/* eaton-pdu-revelation-mib.c - data to monitor Eaton ePDUs branded as:
* G1 Aphel based ePDUs (Complex) - Revelation
*
* Copyright (C) 2008 - 2017
* Arnaud Quette <arnaud.quette@gmail.com>
* Arnaud Quette <ArnaudQuette@Eaton.com>
* Copyright (C) 2015 - 2017
* Jim Klimov <EvgenyKlimov@Eaton.com>
*
* Supported by Eaton <http://www.eaton.com>
* and previously MGE Office Protection Systems <http://www.mgeops.com>
*
* This program is free software; you can redistribute it and/or modify
* it under the terms of the GNU General Public License as published by
* the Free Software Foundation; either version 2 of the License, or
* (at your option) any later version.
*
* This program is distributed in the hope that it will be useful,
* but WITHOUT ANY WARRANTY; without even the implied warranty of
* MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
* GNU General Public License for more details.
*
*
* You should have received a copy of the GNU General Public License
* along with this program; if not, write to the Free Software
* Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
*
*/
#include "eaton-pdu-revelation-mib.h"
#define EATON_APHEL_REVELATION_MIB_VERSION "0.52"
/* APHEL PDU-MIB - Revelation MIB (Managed ePDU)
* ********************************************* */
#define AR_BASE_OID ".1.3.6.1.4.1.534.6.6.6"
#define APHEL2_SYSOID AR_BASE_OID
#define APHEL2_OID_MODEL_NAME AR_OID_MODEL_NAME
#define AR_OID_MODEL_NAME AR_BASE_OID ".1.1.12.0"
#define AR_OID_DEVICE_NAME AR_BASE_OID ".1.1.13.0"
#define AR_OID_FIRMREV AR_BASE_OID ".1.1.1.0"
#define AR_OID_SERIAL AR_BASE_OID ".1.1.2.0"
#define AR_OID_UNIT_MACADDR AR_BASE_OID ".1.1.6.0"
#define AR_OID_UNIT_CURRENT AR_BASE_OID ".1.3.1.1"
#define AR_OID_UNIT_VOLTAGE AR_BASE_OID ".1.3.1.2"
#define AR_OID_UNIT_ACTIVEPOWER AR_BASE_OID ".1.3.1.3"
#define AR_OID_UNIT_APPARENTPOWER AR_BASE_OID ".1.3.1.4"
#define AR_OID_UNIT_CPUTEMPERATURE AR_BASE_OID ".1.3.1.5.0"
#define AR_OID_OUTLET_INDEX AR_BASE_OID ".1.2.2.1.1"
#define AR_OID_OUTLET_NAME AR_BASE_OID ".1.2.2.1.2"
#define AR_OID_OUTLET_STATUS AR_BASE_OID ".1.2.2.1.3"
static info_lkp_t revelation_outlet_status_info[] = {
{ -1, "error", NULL, NULL },
{ 0, "off", NULL, NULL },
{ 1, "on", NULL, NULL },
{ 2, "cycling", NULL, NULL }, /* transitional status */
{ 0, NULL, NULL, NULL }
};
/* Ugly hack: having the matching OID present means that the outlet is
* switchable. So, it should not require this value lookup */
static info_lkp_t revelation_outlet_switchability_info[] = {
{ -1, "yes", NULL, NULL },
{ 0, "yes", NULL, NULL },
{ 1, "yes", NULL, NULL },
{ 2, "yes", NULL, NULL },
{ 0, NULL, NULL, NULL }
};
#define DO_OFF "0"
#define DO_ON "1"
#define DO_CYCLE "2"
#define AR_OID_OUTLET_COUNT AR_BASE_OID ".1.2.1.0"
#define AR_OID_OUTLET_CURRENT AR_BASE_OID ".1.2.2.1.4"
#define AR_OID_OUTLET_MAXCURRENT AR_BASE_OID ".1.2.2.1.5"
#define AR_OID_OUTLET_VOLTAGE AR_BASE_OID ".1.2.2.1.6"
#define AR_OID_OUTLET_ACTIVEPOWER AR_BASE_OID ".1.2.2.1.7"
#define AR_OID_OUTLET_APPARENTPOWER AR_BASE_OID ".1.2.2.1.8"
#define AR_OID_OUTLET_POWERFACTOR AR_BASE_OID ".1.2.2.1.9"
/* Snmp2NUT lookup table for Eaton Revelation MIB */
static snmp_info_t eaton_aphel_revelation_mib[] = {
/* standard MIB items */
{ "device.description", ST_FLAG_STRING | ST_FLAG_RW, SU_INFOSIZE, ".1.3.6.1.2.1.1.1.0", NULL, SU_FLAG_OK, NULL },
{ "device.contact", ST_FLAG_STRING | ST_FLAG_RW, SU_INFOSIZE, ".1.3.6.1.2.1.1.4.0", NULL, SU_FLAG_OK, NULL },
{ "device.location", ST_FLAG_STRING | ST_FLAG_RW, SU_INFOSIZE, ".1.3.6.1.2.1.1.6.0", NULL, SU_FLAG_OK, NULL },
/* Device collection */
{ "device.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "device.model", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_MODEL_NAME,
"Eaton Powerware ePDU Managed", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
{ "device.serial", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_SERIAL, "",
SU_FLAG_STATIC | SU_FLAG_OK, NULL },
{ "device.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "device.macaddr", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_UNIT_MACADDR, "",
SU_FLAG_STATIC | SU_FLAG_OK, NULL },
/* hardwareRev.0 = Integer: 26 */
/* FIXME: not compliant! to be RFC'ed */
{ "device.revision", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.534.6.6.6.1.1.7.0",
"", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
/* UPS collection */
{ "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, NULL, "EATON | Powerware",
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "ups.model", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_MODEL_NAME,
"Generic SNMP PDU", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
{ "ups.id", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_DEVICE_NAME,
"unknown", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
{ "ups.serial", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_SERIAL, "",
SU_FLAG_STATIC | SU_FLAG_OK, NULL },
{ "ups.firmware", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_FIRMREV, "",
SU_FLAG_STATIC | SU_FLAG_OK, NULL },
{ "ups.type", ST_FLAG_STRING, SU_INFOSIZE, NULL, "pdu",
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "ups.temperature", 0, 1, AR_OID_UNIT_CPUTEMPERATURE, NULL, 0, NULL },
/* Outlet collection */
{ "outlet.id", 0, 1, NULL, "0", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "outlet.desc", ST_FLAG_RW | ST_FLAG_STRING, 20, NULL, "All outlets",
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "outlet.count", 0, 1, AR_OID_OUTLET_COUNT, "0", 0, NULL },
{ "outlet.current", 0, 0.001, AR_OID_UNIT_CURRENT ".0", NULL, 0, NULL },
{ "outlet.voltage", 0, 0.001, AR_OID_UNIT_VOLTAGE ".0", NULL, 0, NULL },
{ "outlet.realpower", 0, 1.0, AR_OID_UNIT_ACTIVEPOWER ".0", NULL, 0, NULL },
{ "outlet.power", 0, 1.0, AR_OID_UNIT_APPARENTPOWER ".0", NULL, 0, NULL },
/* outlet template definition
* Caution: the index of the data start at 0, while the name is +1
* ie outlet.1 => <OID>.0 */
{ "outlet.%i.switchable", 0, 1, AR_OID_OUTLET_STATUS ".%i", "yes", SU_FLAG_STATIC | SU_OUTLET, &revelation_outlet_switchability_info[0] },
{ "outlet.%i.id", 0, 1, NULL, "%i", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK | SU_OUTLET, NULL },
{ "outlet.%i.desc", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE, AR_OID_OUTLET_NAME ".%i", NULL, SU_OUTLET, NULL },
{ "outlet.%i.status", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_OUTLET_STATUS ".%i", NULL, SU_FLAG_OK | SU_OUTLET, &revelation_outlet_status_info[0] },
{ "outlet.%i.current", 0, 0.001, AR_OID_OUTLET_CURRENT ".%i", NULL, SU_OUTLET, NULL },
{ "outlet.%i.current.maximum", 0, 0.001, AR_OID_OUTLET_MAXCURRENT ".%i", NULL, SU_OUTLET, NULL },
{ "outlet.%i.realpower", 0, 1.0, AR_OID_OUTLET_ACTIVEPOWER ".%i", NULL, SU_OUTLET, NULL },
{ "outlet.%i.voltage", 0, 1.0, AR_OID_OUTLET_VOLTAGE ".%i", NULL, SU_OUTLET, NULL },
{ "outlet.%i.powerfactor", 0, 0.01, AR_OID_OUTLET_POWERFACTOR ".%i", NULL, SU_OUTLET, NULL },
{ "outlet.%i.power", 0, 1.0, AR_OID_OUTLET_APPARENTPOWER ".%i", NULL, SU_OUTLET, NULL },
/* FIXME:
* - delay for startup/shutdown sequence
* - support for multiple Ambient sensors ( max. 8), starting at index '0'
* ambient.%i.temperature => .1.3.6.1.4.1.534.6.6.6.2.2.1.3.%i
* ambient.%i.humidity => .1.3.6.1.4.1.534.6.6.6.2.4.1.3.%i
*/
/* Ambient collection */
/* We use critical levels, for both temperature and humidity,
* since warning levels are also available! */
{ "ambient.temperature", 0, 1.0, ".1.3.6.1.4.1.534.6.6.6.2.2.1.3.0", NULL, SU_FLAG_OK, NULL },
{ "ambient.temperature.low", 0, 1.0, "1.3.6.1.4.1.534.6.6.6.2.2.1.6.0", NULL, SU_FLAG_OK, NULL },
{ "ambient.temperature.high", 0, 1.0, "1.3.6.1.4.1.534.6.6.6.2.2.1.7.0", NULL, SU_FLAG_OK, NULL },
{ "ambient.humidity", 0, 1.0, ".1.3.6.1.4.1.534.6.6.6.2.4.1.3.0", NULL, SU_FLAG_OK, NULL },
{ "ambient.humidity.low", 0, 1.0, ".1.3.6.1.4.1.534.6.6.6.2.4.1.6.0", NULL, SU_FLAG_OK, NULL },
{ "ambient.humidity.high", 0, 1.0, ".1.3.6.1.4.1.534.6.6.6.2.4.1.7.0", NULL, SU_FLAG_OK, NULL },
/* instant commands. */
/* Note that load.cycle might be replaced by / mapped on shutdown.reboot */
/* no counterpart found!
{ "outlet.load.off", 0, DO_OFF, AR_OID_OUTLET_STATUS ".0", NULL, SU_TYPE_CMD, NULL },
{ "outlet.load.on", 0, DO_ON, AR_OID_OUTLET_STATUS ".0", NULL, SU_TYPE_CMD, NULL },
{ "outlet.load.cycle", 0, DO_CYCLE, AR_OID_OUTLET_STATUS ".0", NULL, SU_TYPE_CMD, NULL }, */
{ "outlet.%i.load.off", 0, 1, AR_OID_OUTLET_STATUS ".%i", DO_OFF, SU_TYPE_CMD | SU_OUTLET, NULL },
{ "outlet.%i.load.on", 0, 1, AR_OID_OUTLET_STATUS ".%i", DO_ON, SU_TYPE_CMD | SU_OUTLET, NULL },
{ "outlet.%i.load.cycle", 0, 1, AR_OID_OUTLET_STATUS ".%i", DO_CYCLE, SU_TYPE_CMD | SU_OUTLET, NULL },
/* end of structure. */
{ NULL, 0, 0, NULL, NULL, 0, NULL }
};
mib2nut_info_t aphel_revelation = { "aphel_revelation", EATON_APHEL_REVELATION_MIB_VERSION, NULL, APHEL2_OID_MODEL_NAME, eaton_aphel_revelation_mib, APHEL2_SYSOID, NULL };