.SH "NAME"
|
|
snmp-ups \- Multi\-MIB Driver for SNMP UPS equipment
|
|
.SH "NOTE"
|
|
.sp
|
|
This man page only documents the hardware\-specific features of the snmp\-ups driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&.
|
|
.SH "SUPPORTED HARDWARE"
|
|
.sp
|
|
The snmp\-ups driver automatically detects and supports a wide range of devices by loading various MIBS, such as:
|
|
.PP
|
|
\fBietf\fR
|
|
.RS 4
|
|
UPS that is RFC 1628 (UPS MIB) compliant, e\&.g\&. MGE UPS SYSTEMS, Liebert, perhaps others (default)
|
|
.RE
|
|
.PP
|
|
\fBmge\fR
|
|
.RS 4
|
|
MGE UPS SYSTEMS and MGE Office Protection Systems devices with SNMP cards (ref 66062, 66045, 66074 and 66244)
|
|
.RE
|
|
.PP
|
|
\fBapcc\fR
|
|
.RS 4
|
|
APC AP9605, AP9606, AP9617, and AP9618 APC network management cards, as well as any others supporting the APC POWERNET MIB
|
|
.RE
|
|
.PP
|
|
\fBnetvision\fR
|
|
.RS 4
|
|
Socomec Sicon UPS with Netvision Web/SNMP management card/external box
|
|
.RE
|
|
.PP
|
|
\fBpw\fR
|
|
.RS 4
|
|
Powerware devices with ConnectUPS SNMP cards
|
|
.RE
|
|
.PP
|
|
\fBpxgx_ups\fR
|
|
.RS 4
|
|
Eaton devices with Power Xpert Gateway UPS Card
|
|
.RE
|
|
.PP
|
|
\fBaphel_genesisII\fR
|
|
.RS 4
|
|
Eaton Powerware ePDU Monitored
|
|
.RE
|
|
.PP
|
|
\fBaphel_revelation\fR
|
|
.RS 4
|
|
Eaton Powerware ePDU Managed
|
|
.RE
|
|
.PP
|
|
\fBraritan\fR
|
|
.RS 4
|
|
Various Raritan PDUs (Dominion PX, PM, RPC)
|
|
.RE
|
|
.PP
|
|
\fBraritan\-px2\fR
|
|
.RS 4
|
|
Various Raritan PDUs (Dominion PX2)
|
|
.RE
|
|
.PP
|
|
\fBbaytech\fR
|
|
.RS 4
|
|
Various BayTech PDUs
|
|
.RE
|
|
.PP
|
|
\fBcpqpower\fR
|
|
.RS 4
|
|
HP/Compaq AF401A management card, perhaps others
|
|
.RE
|
|
.PP
|
|
\fBcyberpower\fR
|
|
.RS 4
|
|
Cyberpower RMCARD201\&. Should also support RMCARD100 (net version), RMCARD202 and RMCARD301
|
|
.RE
|
|
.PP
|
|
\fBhuawei\fR
|
|
.RS 4
|
|
Huawei UPS5000\-E, perhaps others
|
|
.RE
|
|
.PP
|
|
\fBtripplite\fR
|
|
.RS 4
|
|
TrippLite UPSes; at this time this is the IETF MIB mapping with just the Tripplite entry point OID to verify the device vendor, and a real hardware\-specific configuration will be added in the future development\&.
|
|
.RE
|
|
.sp
|
|
For a complete and up\-to\-date listing, you can query the driver by passing the \fBmibs=\-\-list\fR argument (see below)\&.
|
|
.SH "EXTRA ARGUMENTS"
|
|
.sp
|
|
This driver supports the following optional settings in the \fBups.conf\fR(5):
|
|
.PP
|
|
\fBport\fR=\fIhostname[:port]\fR
|
|
.RS 4
|
|
Set SNMP hostname, or IP address, and port number of the peer SNMP agent\&. There is no default for the hostname, but the default port is 161\&.
|
|
.RE
|
|
.PP
|
|
\fBmibs\fR=\fI\-\-list\fR
|
|
.RS 4
|
|
A special option which allows to list the currently known MIB\-to\-NUT mappings and exit the driver binary, intended for command\-line usage like this:
|
|
.RE
|
|
.sp
|
|
.if n \{\
|
|
.RS 4
|
|
.\}
|
|
.nf
|
|
$ snmp\-ups \-a snmp\-test \-x mibs=\-\-list
|
|
.fi
|
|
.if n \{\
|
|
.RE
|
|
.\}
|
|
.PP
|
|
\fBmibs\fR=\fIname\fR
|
|
.RS 4
|
|
Set MIB compliance (default=auto, allowed entries: refer to SUPPORTED HARDWARE above)\&.
|
|
.sp
|
|
With "auto", the driver will try a select set of SNMP objects until it finds one that the device responds to\&.
|
|
.sp
|
|
Note that since NUT 2\&.6\&.2, snmp\-ups has a new method that uses sysObjectID (which is a pointer to the preferred MIB of the device) to detect supported devices\&. This renders void the
|
|
\fBrequirement\fR
|
|
to use the "mibs" option\&.
|
|
.RE
|
|
.PP
|
|
\fBcommunity\fR=\fIname\fR
|
|
.RS 4
|
|
Set community name (default = public)\&. Note that a RW community name is required to change UPS settings and send commands (as for a powerdown)\&.
|
|
.RE
|
|
.PP
|
|
\fBsnmp_version\fR=\fIversion\fR
|
|
.RS 4
|
|
Set SNMP version (default = v1, allowed: v2c, v3)
|
|
.RE
|
|
.PP
|
|
\fBsnmp_retries\fR=\fIretries\fR
|
|
.RS 4
|
|
Specifies the number of Net\-SNMP retries to be used in the requests (default=5)
|
|
.RE
|
|
.PP
|
|
\fBsnmp_timeout\fR=\fItimeout\fR
|
|
.RS 4
|
|
Specifies the Net\-SNMP timeout in seconds between retries (default=1)
|
|
.RE
|
|
.PP
|
|
\fBsymmetrathreephase\fR
|
|
.RS 4
|
|
Enable APCC three phase Symmetra quirks (use on APCC three phase Symmetras): Convert from three phase line\-to\-line voltage to line\-to\-neutral voltage (default: not enabled)
|
|
.RE
|
|
.PP
|
|
\fBpollfreq\fR=\fInum\fR
|
|
.RS 4
|
|
Set polling interval for full updates, in seconds, to reduce SNMP network traffic relative to the quick updates performed every "pollinterval" (the latter option is described in
|
|
\fBups.conf\fR(5))\&. The default value is 30 (in seconds)\&.
|
|
.RE
|
|
.PP
|
|
\fBnotransferoids\fR
|
|
.RS 4
|
|
Disable the monitoring of the low and high voltage transfer OIDs in the hardware\&. This will remove input\&.transfer\&.low and input\&.transfer\&.high from the list of variables\&. This should only be used on APCC Symmetra equipment which has strangeness in the three\-phase power reporting\&.
|
|
.RE
|
|
.PP
|
|
\fBsecLevel\fR=\fIvalue\fR
|
|
.RS 4
|
|
Set the securityLevel used for SNMPv3 messages (default=noAuthNoPriv, allowed: authNoPriv,authPriv)
|
|
.RE
|
|
.PP
|
|
\fBsecName\fR=\fIvalue\fR
|
|
.RS 4
|
|
Set the securityName used for authenticated SNMPv3 messages (no default)
|
|
.RE
|
|
.PP
|
|
\fBauthPassword\fR=\fIvalue\fR
|
|
.RS 4
|
|
Set the authentication pass phrase used for authenticated SNMPv3 messages (no default)
|
|
.RE
|
|
.PP
|
|
\fBprivPassword\fR=\fIvalue\fR
|
|
.RS 4
|
|
Set the privacy pass phrase used for encrypted SNMPv3 messages (no default)
|
|
.RE
|
|
.PP
|
|
\fBauthProtocol\fR=\fIvalue\fR
|
|
.RS 4
|
|
Set the authentication protocol (MD5, SHA, SHA256, SHA384 or SHA512) used for authenticated SNMPv3 messages (default=MD5)\&. Note that the exact protocol list depends on Net\-SNMP library capabilities; check help of the
|
|
snmp\-ups
|
|
binary program for the run\-time supported list\&.
|
|
.RE
|
|
.PP
|
|
\fBprivProtocol\fR=\fIvalue\fR
|
|
.RS 4
|
|
Set the privacy protocol (DES, AES, AES192 or AES256) used for encrypted SNMPv3 messages (default=DES)\&. Note that the exact protocol list depends on Net\-SNMP library capabilities; check help of the
|
|
snmp\-ups
|
|
binary program for the run\-time supported list\&.
|
|
.RE
|
|
.SH "REQUIREMENTS"
|
|
.sp
|
|
You will need to install the Net\-SNMP package from http://www\&.net\-snmp\&.org/ before building this driver\&.
|
|
.sp
|
|
SNMP v3 also requires OpenSSL support from http://www\&.openssl\&.org\&.
|
|
.SH "LIMITATIONS"
|
|
.SS "Shutdown"
|
|
.sp
|
|
The shutdown sequence should be tested before relying on NUT to send a shutdown command to the UPS\&. The problem is that the host network stack may have been torn down by the time the driver is invoked to send the shutdown command\&. The driver attempts to send shutdown\&.return, shutdown\&.reboot, and load\&.off\&.delay commands to the UPS in sequence, stopping after the first supported command\&.
|
|
.SH "INSTALLATION"
|
|
.sp
|
|
This driver is only built if the Net\-SNMP development files are present at configuration time\&. You can also force it to be built by using configure \-\-with\-snmp=yes before calling make\&.
|
|
.SH "EXAMPLES"
|
|
.sp
|
|
The hostname of the UPS is specified with the "port" value in ups\&.conf, and may include a non\-standard (161) remote peer port:
|
|
.sp
|
|
.if n \{\
|
|
.RS 4
|
|
.\}
|
|
.nf
|
|
[snmpv1]
|
|
driver = snmp\-ups
|
|
port = snmp\-ups\&.example\&.com
|
|
community = public
|
|
snmp_version = v1
|
|
pollfreq = 15
|
|
desc = "Example SNMP v1 device"
|
|
|
|
[snmpv3]
|
|
driver = snmp\-ups
|
|
port = 166\&.99\&.224\&.132:170
|
|
snmp_version = v3
|
|
secLevel = authPriv
|
|
secName = mysecurityname
|
|
authPassword = myauthenticationpassphrase
|
|
privPassword = myprivatepassphrase
|
|
desc = "Example SNMP v3 device, with the highest security level"
|
|
.fi
|
|
.if n \{\
|
|
.RE
|
|
.\}
|
|
.SH "AUTHORS"
|
|
.sp
|
|
.RS 4
|
|
.ie n \{\
|
|
\h'-04'\(bu\h'+03'\c
|
|
.\}
|
|
.el \{\
|
|
.sp -1
|
|
.IP \(bu 2.3
|
|
.\}
|
|
Arnaud Quette
|
|
.RE
|
|
.sp
|
|
.RS 4
|
|
.ie n \{\
|
|
\h'-04'\(bu\h'+03'\c
|
|
.\}
|
|
.el \{\
|
|
.sp -1
|
|
.IP \(bu 2.3
|
|
.\}
|
|
Dmitry Frolov
|
|
.RE
|
|
.sp
|
|
.RS 4
|
|
.ie n \{\
|
|
\h'-04'\(bu\h'+03'\c
|
|
.\}
|
|
.el \{\
|
|
.sp -1
|
|
.IP \(bu 2.3
|
|
.\}
|
|
Jim Klimov
|
|
.RE
|
|
.SH "SEE ALSO"
|
|
.SS "The core driver:"
|
|
.sp
|
|
\fBnutupsdrv\fR(8)
|
|
.SS "NUT SNMP Protocols Library"
|
|
.sp
|
|
Available at: http://www\&.networkupstools\&.org/ups\-protocols\&.html#_snmp
|
|
.SS "Internet resources:"
|
|
.sp
|
|
The NUT (Network UPS Tools) home page: http://www\&.networkupstools\&.org/
|