/* compaq-mib.c - data to monitor SNMP UPS with NUT * * Copyright (C) * 2002-2012 Arnaud Quette * 2002-2006 Niels Baggesen * 2002-2006 Philip Ward * * This program was sponsored by MGE UPS SYSTEMS, and now Eaton * * This version has been tested using: * HP R5500XR UPS with management card AF401A and a single phase input * HP R/T3000 UPS with management card AF465A and a single phase input * * This program is free software; you can redistribute it and/or modify * it under the terms of the GNU General Public License as published by * the Free Software Foundation; either version 2 of the License, or * (at your option) any later version. * * This program is distributed in the hope that it will be useful, * but WITHOUT ANY WARRANTY; without even the implied warranty of * MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the * GNU General Public License for more details. * * * You should have received a copy of the GNU General Public License * along with this program; if not, write to the Free Software * Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA * */ #include "compaq-mib.h" #define CPQPOWER_MIB_VERSION "1.6" #define DEFAULT_ONDELAY 30 #define DEFAULT_OFFDELAY 20 #define STR_DEFAULT_ONDELAY "30" #define STR_DEFAULT_OFFDELAY "20" /* Note: RFC-1628 (UPS MIB) is also supported on these devices! */ /* SNMP OIDs set */ #define CPQPOWER_OID_UPS_MIB ".1.3.6.1.4.1.232.165.3" /* FIXME: to be verified */ #define CPQPOWER_SYSOID CPQPOWER_OID_UPS_MIB #define CPQPOWER_OID_MFR_NAME ".1.3.6.1.4.1.232.165.3.1.1.0" /* UPS-MIB::upsIdentManufacturer */ #define CPQPOWER_OID_MODEL_NAME ".1.3.6.1.4.1.232.165.3.1.2.0" /* UPS-MIB::upsIdentModel */ #define CPQPOWER_OID_FIRMREV ".1.3.6.1.4.1.232.165.3.1.3.0" /* UPS-MIB::upsIdentUPSSoftwareVersion */ #define CPQPOWER_OID_OEMCODE ".1.3.6.1.4.1.232.165.3.1.4.0" /* UPS-MIB::upsIdentAgentSoftwareVersion */ #define CPQPOWER_OID_BATT_RUNTIME ".1.3.6.1.4.1.232.165.3.2.1.0" /* UPS-MIB::upsEstimatedMinutesRemaining */ #define CPQPOWER_OID_BATT_VOLTAGE ".1.3.6.1.4.1.232.165.3.2.2.0" /* UPS-MIB::upsBatteryVoltage */ #define CPQPOWER_OID_BATT_CURRENT ".1.3.6.1.4.1.232.165.3.2.3.0" /* UPS-MIB::upsBatteryCurrent */ #define CPQPOWER_OID_BATT_CHARGE ".1.3.6.1.4.1.232.165.3.2.4.0" /* UPS-MIB::upsBattCapacity */ #define CPQPOWER_OID_BATT_STATUS ".1.3.6.1.4.1.232.165.3.2.5.0" /* UPS-MIB::upsBatteryAbmStatus */ #define CPQPOWER_OID_IN_FREQ ".1.3.6.1.4.1.232.165.3.3.1.0" /* UPS-MIB::upsInputFrequency */ #define CPQPOWER_OID_IN_LINEBADS ".1.3.6.1.4.1.232.165.3.3.2.0" /* UPS-MIB::upsInputLineBads */ #define CPQPOWER_OID_IN_LINES ".1.3.6.1.4.1.232.165.3.3.3.0" /* UPS-MIB::upsInputNumPhases */ #define CPQPOWER_OID_IN_PHASE ".1.3.6.1.4.1.232.165.3.3.4.1.1" /* UPS-MIB::upsInputPhase */ #define CPQPOWER_OID_IN_VOLTAGE ".1.3.6.1.4.1.232.165.3.3.4.1.2" /* UPS-MIB::upsInputVoltage */ #define CPQPOWER_OID_IN_CURRENT ".1.3.6.1.4.1.232.165.3.3.4.1.3" /* UPS-MIB::upsInputCurrent */ #define CPQPOWER_OID_IN_POWER ".1.3.6.1.4.1.232.165.3.3.4.1.4" /* UPS-MIB::upsInputWatts */ #define CPQPOWER_OID_LOAD_LEVEL ".1.3.6.1.4.1.232.165.3.4.1.0" /* UPS-MIB::upsOutputLoad */ #define CPQPOWER_OID_OUT_FREQUENCY ".1.3.6.1.4.1.232.165.3.4.2.0" /* UPS-MIB::upsOutputFrequency */ #define CPQPOWER_OID_OUT_LINES ".1.3.6.1.4.1.232.165.3.4.3.0" /* UPS-MIB::upsOutputNumPhases */ #define CPQPOWER_OID_OUT_PHASE ".1.3.6.1.4.1.232.165.3.4.4.1.1" /* UPS-MIB::upsOutputPhase */ #define CPQPOWER_OID_OUT_VOLTAGE ".1.3.6.1.4.1.232.165.3.4.4.1.2" /* UPS-MIB::upsOutputVoltage */ #define CPQPOWER_OID_OUT_CURRENT ".1.3.6.1.4.1.232.165.3.4.4.1.3" /* UPS-MIB::upsOutputCurrent */ #define CPQPOWER_OID_OUT_POWER ".1.3.6.1.4.1.232.165.3.4.4.1.4" /* UPS-MIB::upsOutputWatts */ #define CPQPOWER_OID_POWER_STATUS ".1.3.6.1.4.1.232.165.3.4.5.0" /* UPS-MIB::upsOutputSource */ #define CPQPOWER_OID_AMBIENT_TEMP ".1.3.6.1.4.1.232.165.3.6.1.0" /* UPS-MIB::upsEnvAmbientTemp */ #define CPQPOWER_OID_UPS_TEST_BATT ".1.3.6.1.4.1.232.165.3.7.1.0" /* UPS-MIB::upsTestBattery */ #define CPQPOWER_OID_UPS_TEST_RES ".1.3.6.1.4.1.232.165.3.7.2.0" /* UPS-MIB::upsTestBatteryStatus */ #define CPQPOWER_OID_ALARM_OB ".1.3.6.1.4.1.232.165.3.7.3.0" /* UPS-MIB::upsOnBattery */ #define CPQPOWER_OID_ALARM_LB ".1.3.6.1.4.1.232.165.3.7.4.0" /* UPS-MIB::upsLowBattery */ /* Not used, as no longer supported by MIB ver. 1.76 (Github issue 118) static info_lkp_t cpqpower_alarm_ob[] = { { 1, "OB" }, { 0, NULL } }; */ /* Not used, as no longer supported by MIB ver. 1.76 (Github issue 118) static info_lkp_t cpqpower_alarm_lb[] = { { 1, "LB" }, { 0, NULL } }; */ /* Defines for CPQPOWER_OID_POWER_STATUS (1) */ static info_lkp_t cpqpower_pwr_info[] = { { 1, "" /* other */ }, { 2, "OFF" /* none */ }, { 3, "OL" /* normal */ }, { 4, "OL BYPASS" /* bypass */ }, { 5, "OB" /* battery */ }, { 6, "OL BOOST" /* booster */ }, { 7, "OL TRIM" /* reducer */ }, { 8, "OL" /* parallelCapacity */ }, { 9, "OL" /* parallelRedundant */ }, { 10, "OL" /* HighEfficiencyMode */ }, { 0, NULL } } ; static info_lkp_t cpqpower_mode_info[] = { { 1, "" }, { 2, "" }, { 3, "normal" }, { 4, "" }, { 5, "" }, { 6, "" }, { 7, "" }, { 8, "parallel capacity" }, { 9, "parallel redundancy" }, {10, "high efficiency" }, { 0, NULL } }; static info_lkp_t cpqpower_battery_abm_status[] = { { 1, "CHRG" }, { 2, "DISCHRG" }, /* { 3, "Floating" }, */ /* { 4, "Resting" }, */ /* { 5, "Unknown" }, */ { 0, NULL } } ; /* Defines for CPQPOWER_OID_UPS_TEST_RES */ static info_lkp_t cpqpower_test_res_info[] = { { 1, "Unknown" }, { 2, "Done and passed" }, { 3, "Done and error" }, { 4, "In progress" }, { 5, "Not supported" }, { 6, "Inhibited" }, { 7, "Scheduled" }, { 0, NULL } } ; #define CPQPOWER_START_TEST 1 static info_lkp_t cpqpower_outlet_status_info[] = { { 1, "on" }, { 2, "off" }, { 3, "pendingOff" }, /* transitional status */ { 4, "pendingOn" }, /* transitional status */ { 5, "unknown" }, { 0, NULL } }; /* Ugly hack: having the matching OID present means that the outlet is * switchable. So, it should not require this value lookup */ static info_lkp_t cpqpower_outlet_switchability_info[] = { { 1, "yes" }, { 2, "yes" }, { 3, "yes" }, { 4, "yes" }, { 0, NULL } }; #define CPQPOWER_OID_SD_AFTER_DELAY ".1.3.6.1.4.1.232.165.3.8.1.0" /* UPS-MIB::upsControlOutputOffDelay */ #define CPQPOWER_OFF_DO 0 /* Snmp2NUT lookup table */ static snmp_info_t cpqpower_mib[] = { /* UPS page */ /* info_type, info_flags, info_len, OID, dfl, flags, oid2info, setvar */ { "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_MFR_NAME, "HP/Compaq", SU_FLAG_STATIC, NULL }, { "ups.model", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_MODEL_NAME, "SNMP UPS", SU_FLAG_STATIC, NULL }, /* { "ups.model.aux", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_OEMCODE, "", SU_FLAG_STATIC, NULL },*/ { "ups.serial", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.232.165.1.2.7.0", "", SU_FLAG_STATIC | SU_FLAG_OK, NULL }, /* FIXME: split between firmware and firmware.aux ("00.01.0019;00.01.0004") * UPS Firmware Revision : 00.01.0004 * Communication Board Firmware Revision : 00.01.0019 */ { "ups.firmware", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_FIRMREV, "", SU_FLAG_STATIC, NULL }, { "ups.load", 0, 1.0, CPQPOWER_OID_LOAD_LEVEL, "", 0, NULL }, { "ups.realpower", 0, 1.0, CPQPOWER_OID_OUT_POWER, "", SU_OUTPUT_1, NULL }, { "ups.realpower", 0, 1.0, ".1.3.6.1.4.1.232.165.3.9.3.0", "", SU_OUTPUT_1, NULL }, { "ups.L1.realpower", 0, 0.1, CPQPOWER_OID_OUT_POWER ".1", "", SU_OUTPUT_3, NULL }, { "ups.L2.realpower", 0, 0.1, CPQPOWER_OID_OUT_POWER ".2", "", SU_OUTPUT_3, NULL }, { "ups.L3.realpower", 0, 0.1, CPQPOWER_OID_OUT_POWER ".3", "", SU_OUTPUT_3, NULL }, { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_POWER_STATUS, "OFF", SU_STATUS_PWR, cpqpower_pwr_info }, { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_BATT_STATUS, "", SU_STATUS_PWR, cpqpower_battery_abm_status }, /* The next two lines are no longer supported by MIB ver. 1.76 (Github issue 118) * { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_ALARM_OB, "", SU_STATUS_BATT, cpqpower_alarm_ob }, * { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_ALARM_LB, "", SU_STATUS_BATT, cpqpower_alarm_lb }, */ /* { "ups.status", ST_FLAG_STRING, SU_INFOSIZE, IETF_OID_BATT_STATUS, "", SU_STATUS_BATT, ietf_batt_info }, */ /* FIXME: this should use either .1.3.6.1.4.1.232.165.3.11.1.0 (upsTopologyType) * or .1.3.6.1.4.1.232.165.3.11.2.0 (upsTopoMachineCode) */ { "ups.type", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_POWER_STATUS, "", SU_STATUS_PWR, cpqpower_mode_info }, { "ups.test.result", ST_FLAG_STRING, SU_INFOSIZE, CPQPOWER_OID_UPS_TEST_RES, "", 0, cpqpower_test_res_info }, /* FIXME: handle ups.date and ups.time * - OID: .1.3.6.1.4.1.232.165.3.9.5.0 * - format MM/DD/YYYY HH:MM:SS */ /* FIXME: handle upsInputSource.0 (".1.3.6.1.4.1.232.165.3.3.5.0") * other(1) * none(2) * primaryUtility(3) * bypassFeed(4) * secondaryUtility(5) * generator(6) * flywheel(7) * fuelcell(8) */ { "ups.delay.shutdown", ST_FLAG_STRING | ST_FLAG_RW, 6, ".1.3.6.1.4.1.232.165.3.8.1.0", STR_DEFAULT_OFFDELAY, SU_FLAG_ABSENT | SU_FLAG_OK, NULL }, { "ups.delay.start", ST_FLAG_STRING | ST_FLAG_RW, 6, ".1.3.6.1.4.1.232.165.3.8.2.0", STR_DEFAULT_ONDELAY, SU_FLAG_ABSENT | SU_FLAG_OK, NULL }, { "ups.timer.shutdown", 0, 1, ".1.3.6.1.4.1.232.165.3.8.1.0", "", SU_FLAG_OK, NULL }, { "ups.timer.start", 0, 1, ".1.3.6.1.4.1.232.165.3.8.2.0", "", SU_FLAG_OK, NULL }, /* Ambient page */ { "ambient.temperature", 0, 1.0, CPQPOWER_OID_AMBIENT_TEMP, "", 0, NULL }, { "ambient.temperature.low", 0, 1.0, ".1.3.6.1.4.1.232.165.3.6.2.0", "", 0, NULL }, { "ambient.temperature.high", 0, 1.0, ".1.3.6.1.4.1.232.165.3.6.3.0", "", 0, NULL }, /* Battery page */ { "battery.charge", 0, 1.0, CPQPOWER_OID_BATT_CHARGE, "", 0, NULL }, { "battery.runtime", 0, 1.0, CPQPOWER_OID_BATT_RUNTIME, "", 0, NULL }, { "battery.voltage", 0, 0.1, CPQPOWER_OID_BATT_VOLTAGE, "", 0, NULL }, { "battery.current", 0, 0.1, CPQPOWER_OID_BATT_CURRENT, "", 0, NULL }, /* FIXME: need the new variable (for ABM) { "battery.status", 0, 0.1, ".1.3.6.1.4.1.232.165.3.2.5.0", "", 0, NULL }, */ /* Input page */ { "input.phases", 0, 1.0, CPQPOWER_OID_IN_LINES, "", SU_FLAG_SETINT, NULL, &input_phases }, /* { "input.phase", 0, 1.0, CPQPOWER_OID_IN_PHASE, "", SU_OUTPUT_1, NULL }, */ { "input.frequency", 0, 0.1, CPQPOWER_OID_IN_FREQ , "", 0, NULL }, { "input.voltage", 0, 1.0, CPQPOWER_OID_IN_VOLTAGE, "", SU_OUTPUT_1, NULL }, { "input.voltage", 0, 1.0, ".1.3.6.1.4.1.232.165.3.3.4.1.2.1", "", SU_OUTPUT_1, NULL }, { "input.voltage.nominal", ST_FLAG_RW | ST_FLAG_STRING, 3, ".1.3.6.1.4.1.232.165.3.9.2.0", "", SU_OUTPUT_1, NULL }, { "input.L1-N.voltage", 0, 1.0, CPQPOWER_OID_IN_VOLTAGE ".1", "", SU_INPUT_3, NULL }, { "input.L2-N.voltage", 0, 1.0, CPQPOWER_OID_IN_VOLTAGE ".2", "", SU_INPUT_3, NULL }, { "input.L3-N.voltage", 0, 1.0, CPQPOWER_OID_IN_VOLTAGE ".3", "", SU_INPUT_3, NULL }, { "input.current", 0, 0.1, CPQPOWER_OID_IN_CURRENT, "", SU_OUTPUT_1, NULL }, { "input.current", 0, 0.1, ".1.3.6.1.4.1.232.165.3.3.4.1.3.1", "", SU_OUTPUT_1, NULL }, { "input.L1.current", 0, 0.1, CPQPOWER_OID_IN_CURRENT ".1", "", SU_INPUT_3, NULL }, { "input.L2.current", 0, 0.1, CPQPOWER_OID_IN_CURRENT ".2", "", SU_INPUT_3, NULL }, { "input.L3.current", 0, 0.1, CPQPOWER_OID_IN_CURRENT ".3", "", SU_INPUT_3, NULL }, { "input.realpower", 0, 0.1, CPQPOWER_OID_IN_POWER, "", SU_OUTPUT_1, NULL }, { "input.L1.realpower", 0, 0.1, CPQPOWER_OID_IN_POWER ".1", "", SU_INPUT_3, NULL }, { "input.L2.realpower", 0, 0.1, CPQPOWER_OID_IN_POWER ".2", "", SU_INPUT_3, NULL }, { "input.L3.realpower", 0, 0.1, CPQPOWER_OID_IN_POWER ".3", "", SU_INPUT_3, NULL }, { "input.quality", 0, 1.0, CPQPOWER_OID_IN_LINEBADS, "", 0, NULL }, /* Output page */ { "output.phases", 0, 1.0, CPQPOWER_OID_OUT_LINES, "", SU_FLAG_SETINT, NULL, &output_phases }, /* { "output.phase", 0, 1.0, CPQPOWER_OID_OUT_PHASE, "", SU_OUTPUT_1, NULL }, */ { "output.frequency", 0, 0.1, CPQPOWER_OID_OUT_FREQUENCY, "", 0, NULL }, /* FIXME: handle multiplier (0.1 there) */ { "output.frequency.nominal", ST_FLAG_RW | ST_FLAG_STRING, 3, ".1.3.6.1.4.1.232.165.3.9.4.0", "", SU_OUTPUT_1, NULL }, { "output.voltage", 0, 1.0, CPQPOWER_OID_OUT_VOLTAGE, "", SU_OUTPUT_1, NULL }, { "output.voltage", 0, 1.0, ".1.3.6.1.4.1.232.165.3.4.4.1.2.1", "", SU_OUTPUT_1, NULL }, { "output.voltage.nominal", ST_FLAG_RW | ST_FLAG_STRING, 3, ".1.3.6.1.4.1.232.165.3.9.1.0", "", SU_OUTPUT_1, NULL }, { "output.L1-N.voltage", 0, 1.0, CPQPOWER_OID_OUT_VOLTAGE ".1", "", SU_OUTPUT_3, NULL }, { "output.L2-N.voltage", 0, 1.0, CPQPOWER_OID_OUT_VOLTAGE ".2", "", SU_OUTPUT_3, NULL }, { "output.L3-N.voltage", 0, 1.0, CPQPOWER_OID_OUT_VOLTAGE ".3", "", SU_OUTPUT_3, NULL }, { "output.current", 0, 0.1, CPQPOWER_OID_OUT_CURRENT, "", SU_OUTPUT_1, NULL }, { "output.current", 0, 0.1, ".1.3.6.1.4.1.232.165.3.4.4.1.3.1", "", SU_OUTPUT_1, NULL }, /* { "output.realpower", 0, 1.0, ".1.3.6.1.4.1.232.165.3.4.4.1.4", "", SU_OUTPUT_1, NULL }, */ { "output.L1.current", 0, 0.1, CPQPOWER_OID_OUT_CURRENT ".1", "", SU_OUTPUT_3, NULL }, { "output.L2.current", 0, 0.1, CPQPOWER_OID_OUT_CURRENT ".2", "", SU_OUTPUT_3, NULL }, { "output.L3.current", 0, 0.1, CPQPOWER_OID_OUT_CURRENT ".3", "", SU_OUTPUT_3, NULL }, /* FIXME: what to map with these? * Name/OID: upsConfigLowOutputVoltageLimit.0; Value (Integer): 160 * => input.transfer.low? * Name/OID: upsConfigHighOutputVoltageLimit.0; Value (Integer): 288 * => input.transfer.high? */ /* Outlet page */ { "outlet.id", 0, 1, NULL, "0", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL }, { "outlet.desc", ST_FLAG_RW | ST_FLAG_STRING, 20, NULL, "All outlets", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL }, { "outlet.count", 0, 1, ".1.3.6.1.4.1.232.165.3.10.1.0", "0", 0, NULL }, /* upsNumReceptacles */ /* { "outlet.current", 0, 0.001, AR_OID_UNIT_CURRENT ".0", NULL, 0, NULL, NULL }, { "outlet.voltage", 0, 0.001, AR_OID_UNIT_VOLTAGE ".0", NULL, 0, NULL, NULL }, { "outlet.realpower", 0, 1.0, AR_OID_UNIT_ACTIVEPOWER ".0", NULL, 0, NULL, NULL }, { "outlet.power", 0, 1.0, AR_OID_UNIT_APPARENTPOWER ".0", NULL, 0, NULL, NULL }, */ /* outlet template definition */ /* FIXME always true? */ { "outlet.%i.switchable", ST_FLAG_STRING, 3, ".1.3.6.1.4.1.232.165.3.10.2.1.1.%i", "yes", SU_FLAG_STATIC | SU_OUTLET, &cpqpower_outlet_switchability_info[0], NULL }, { "outlet.%i.id", 0, 1, ".1.3.6.1.4.1.232.165.3.10.2.1.1.%i", "%i", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK | SU_OUTLET, NULL, NULL }, /* { "outlet.%i.desc", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE, AR_OID_OUTLET_NAME ".%i", NULL, SU_OUTLET, NULL, NULL }, */ { "outlet.%i.status", ST_FLAG_STRING, SU_INFOSIZE, ".1.3.6.1.4.1.232.165.3.10.2.1.2.%i", NULL, SU_FLAG_OK | SU_OUTLET, &cpqpower_outlet_status_info[0], NULL }, /* FIXME: come up with a suitable varname! * - The delay after going On Battery until the Receptacle is automatically turned Off. * A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. * { "outlet.%i.autoswitch.delay.shutdown", ST_FLAG_STRING | ST_FLAG_RW, 6, ".1.3.6.1.4.1.232.165.3.10.2.1.5.%i", STR_DEFAULT_OFFDELAY, SU_FLAG_ABSENT | SU_FLAG_OK, NULL }, // upsRecepAutoOffDelay * - Seconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. * A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to do so. * { "outlet.%i.autoswitch.delay.start", ST_FLAG_STRING | ST_FLAG_RW, 6, ".1.3.6.1.4.1.232.165.3.10.2.1.5.%i", STR_DEFAULT_OFFDELAY, SU_FLAG_ABSENT | SU_FLAG_OK, NULL }, // upsRecepAutoOnDelay */ /* FIXME: also define .stop (as for 'shutdown.reboot') * and .delay */ { "outlet.%i.load.off", 0, 0, ".1.3.6.1.4.1.232.165.3.10.2.1.3.%i", NULL, SU_TYPE_CMD | SU_OUTLET, NULL, NULL }, { "outlet.%i.load.on", 0, 0, ".1.3.6.1.4.1.232.165.3.10.2.1.4.%i", NULL, SU_TYPE_CMD | SU_OUTLET, NULL, NULL }, /* FIXME: also define a .delay or map to "outlet.%i.delay.shutdown" */ { "outlet.%i.load.cycle", 0, 0, ".1.3.6.1.4.1.232.165.3.10.2.1.7.%i", NULL, SU_TYPE_CMD | SU_OUTLET, NULL, NULL }, /* instant commands. */ /* We need to duplicate load.{on,off} Vs load.{on,off}.delay, since * "0" cancels the shutdown, so we put "1" (second) for immediate off! */ { "load.off", 0, 1, ".1.3.6.1.4.1.232.165.3.8.1.0", "", SU_TYPE_CMD, NULL }, { "load.on", 0, 1, ".1.3.6.1.4.1.232.165.3.8.2.0", "", SU_TYPE_CMD, NULL }, { "shutdown.stop", 0, 0, ".1.3.6.1.4.1.232.165.3.8.1.0", "", SU_TYPE_CMD | SU_FLAG_OK, NULL }, /* FIXME: need ups.{timer,delay}.{start,shutdown} param counterparts! */ { "load.off.delay", 0, DEFAULT_OFFDELAY, ".1.3.6.1.4.1.232.165.3.8.1.0", "", SU_TYPE_CMD, NULL }, { "load.on.delay", 0, DEFAULT_ONDELAY, ".1.3.6.1.4.1.232.165.3.8.2.0", "", SU_TYPE_CMD, NULL }, /* { CMD_SHUTDOWN, 0, CPQPOWER_OFF_GRACEFUL, CPQPOWER_OID_OFF, "", 0, NULL }, */ { "shutdown.reboot", 0, 0, ".1.3.6.1.4.1.232.165.3.8.6.0", "", SU_TYPE_CMD | SU_FLAG_OK, NULL }, { "test.battery.start", 0, CPQPOWER_START_TEST, ".1.3.6.1.4.1.232.165.3.7.1.0", "", SU_TYPE_CMD | SU_FLAG_OK, NULL }, /* end of structure. */ { NULL, 0, 0, NULL, NULL, 0, NULL } }; mib2nut_info_t compaq = { "cpqpower", CPQPOWER_MIB_VERSION, NULL, CPQPOWER_OID_MFR_NAME, cpqpower_mib, CPQPOWER_SYSOID };