nut-debian/docs/man/oneac.8

217 lines
5.0 KiB
Groff
Raw Normal View History

2011-01-26 11:35:08 +02:00
'\" t
.\" Title: oneac
.\" Author: [see the "AUTHOR" section]
2013-11-24 17:00:12 +02:00
.\" Generator: DocBook XSL Stylesheets v1.76.1 <http://docbook.sf.net/>
.\" Date: 07/26/2013
2011-01-26 11:35:08 +02:00
.\" Manual: NUT Manual
2013-11-24 17:00:12 +02:00
.\" Source: Network UPS Tools 2.6.5
2011-01-26 11:35:08 +02:00
.\" Language: English
.\"
2013-11-24 17:00:12 +02:00
.TH "ONEAC" "8" "07/26/2013" "Network UPS Tools 2\&.6\&.5" "NUT Manual"
2011-01-26 11:35:08 +02:00
.\" -----------------------------------------------------------------
.\" * Define some portability stuff
.\" -----------------------------------------------------------------
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
.\" http://bugs.debian.org/507673
.\" http://lists.gnu.org/archive/html/groff/2009-02/msg00013.html
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
.ie \n(.g .ds Aq \(aq
.el .ds Aq '
.\" -----------------------------------------------------------------
.\" * set default formatting
.\" -----------------------------------------------------------------
.\" disable hyphenation
.nh
.\" disable justification (adjust text to left margin only)
.ad l
.\" -----------------------------------------------------------------
.\" * MAIN CONTENT STARTS HERE *
.\" -----------------------------------------------------------------
.SH "NAME"
oneac \- Driver for Oneac UPS equipment
.SH "NOTE"
.sp
This man page only documents the hardware\-specific features of the oneac driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&.
.SH "SUPPORTED HARDWARE"
.sp
2012-06-01 16:55:19 +03:00
This driver supports various Oneac UPS families:
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
EG (late 80s, early 90s, plug\-in serial interface card)
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
ON (early and mid\-90s, plug\-in serial interface card)
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
OZ (mid\-90s on, DB\-25 std\&., interface slot)
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
OB (early 2000\(cqs on, big cabinet, DB\-25 std\&., interface slot)
.RE
.sp
If your UPS is equipped with the Basic Interface card, use the \fBgenericups\fR(8) driver\&.
2011-01-26 11:35:08 +02:00
.SH "EXTRA ARGUMENTS"
.sp
This driver supports the following optional settings in the \fBups.conf\fR(5) file:
.PP
\fBtesttime\fR=\fInum\fR
.RS 4
Change battery test time from the 2 minute default\&.
.RE
2012-06-01 16:55:19 +03:00
.PP
\fBoffdelay\fR=\fInum\fR
.RS 4
Change shutdown delay time from 0 second default\&.
.RE
2011-01-26 11:35:08 +02:00
.SH "INSTANT COMMANDS"
.sp
2012-06-01 16:55:19 +03:00
This driver supports the following Instant Commands\&. (See \fBupscmd\fR(8))
.SS "All UPS units"
2011-01-26 11:35:08 +02:00
.PP
2012-06-01 16:55:19 +03:00
\fBshutdown\&.return\fR
2011-01-26 11:35:08 +02:00
.RS 4
2012-06-01 16:55:19 +03:00
Turn off the load possibly after a delay and return when power is back\&.
.RE
.PP
\fBshutdown\&.stop\fR
.RS 4
Stop a shutdown in progress\&.
2011-01-26 11:35:08 +02:00
.RE
.PP
2012-06-01 16:55:19 +03:00
\fBshutdown\&.reboot\fR
2011-01-26 11:35:08 +02:00
.RS 4
2012-06-01 16:55:19 +03:00
Shut down the load briefly while rebooting the UPS\&.
.RE
.PP
\fBtest\&.failure\&.start\fR
.RS 4
Starts a 15 second long simulation of an input power failure\&.
.RE
.PP
\fBtest\&.battery\&.start\&.quick\fR
.RS 4
Start a "quick" battery test\&. The default time is 2 minutes\&. This time can be set in the
2011-01-26 11:35:08 +02:00
\fBups\&.conf\fR
file\&. See
\fBtestime\fR
above\&.
.RE
.PP
\fBtest\&.battery\&.stop\fR
.RS 4
Stops a battery test that is in progress\&.
.RE
2012-06-01 16:55:19 +03:00
.SS "All ON UPS units"
2011-01-26 11:35:08 +02:00
.PP
2012-06-01 16:55:19 +03:00
\fBreset\&.input\&.minmax\fR
2011-01-26 11:35:08 +02:00
.RS 4
2012-06-01 16:55:19 +03:00
Reset the minimum and maximum input line voltage values seen since the last reset or power on\&.
.RE
.SS "Newer ON UPS units"
.PP
\fBtest\&.panel\&.start\fR
.RS 4
Start testing the UPS panel\&.
.RE
.PP
\fBtest\&.battery\&.start\&.deep\fR
.RS 4
Start a "deep" battery test\&. This test runs the UPS until the low battery point and then returns to the AC line\&.
.RE
.PP
\fBreset\&.input\&.minmax\fR
.RS 4
Reset the minimum and maximum input line voltage values seen since the last reset or power on\&.
.RE
.PP
\fBbeeper\&.enable\fR
.RS 4
Enable UPS beeper/buzzer\&.
.RE
.PP
\fBbeeper\&.disable\fR
.RS 4
Disable UPS beeper/buzzer\&.
.RE
.PP
\fBbeeper\&.mute\fR
.RS 4
Mutes the UPS beeper/buzzer for the current alarm condition(s)\&.
.RE
.SH "WRITABLE VARIABLES"
.sp
See \fBupsrw\fR(8) to see what variables are writable for the UPS\&.
.if n \{\
.sp
.\}
.RS 4
.it 1 an-trap
.nr an-no-space-flag 1
.nr an-break-flag 1
.br
.ps +1
\fBNote\fR
.ps -1
.br
.sp
If your UPS supports writing battery\&.runtime\&.low, the new set value is to be entered in minutes (up to 99) but the reported value is reported in seconds (set value * 60)\&.
.sp .5v
.RE
.if n \{\
.sp
.\}
.RS 4
.it 1 an-trap
.nr an-no-space-flag 1
.nr an-break-flag 1
.br
.ps +1
\fBNote\fR
.ps -1
.br
.sp
If your UPS supports input\&.transfer\&.low and input\&.transfer\&.high, those values are used to create an allowable output range\&. The UPS will do what it can to keep the output voltage value within the defined range (for example: tap change or switch to inverter)\&.
.sp .5v
2011-01-26 11:35:08 +02:00
.RE
.SH "AUTHOR"
.sp
2012-06-01 16:55:19 +03:00
Bill Elliot <bill@wreassoc\&.com>, Eric Lawson <elawson@inficad\&.com>
2011-01-26 11:35:08 +02:00
.SH "SEE ALSO"
.SS "The core driver:"
.sp
\fBnutupsdrv\fR(8)
.SS "Internet resources:"
.sp
The NUT (Network UPS Tools) home page: http://www\&.networkupstools\&.org/