/* tripplite.h - model specific routines for Tripp Lite SmartUPS models
|
|
(tested with:
|
|
"SMART 700" [on back -- "SmartPro UPS" on front], "SMART700SER")
|
|
|
|
tripplite.c was derived from Russell Kroll's bestups.c by Rik Faith.
|
|
|
|
Copyright (C) 1999 Russell Kroll <rkroll@exploits.org>
|
|
Copyright (C) 2001 Rickard E. (Rik) Faith <faith@alephnull.com>
|
|
Copyright (C) 2004,2008 Nicholas J. Kain <nicholas@kain.us>
|
|
|
|
This program is free software; you can redistribute it and/or modify
|
|
it under the terms of the GNU General Public License as published by
|
|
the Free Software Foundation; either version 2 of the License, or
|
|
(at your option) any later version.
|
|
|
|
This program is distributed in the hope that it will be useful,
|
|
but WITHOUT ANY WARRANTY; without even the implied warranty of
|
|
MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
|
|
GNU General Public License for more details.
|
|
|
|
You should have received a copy of the GNU General Public License
|
|
along with this program; if not, write to the Free Software
|
|
Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
|
|
*/
|
|
|
|
#define ENDCHAR '\n' /* replies end with CR LF -- use LF to end */
|
|
#define IGNCHAR '\r' /* ignore CR */
|
|
#define MAXTRIES 3 /* max number of times we try to detect ups */
|
|
#define SER_WAIT_SEC 1 /* allow 1.0 sec for ser_get calls */
|
|
#define SER_WAIT_USEC 0
|
|
#define DEFAULT_OFFDELAY 64 /* seconds (max 0xFF) */
|
|
#define DEFAULT_STARTDELAY 60 /* seconds (max 0xFFFFFF) */
|
|
#define DEFAULT_BOOTDELAY 64 /* seconds (max 0xFF) */
|
|
|
|
/* Sometimes the UPS seems to return bad data, so we range check it. */
|
|
#define INVOLT_MAX 270
|
|
#define INVOLT_MIN 0
|
|
#define FREQ_MAX 80.0
|
|
#define FREQ_MIN 30.0
|
|
#define TEMP_MAX 100
|
|
#define TEMP_MIN 0
|
|
#define LOAD_MAX 100
|
|
#define LOAD_MIN 0
|
|
|
|
/* We calculate battery charge (q) as a function of voltage (V).
|
|
* It seems that this function probably varies by firmware revision or
|
|
* UPS model - the Windows monitoring software gives different q for a
|
|
* given V than the old open source Tripp Lite monitoring software.
|
|
*
|
|
* The discharge curve should be the same for any given battery chemistry,
|
|
* so it should only be necessary to specify the minimum and maximum
|
|
* voltages likely to be seen in operation.
|
|
*/
|
|
|
|
/* Interval notation for Q% = 10% <= [minV, maxV] <= 100% */
|
|
#define MAX_VOLT 13.4 /* Max battery voltage (100%) */
|
|
#define MIN_VOLT 11.0 /* Min battery voltage (10%) */
|
|
|