/*misc stuff*/
|
|
#define ENDCHAR '\r'
|
|
#define IGNCHARS "\n"
|
|
#define COMMAND_END "\r\n"
|
|
#define DEFAULT_BAT_TEST_TIME "02"
|
|
|
|
/*Information requests*/
|
|
|
|
#define GET_ALL '%'
|
|
#define GET_ALL_EXT_2 '^'
|
|
#define GET_ALL_EXT_1 '&'
|
|
#define GET_MFR 'M'
|
|
#define GET_FAMILY 'F'
|
|
#define GET_VERSION 'N'
|
|
#define GET_ON_INVERTER 'G'
|
|
#define GET_BATLOW 'K'
|
|
#define GET_STATUS 'X'
|
|
#define GET_LAST_XFER 'W'
|
|
#define GET_INVERTER_RDY 'I'
|
|
#define GET_TEST_TIME 'Q'
|
|
#define GET_NOM_FREQ 'H'
|
|
#define GET_NOM_VOLTAGE 'V'
|
|
#define GET_DISPLAY_CODE 'D'
|
|
#define GET_CONDITION_CODE 'C'
|
|
#define GET_PERCENT_LOAD 'P'
|
|
#define GET_PERCENT_BAT_REM 'T'
|
|
#define GET_INPUT_LINE_VOLT 'L'
|
|
#define GET_MIN_INPUT_VOLT 'A'
|
|
#define GET_MAX_INPUT_VOLT 'E'
|
|
#define GET_OUTPUT_VOLT 'S'
|
|
#define GET_BOOSTING 'B'
|
|
|
|
/*Control functions*/
|
|
#define SIM_PWR_FAIL "\x02\x15" /*^B^U 15 second battery test*/
|
|
#define SHUTDOWN "\x0f\x06" /*^O^F (a letter O)*/
|
|
#define RESET_MIN_MAX 'R'
|
|
#define BAT_TEST_PREFIX "\x02" /*needs 2 more chars. minutes*/
|
|
#define DELAYED_SHUTDOWN_PREFIX 'Z' /*needs 3 more chars. seconds */
|
|
|
|
#define DONT_UNDERSTAND '*'
|
|
#define CANT_COMPLY '#'
|
|
#define NO_VALUE_YET '.'
|
|
|
|
|
|
/*responses*/
|
|
#define MFGR "ONEAC"
|
|
#define FAMILY_ON "ON"
|
|
#define FAMILY_ON_EXT "OZ"
|
|
#define FAMILY_EG "EG"
|
|
#define YES 'Y'
|
|
#define NO 'N'
|
|
#define NORMAL '@'
|
|
#define ON_BAT_LOW_LINE 'A'
|
|
#define ON_BAT_HI_LINE 'Q'
|
|
#define LO_BAT_LOW_LINE 'C'
|
|
#define LO_BAT_HI_LINE 'S'
|
|
#define TOO_HOT '`'
|
|
#define FIX_ME 'D'
|
|
#define BAD_BAT 'H'
|
|
#define V230AC '2'
|
|
#define V120AC '1'
|
|
#define XFER_BLACKOUT 'B'
|
|
#define XFER_LOW_VOLT 'L'
|
|
#define XFER_HI_VOLT 'H'
|
|
|
|
/*front panel alarm codes*/
|
|
#define CODE_BREAKER_OPEN "c1" /*input circuit breaker open*/
|
|
#define CODE_BAT_FUSE_OPEN "c2" /*battery not connected. Open fuse?*/
|
|
#define CODE_TOO_HOT "c3" /*UPS too hot*/
|
|
#define CODE_CHARGING "c4" /*recharging battery pack*/
|
|
#define CODE_LOW_BAT_CAP "c5" /*batteries getting too old*/
|
|
#define CODE_OVERLOAD "c8" /*"slight" overload*/
|
|
#define CODE_GROSS_OVLE "c9" /*gross overload 1 minute to power off*/
|
|
#define CODE_CHRGR_FUSE_OPEN "u1" /*battery charger fuse probably open*/
|