Korte <adkorte-guest@alioth.debian.org>
|
|
|
|
.SH SEE ALSO
|
|
|
|
.SS The core driver:
|
|
\fBnutupsdrv\fR(8)
|
|
|
|
.SS Internet resources:
|
|