'\" t .\" Title: snmp-ups .\" Author: [see the "AUTHORS" section] .\" Generator: DocBook XSL Stylesheets v1.75.2 .\" Date: 08/07/2012 .\" Manual: NUT Manual .\" Source: Network UPS Tools .\" Language: English .\" .TH "SNMP\-UPS" "8" "08/07/2012" "Network UPS Tools" "NUT Manual" .\" ----------------------------------------------------------------- .\" * Define some portability stuff .\" ----------------------------------------------------------------- .\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ .\" http://bugs.debian.org/507673 .\" http://lists.gnu.org/archive/html/groff/2009-02/msg00013.html .\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ .ie \n(.g .ds Aq \(aq .el .ds Aq ' .\" ----------------------------------------------------------------- .\" * set default formatting .\" ----------------------------------------------------------------- .\" disable hyphenation .nh .\" disable justification (adjust text to left margin only) .ad l .\" ----------------------------------------------------------------- .\" * MAIN CONTENT STARTS HERE * .\" ----------------------------------------------------------------- .SH "NAME" snmp-ups \- Multi\-MIB Driver for SNMP UPS equipment .SH "NOTE" .sp This man page only documents the hardware\-specific features of the snmp\-ups driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&. .SH "SUPPORTED HARDWARE" .sp The snmp\-ups driver automatically detects and supports a wide range of devices by loading various MIBS: \fBietf\fR:: UPS that is RFC 1628 (UPS MIB) compliant, e\&.g\&. MGE UPS SYSTEMS, Liebert, perhaps others (default) .PP \fBmge\fR .RS 4 MGE UPS SYSTEMS and MGE Office Protection Systems devices with SNMP cards (ref 66062, 66045, 66074 and 66244) .RE .PP \fBapcc\fR .RS 4 APC AP9605, AP9606, AP9617, and AP9618 APC network management cards, as well as any others supporting the APC POWERNET MIB .RE .PP \fBnetvision\fR .RS 4 Socomec Sicon UPS with Netvision Web/SNMP management card/external box .RE .PP \fBpw\fR .RS 4 Powerware devices with ConnectUPS SNMP cards .RE .PP \fBaphel_genesisII\fR .RS 4 Eaton Powerware ePDU Monitored .RE .PP \fBaphel_revelation\fR .RS 4 Eaton Powerware ePDU Managed .RE .PP \fBraritan\fR .RS 4 Various Raritan PDUs .RE .PP \fBbaytech\fR .RS 4 Various BayTech PDUs .RE .PP \fBcpqpower\fR .RS 4 HP/Compaq AF401A management card, perhaps others .RE .PP \fBcyberpower\fR .RS 4 Cyberpower RMCARD201\&. Should also support RMCARD100 (net version), RMCARD202 and RMCARD301 .RE .SH "EXTRA ARGUMENTS" .sp This driver supports the following optional settings in the \fBups.conf\fR(5): .PP \fBmibs\fR=\fIname\fR .RS 4 Set MIB compliance (default=auto, allowed entries: refer to the above SUPPORTED HARDWARE)\&. With "auto", the driver will try a select set of SNMP objects until it finds one that the device responds to\&. .RE .PP \fBcommunity\fR=\fIname\fR .RS 4 Set community name (default = public)\&. Note that you require a RW community name to change UPS settings (as for a powerdown)\&. .RE .PP \fBsnmp_version\fR=\fIversion\fR .RS 4 Set SNMP version (default = v1, the other allowed value is v2c) .RE .PP \fBpollfreq\fR=\fIvalue\fR .RS 4 Set polling frequency in seconds, to reduce network flow (default=30) .RE .PP \fBnotransferoids\fR .RS 4 Disable the monitoring of the low and high voltage transfer OIDs in the hardware\&. This will remove input\&.transfer\&.low and input\&.transfer\&.high from the list of variables\&. This should only be used on APCC Symmetra equipment which has strangeness in the three\-phase power reporting\&. .RE .PP \fBsecLevel\fR=\fIvalue\fR .RS 4 Set the securityLevel used for SNMPv3 messages (default=noAuthNoPriv, allowed: authNoPriv,authPriv) .RE .PP \fBsecName\fR=\fIvalue\fR .RS 4 Set the securityName used for authenticated SNMPv3 messages (no default) .RE .PP \fBauthPassword\fR=\fIvalue\fR .RS 4 Set the authentication pass phrase used for authenticated SNMPv3 messages (no default) .RE .PP \fBprivPassword\fR=\fIvalue\fR .RS 4 Set the privacy pass phrase used for encrypted SNMPv3 messages (no default) .RE .PP \fBauthProtocol\fR=\fIvalue\fR .RS 4 Set the authentication protocol (MD5 or SHA) used for authenticated SNMPv3 messages (default=MD5) .RE .PP \fBprivProtocol\fR=\fIvalue\fR .RS 4 Set the privacy protocol (DES or AES) used for encrypted SNMPv3 messages (default=DES) .RE .SH "REQUIREMENTS" .sp You will need to install the Net\-SNMP package from http://www\&.net\-snmp\&.org/ before building this driver\&. .sp SNMP v3 also requires OpenSSL support from http://www\&.openssl\&.org\&. .SH "LIMITATION" .SS "Shutdown" .sp This driver does not provide a proper upsdrv_shutdown() function\&. There probably never will be one, since at the time this script should run (near the end of the system halt script), there will be no network capabilities anymore\&. Probably the only way to shutdown an SNMP UPS is by sending it a shutdown with delay command through \fBupscmd\fR(8) and hope for the best that the system will have finished shutting down before the power is cut\&. .SH "INSTALLATION" .sp This driver is only built if the Net\-SNMP development files are present on the system\&. You can also force it to be built by using "configure \-\-with\-snmp=yes" before calling make\&. .SH "IMPLEMENTATION" .sp The hostname of the UPS is specified with the "port" value in ups\&.conf, i\&.e\&.: .sp .if n \{\ .RS 4 .\} .nf [snmpv1] driver = snmp\-ups port = snmp\-ups\&.example\&.com community = public snmp_version = v1 mibs = ietf pollfreq = 15 desc = "Example SNMP v1 device" .fi .if n \{\ .RE .\} .sp .if n \{\ .RS 4 .\} .nf [snmpv3] driver = snmp\-ups port = 166\&.99\&.224\&.132 mibs = mge secLevel = authPriv secName = mysecurityname authPassword = myauthenticationpassphrase privPassword = myprivatepassphrase desc = "Example SNMP v3 device, with the highest security level" .fi .if n \{\ .RE .\} .SH "AUTHORS" .sp Arnaud Quette, Dmitry Frolov .sp Sponsored by Eaton http://www\&.eaton\&.com and originally by MGE UPS SYSTEMS http://www\&.mgeups\&.com/ .SH "SEE ALSO" .SS "The core driver:" .sp \fBnutupsdrv\fR(8) .SS "NUT SNMP Protocols Library" .sp Available at: http://www\&.networkupstools\&.org/protocols/snmp/ .SS "Internet resources:" .sp The NUT (Network UPS Tools) home page: http://www\&.networkupstools\&.org/