299 lines
9.0 KiB
C
299 lines
9.0 KiB
C
|
/*
|
||
|
* nutdrv_siemens_sitop.c - model specific routines for the Siemens SITOP UPS500 series
|
||
|
*
|
||
|
*
|
||
|
* Copyright (C) 2018 Matthijs H. ten Berge <m.tenberge@awl.nl>
|
||
|
*
|
||
|
* This program is free software; you can redistribute it and/or modify
|
||
|
* it under the terms of the GNU General Public License as published by
|
||
|
* the Free Software Foundation; either version 2 of the License, or
|
||
|
* (at your option) any later version.
|
||
|
*
|
||
|
* This program is distributed in the hope that it will be useful,
|
||
|
* but WITHOUT ANY WARRANTY; without even the implied warranty of
|
||
|
* MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
|
||
|
* GNU General Public License for more details.
|
||
|
*
|
||
|
* You should have received a copy of the GNU General Public License
|
||
|
* along with this program; if not, write to the Free Software
|
||
|
* Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
|
||
|
*/
|
||
|
|
||
|
/*
|
||
|
* Notes:
|
||
|
* These UPSes operate at 24V DC (both input and output), instead of 110V/230V AC.
|
||
|
* Therefore, the line input is also referred to by Siemens as 'DC'.
|
||
|
*
|
||
|
* The device is configured via DIP-switches.
|
||
|
* For correct functioning in combination with NUT, set the DIP-switches to the following:
|
||
|
* switch 1-4: choose whatever suits your situation. Any combination will work with NUT.
|
||
|
* switch 5 ('=>' / 't'): set to OFF ('t')
|
||
|
* switch 6-10 (delay): set to OFF (no additional delay)
|
||
|
* switch 11 (INTERR.): set to ON
|
||
|
* switch 12 (ON/OFF): set to ON
|
||
|
*
|
||
|
* These UPSes are available with serial or USB port.
|
||
|
* Both are supported by this driver. The version with USB port simply contains
|
||
|
* a serial-over-USB chip, so as far as this driver is concerned, all models are
|
||
|
* actually serial models.
|
||
|
*
|
||
|
* The FTDI USB-to-serial converters in the USB-models are programmed with a non-standard
|
||
|
* Product ID (mine had 0403:e0e3), but can be used with the normal ftdi_sio driver:
|
||
|
* # modprobe ftdi_sio
|
||
|
* # echo 0403 e0e3 > /sys/bus/usb-serial/drivers/ftdi_sio/new_id
|
||
|
*
|
||
|
* This can also be automated via a udev rule:
|
||
|
* ACTION=="add", ATTRS{idVendor}=="0403", ATTRS{idProduct}=="e0e3", \
|
||
|
* RUN+="/sbin/modprobe ftdi_sio", \
|
||
|
* RUN+="/bin/sh -c 'echo 0403 e0e3 > /sys/bus/usb-serial/drivers/ftdi_sio/new_id'"
|
||
|
*
|
||
|
* Use the following udev rule to create a persistent device name, for example /dev/ttyUPS:
|
||
|
* SUBSYSTEM=="tty" ATTRS{idVendor}=="0403", ATTRS{idProduct}=="e0e3" SYMLINK+="ttyUPS"
|
||
|
*/
|
||
|
|
||
|
#include "main.h"
|
||
|
#include "serial.h"
|
||
|
#include "nut_stdint.h"
|
||
|
|
||
|
#define DRIVER_NAME "Siemens SITOP UPS500 series driver"
|
||
|
#define DRIVER_VERSION "0.03"
|
||
|
|
||
|
#define RX_BUFFER_SIZE 100
|
||
|
|
||
|
/* driver description structure */
|
||
|
upsdrv_info_t upsdrv_info = {
|
||
|
DRIVER_NAME,
|
||
|
DRIVER_VERSION,
|
||
|
"Matthijs H. ten Berge <m.tenberge@awl.nl>",
|
||
|
DRV_EXPERIMENTAL,
|
||
|
{ NULL }
|
||
|
};
|
||
|
|
||
|
/* The maximum number of consecutive polls in which the UPS does not provide any data: */
|
||
|
static unsigned int max_polls_without_data;
|
||
|
/* The current number: */
|
||
|
static unsigned int nr_polls_without_data;
|
||
|
/* receive buffer */
|
||
|
static char rx_buffer[RX_BUFFER_SIZE];
|
||
|
static size_t rx_count;
|
||
|
|
||
|
static struct {
|
||
|
int battery_alarm;
|
||
|
int dc_input_low;
|
||
|
int on_battery;
|
||
|
int battery_above_85_percent;
|
||
|
} current_ups_status;
|
||
|
|
||
|
/* remove n bytes from the head of rx_buffer, shift the remaining bytes to the start */
|
||
|
static void rm_buffer_head(unsigned int n) {
|
||
|
if (rx_count <= n) {
|
||
|
/* nothing left */
|
||
|
rx_count = 0;
|
||
|
return;
|
||
|
}
|
||
|
rx_count -= n;
|
||
|
memmove(rx_buffer, rx_buffer + n, rx_count);
|
||
|
}
|
||
|
|
||
|
/* parse incoming data from the UPS.
|
||
|
* return true if something new was received.
|
||
|
*/
|
||
|
static int check_for_new_data() {
|
||
|
int new_data_received = 0;
|
||
|
int done = 0;
|
||
|
ssize_t num_received;
|
||
|
|
||
|
while (!done) {
|
||
|
/* Get new data from the serial port.
|
||
|
* No extra delay, just get the chars that were already buffered.
|
||
|
*/
|
||
|
num_received = ser_get_buf(upsfd, rx_buffer + rx_count, RX_BUFFER_SIZE - rx_count, 0, 0);
|
||
|
if (num_received < 0) {
|
||
|
/* comm error */
|
||
|
ser_comm_fail("error %zd while reading", num_received);
|
||
|
/* discard any remaining old data from the receive buffer: */
|
||
|
rx_count = 0;
|
||
|
/* try to re-open the serial port: */
|
||
|
if (upsfd) {
|
||
|
ser_close(upsfd, device_path);
|
||
|
upsfd = 0;
|
||
|
}
|
||
|
upsfd = ser_open_nf(device_path);
|
||
|
ser_set_speed_nf(upsfd, device_path, B9600);
|
||
|
done = 1;
|
||
|
} else if (num_received == 0) {
|
||
|
/* no (more) new data */
|
||
|
done = 1;
|
||
|
} else {
|
||
|
rx_count += (unsigned int)num_received;
|
||
|
|
||
|
/* parse received input data: */
|
||
|
while (rx_count >= 5) { /* all valid input messages are strings of 5 characters */
|
||
|
if (strncmp(rx_buffer, "BUFRD", 5) == 0) {
|
||
|
current_ups_status.battery_alarm = 0;
|
||
|
} else if (strncmp(rx_buffer, "ALARM", 5) == 0) {
|
||
|
current_ups_status.battery_alarm = 1;
|
||
|
} else if (strncmp(rx_buffer, "DC_OK", 5) == 0) {
|
||
|
current_ups_status.dc_input_low = 0;
|
||
|
} else if (strncmp(rx_buffer, "DC_LO", 5) == 0) {
|
||
|
current_ups_status.dc_input_low = 1;
|
||
|
} else if (strncmp(rx_buffer, "*****", 5) == 0) {
|
||
|
current_ups_status.on_battery = 0;
|
||
|
} else if (strncmp(rx_buffer, "*BAT*", 5) == 0) {
|
||
|
current_ups_status.on_battery = 1;
|
||
|
} else if (strncmp(rx_buffer, "BA>85", 5) == 0) {
|
||
|
current_ups_status.battery_above_85_percent = 1;
|
||
|
} else if (strncmp(rx_buffer, "BA<85", 5) == 0) {
|
||
|
current_ups_status.battery_above_85_percent = 0;
|
||
|
} else {
|
||
|
/* nothing sensible found at the start of the rx_buffer. */
|
||
|
rm_buffer_head(1);
|
||
|
continue; /* skip the code below */
|
||
|
}
|
||
|
rm_buffer_head(5);
|
||
|
new_data_received = 1;
|
||
|
}
|
||
|
}
|
||
|
}
|
||
|
return new_data_received;
|
||
|
}
|
||
|
|
||
|
|
||
|
static int instcmd(const char *cmdname, const char *extra) {
|
||
|
/* Note: the UPS does not really like to receive data.
|
||
|
* For example, sending an "R" without \n hangs the serial port.
|
||
|
* In that situation, the UPS will no longer send any status updates.
|
||
|
* For this reason, an additional \n is appended here.
|
||
|
* The commands are sent twice, because the first command is sometimes
|
||
|
* lost as well.
|
||
|
*/
|
||
|
if (!strcasecmp(cmdname, "shutdown.return")) {
|
||
|
upslogx(LOG_NOTICE, "instcmd: sending command R");
|
||
|
ser_send_pace(upsfd, 200000, "\n\nR\n\n");
|
||
|
ser_send_pace(upsfd, 200000, "R\n\n");
|
||
|
return STAT_INSTCMD_HANDLED;
|
||
|
}
|
||
|
if (!strcasecmp(cmdname, "shutdown.stayoff")) {
|
||
|
upslogx(LOG_NOTICE, "instcmd: sending command S");
|
||
|
ser_send_pace(upsfd, 200000, "\n\nS\n\n");
|
||
|
ser_send_pace(upsfd, 200000, "S\n\n");
|
||
|
return STAT_INSTCMD_HANDLED;
|
||
|
}
|
||
|
|
||
|
upslogx(LOG_NOTICE, "instcmd: unknown command [%s] [%s]", cmdname, extra);
|
||
|
return STAT_INSTCMD_UNKNOWN;
|
||
|
}
|
||
|
|
||
|
|
||
|
void upsdrv_initinfo(void) {
|
||
|
int max_attempts = 5;
|
||
|
int found = 0;
|
||
|
while (!found && max_attempts > 0) {
|
||
|
if (check_for_new_data()) {
|
||
|
found = 1;
|
||
|
} else {
|
||
|
sleep(1); /* Sleep a while, then try again */
|
||
|
}
|
||
|
max_attempts--;
|
||
|
}
|
||
|
if (!found) {
|
||
|
fatalx(EXIT_FAILURE, "No data received from the UPS");
|
||
|
}
|
||
|
|
||
|
dstate_setinfo("device.mfr", "Siemens");
|
||
|
dstate_setinfo("device.model", "SITOP UPS500 series");
|
||
|
|
||
|
/* supported commands: */
|
||
|
dstate_addcmd("shutdown.stayoff");
|
||
|
dstate_addcmd("shutdown.return");
|
||
|
|
||
|
upsh.instcmd = instcmd;
|
||
|
}
|
||
|
|
||
|
|
||
|
void upsdrv_updateinfo(void) {
|
||
|
if (check_for_new_data()) {
|
||
|
nr_polls_without_data = 0;
|
||
|
} else {
|
||
|
nr_polls_without_data++;
|
||
|
/* With unsigned int type, we can limit half-way like this: */
|
||
|
if (nr_polls_without_data > INT_MAX)
|
||
|
nr_polls_without_data = INT_MAX;
|
||
|
}
|
||
|
|
||
|
if (nr_polls_without_data > max_polls_without_data) {
|
||
|
/* data is stale */
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
|
||
|
/* This is all we know about the charge level... */
|
||
|
dstate_setinfo("battery.charge.approx",
|
||
|
(current_ups_status.battery_above_85_percent) ? ">85" : "<85");
|
||
|
|
||
|
status_init();
|
||
|
|
||
|
if (current_ups_status.dc_input_low || current_ups_status.on_battery) {
|
||
|
status_set("OB");
|
||
|
} else {
|
||
|
status_set("OL");
|
||
|
}
|
||
|
if (current_ups_status.battery_alarm) {
|
||
|
status_set("LB");
|
||
|
}
|
||
|
|
||
|
status_commit();
|
||
|
dstate_dataok();
|
||
|
ser_comm_good();
|
||
|
}
|
||
|
|
||
|
void upsdrv_shutdown(void) {
|
||
|
/* tell the UPS to shut down, then return - DO NOT SLEEP HERE */
|
||
|
instcmd("shutdown.return", NULL);
|
||
|
}
|
||
|
|
||
|
|
||
|
void upsdrv_help(void) {
|
||
|
}
|
||
|
|
||
|
/* list flags and values that you want to receive via -x */
|
||
|
void upsdrv_makevartable(void) {
|
||
|
/* allow '-x max_polls_without_data=<some value>' */
|
||
|
addvar(VAR_VALUE, "max_polls_without_data", "The maximum number of consecutive polls in which the UPS does not provide any data.");
|
||
|
}
|
||
|
|
||
|
void upsdrv_initups(void) {
|
||
|
char * maxPollsString;
|
||
|
unsigned int parsed;
|
||
|
|
||
|
upsfd = ser_open(device_path);
|
||
|
ser_set_speed(upsfd, device_path, B9600);
|
||
|
|
||
|
/*
|
||
|
* Fast polling is preferred, because
|
||
|
* A) the UPS spits out new data every 75 msec,
|
||
|
* B) some models in this SITOP series have a _very_ small capacity
|
||
|
* (< 10sec runtime), so every second might count.
|
||
|
*/
|
||
|
if (poll_interval > 5) {
|
||
|
upslogx(LOG_NOTICE,
|
||
|
"Option poll_interval is recommended to be lower than 5 (found: %jd)",
|
||
|
(intmax_t)poll_interval);
|
||
|
}
|
||
|
|
||
|
/* option max_polls_without_data: */
|
||
|
max_polls_without_data = 2;
|
||
|
maxPollsString = getval("max_polls_without_data");
|
||
|
if (maxPollsString) {
|
||
|
if (str_to_uint(maxPollsString, &parsed, 10) == 1) {
|
||
|
max_polls_without_data = parsed;
|
||
|
} else {
|
||
|
upslog_with_errno(LOG_ERR, "Cannot parse option max_polls_without_data");
|
||
|
}
|
||
|
}
|
||
|
}
|
||
|
|
||
|
void upsdrv_cleanup(void) {
|
||
|
ser_close(upsfd, device_path);
|
||
|
}
|