2011-01-26 11:35:08 +02:00
|
|
|
Configuration notes
|
|
|
|
===================
|
|
|
|
|
|
|
|
This chapter describe most of the configuration and use aspects of NUT,
|
|
|
|
including establishing communication with the device and configuring safe
|
|
|
|
shutdowns when the UPS battery runs out of power.
|
|
|
|
|
|
|
|
There are many programs and <<Features,features>> in this
|
|
|
|
package. You should check out the <<Overview,NUT Overview>>
|
|
|
|
and other accompanying documentation to see how it all works.
|
|
|
|
|
|
|
|
NOTE: NUT does not currently provide proper graphical configuration tools.
|
2012-01-24 12:22:33 +02:00
|
|
|
However, there is now support for linkdoc:developer-guide[Augeas,augeas_user],
|
|
|
|
which will enable the easier creation of configuration tools.
|
|
|
|
Moreover, linkman:nut-scanner[8] is available to discover supported devices
|
2022-07-10 10:23:45 +03:00
|
|
|
(USB, SNMP, Eaton XML/HTTP and IPMI) and NUT servers (using Avahi or the
|
|
|
|
classic connection method).
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Details about the configuration files
|
|
|
|
-------------------------------------
|
|
|
|
|
|
|
|
Generalities
|
|
|
|
~~~~~~~~~~~~
|
|
|
|
|
|
|
|
All configuration files within this package are parsed with a common
|
|
|
|
state machine, which means they all can use a number of extras described here.
|
|
|
|
|
|
|
|
First, most of the programs use an uppercase word to declare a
|
|
|
|
configuration directive. This may be something like MONITOR, NOTIFYCMD,
|
|
|
|
or ACCESS. The case does matter here. "monitor" won't be recognized.
|
|
|
|
|
|
|
|
Next, the parser does not care about whitespace between words. If you
|
2016-07-18 03:11:41 +03:00
|
|
|
like to indent things with tabs or spaces, feel free to do it here.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
If you need to set a value to something containing spaces, it has to be
|
|
|
|
contained within "quotes" to keep the parser from splitting up the line.
|
|
|
|
That is, you want to use something like this:
|
|
|
|
|
|
|
|
SHUTDOWNCMD "/sbin/shutdown -h +0"
|
|
|
|
|
|
|
|
Without the quotes, it would only see the first word on the line.
|
|
|
|
|
|
|
|
OK, so let's say you really need to embed that kind of quote within your
|
|
|
|
configuration directive for some reason. You can do that too.
|
|
|
|
|
|
|
|
NOTIFYCMD "/bin/notifyme -foo -bar \"hi there\" -baz"
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
In other words, `\` can be used to escape the `"`.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
Finally, for the situation where you need to put the `\` character into your
|
2011-01-26 11:35:08 +02:00
|
|
|
string, you just escape it.
|
|
|
|
|
|
|
|
NOTIFYCMD "/bin/notifyme c:\\dos\\style\\path"
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
The `\` can actually be used to escape any character, but you only really
|
|
|
|
need it for `\`, `"`, and `#` as they have special meanings to the parser.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2012-01-24 12:22:33 +02:00
|
|
|
When using file names with space characters, you may end up having tricky
|
2016-07-18 03:11:41 +03:00
|
|
|
things since you need to write them inside `""` which must be escaped:
|
2012-01-24 12:22:33 +02:00
|
|
|
|
|
|
|
NOTIFYCMD "\"c:\\path with space\\notifyme\" \"c:\\path with space\\name\""
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
`#` is the comment character. Anything after an unescaped `#` is ignored.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Something like this...
|
|
|
|
|
|
|
|
identity = my#1ups
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
will actually turn into `identity = my`, since the `#` stops the
|
|
|
|
parsing. If you really need to have a `#` in your configuration, then
|
2011-01-26 11:35:08 +02:00
|
|
|
escape it.
|
|
|
|
|
|
|
|
identity = my\#1ups
|
|
|
|
|
|
|
|
Much better.
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
The `=` character should be used with care too. There should be only one
|
|
|
|
"simple" `=` character in a line: between the parameter name and its value.
|
|
|
|
All other `=` characters should be either escaped or within "quotes".
|
2012-06-01 16:55:19 +03:00
|
|
|
|
|
|
|
password = 123=123
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
is incorrect. You should use:
|
2012-06-01 16:55:19 +03:00
|
|
|
|
|
|
|
password = 123\=123
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
or:
|
2012-06-01 16:55:19 +03:00
|
|
|
|
|
|
|
password = "123=123"
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
Line spanning
|
|
|
|
~~~~~~~~~~~~~
|
|
|
|
|
|
|
|
You can put a backslash at the end of the line to join it to the next
|
|
|
|
one. This creates one virtual line that is composed of more than one
|
|
|
|
physical line.
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
Also, if you leave the `""` quote container open before a newline, it will
|
2011-01-26 11:35:08 +02:00
|
|
|
keep scanning until it reaches another one. If you see bizarre behavior
|
|
|
|
in your configuration files, check for an unintentional instance of
|
|
|
|
quotes spanning multiple lines.
|
|
|
|
|
|
|
|
|
|
|
|
Basic configuration
|
|
|
|
-------------------
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
This chapter describes the base configuration to establish communication with
|
2011-01-26 11:35:08 +02:00
|
|
|
the device.
|
|
|
|
|
|
|
|
This will be sufficient for PDU. But for UPS and SCD, you will also need to
|
|
|
|
configure <<UPS_shutdown,automatic shutdowns for low battery events>>.
|
|
|
|
|
|
|
|
image:images/simple.png[]
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
On operating systems with service management frameworks (such as Linux
|
|
|
|
systemd and Solaris/illumos SMF), the life-cycle of driver, data server
|
|
|
|
and monitoring client daemons is managed respectively by `nut-driver`
|
|
|
|
(multi-instance service), `nut-server` and `nut-monitor` services.
|
|
|
|
These are in turn wrapped by an "umbrella" service (or systemd "target")
|
|
|
|
conveniently called `nut` which allows to easily start or stop all those
|
|
|
|
of the bundled services, which are enabled on a particular deployment.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
[[Driver_configuration]]
|
|
|
|
Driver configuration
|
|
|
|
~~~~~~~~~~~~~~~~~~~~
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Create one section per UPS in 'ups.conf'
|
|
|
|
|
|
|
|
NOTE: The default path for a source installation is `/usr/local/ups/etc`,
|
|
|
|
while packaged installation will vary.
|
|
|
|
For example, `/etc/nut` is used on Debian and derivatives,
|
|
|
|
while `/etc/ups` or `/etc/upsd` is used on RedHat and derivatives.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
To find out which driver to use, check the
|
|
|
|
<<HCL,Hardware Compatibility List>>,
|
|
|
|
or `data/driver.list(.in)` source file.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Once you have picked a driver, create a section for your UPS in
|
2022-07-10 10:23:45 +03:00
|
|
|
'ups.conf'. You must supply values at least for "driver" and "port".
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Some drivers may require other flags or settings. The "desc" value
|
|
|
|
is optional, but is recommended to provide a better description of
|
2022-07-10 10:23:45 +03:00
|
|
|
what useful load your UPS is feeding.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
A typical device without any extra settings looks like this:
|
|
|
|
|
|
|
|
[mydevice]
|
|
|
|
driver = mydriver
|
|
|
|
port = /dev/ttyS1
|
|
|
|
desc = "Workstation"
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
[NOTE]
|
|
|
|
======
|
|
|
|
USB drivers (such as `usbhid-ups` for non-SHUT mode, `nutdrv_qx` for
|
|
|
|
non-serial mode, `bcmxcp_usb`, `tripplite_usb`, `blazer_usb`, `riello_usb`
|
|
|
|
and `richcomm_usb`) are special cases and ignore the 'port' value.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
You must still set this value, but it does not matter what you set
|
2022-07-10 10:23:45 +03:00
|
|
|
it to; a common and good practice is to set 'port' to *auto*, but you
|
|
|
|
can put whatever you like.
|
|
|
|
|
|
|
|
If you only own one USB UPS, the driver will find it automatically.
|
|
|
|
|
|
|
|
If you own more than one, refer to the driver's manual page for more
|
|
|
|
information on matching a specific device.
|
|
|
|
======
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
References: linkman:ups.conf[5],
|
|
|
|
linkman:nutupsdrv[8],
|
|
|
|
linkman:bcmxcp_usb[8],
|
|
|
|
linkman:blazer[8],
|
2022-07-10 10:23:45 +03:00
|
|
|
linkman:nutdrv_qx[8],
|
2011-01-26 11:35:08 +02:00
|
|
|
linkman:richcomm_usb[8],
|
2022-07-10 10:23:45 +03:00
|
|
|
linkman:riello_usb[8],
|
2011-01-26 11:35:08 +02:00
|
|
|
linkman:tripplite_usb[8],
|
|
|
|
linkman:usbhid-ups[8]
|
|
|
|
|
|
|
|
|
|
|
|
[[Starting_drivers]]
|
|
|
|
Starting the driver(s)
|
|
|
|
~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Generally, you can just start the driver(s) for your hardware (all sections
|
|
|
|
defined in 'ups.conf') using the following command:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsdrvctl start
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Make sure the driver doesn't report any errors. It should show a
|
|
|
|
few details about the hardware and then enter the background. You
|
|
|
|
should get back to the command prompt a few seconds later. For
|
|
|
|
reference, a successful start of the `usbhid-ups` driver looks like this:
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
# upsdrvctl start
|
2011-01-26 11:35:08 +02:00
|
|
|
Network UPS Tools - Generic HID driver 0.34 (2.4.1)
|
|
|
|
USB communication driver 0.31
|
|
|
|
Using subdriver: MGE HID 1.12
|
|
|
|
Detected EATON - Ellipse MAX 1100 [ADKK22008]
|
|
|
|
|
|
|
|
If the driver doesn't start cleanly, make sure you have picked the
|
|
|
|
right one for your hardware. You might need to try other drivers
|
2022-07-10 10:23:45 +03:00
|
|
|
by changing the "driver=" value in 'ups.conf'.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Be sure to check the driver's man page to see if it needs any extra
|
2022-07-10 10:23:45 +03:00
|
|
|
settings in 'ups.conf' to detect your hardware.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
If it says `can't bind /var/state/ups/...` or similar, then your
|
2011-01-26 11:35:08 +02:00
|
|
|
state path probably isn't writable by the driver. Check the
|
2022-07-10 10:23:45 +03:00
|
|
|
<<StatePath,permissions and mode on that directory>> vs. the
|
|
|
|
user account your driver starts as.
|
|
|
|
|
|
|
|
After making changes, try the <<Ownership, Ownership and permissions>>
|
|
|
|
step again.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Driver(s) as a service
|
|
|
|
~~~~~~~~~~~~~~~~~~~~~~
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
On operating systems with init-scripts managing life-cycle of the operating
|
|
|
|
environment, the `upsdrvctl` program is also commonly used in those scripts.
|
|
|
|
It has a few downsides, such as that if the device was not accessible during
|
|
|
|
OS startup and the driver connection timed out, it would remain not-started
|
|
|
|
until an administrator (or some other script) "kicks" the driver to retry
|
|
|
|
startup. Also, startup of the `upsd` data server daemon and its clients
|
|
|
|
like `upsmon` is delayed until all the NUT drivers complete their startup
|
|
|
|
(or time out trying).
|
|
|
|
|
|
|
|
This can be a big issue on systems which monitor multiple devices, such as
|
|
|
|
big servers with multiple power sources, or administrative workstations
|
|
|
|
which monitor a datacenter full of UPSes.
|
|
|
|
|
|
|
|
For this reason, NUT starting with version 2.8.0 supports startup of its
|
|
|
|
drivers as independent instances of a `nut-driver` service under the Linux
|
|
|
|
systemd and Solaris/illumos SMF service-management frameworks (corresponding
|
|
|
|
files and scripts may be not pre-installed in packaging for other systems).
|
|
|
|
|
|
|
|
Such service instances have their own and independent life-cycle, including
|
|
|
|
parallel driver start and stop processing, and retries of startup in case of
|
|
|
|
failure as implemented by the service framework in the OS. The Linux systemd
|
|
|
|
solution also includes a `nut-driver.target` as a checkpoint that all defined
|
|
|
|
drivers have indeed started up (as well as being a singular way to enable or
|
|
|
|
disable startup of drivers).
|
|
|
|
|
|
|
|
In both cases, a service named `nut-driver-enumerator` is registered, and
|
|
|
|
when it is (re-)started it scans the currently defined device sections in
|
|
|
|
'ups.conf' and the currently defined instances of `nut-driver` service,
|
|
|
|
and brings them in sync (adding or removing service instances), and if
|
|
|
|
there were changes -- it restarts the corresponding drivers (via service
|
|
|
|
instances) as well as the data server which only reads the list of sections
|
|
|
|
at its startup. This helper service should be triggered whenever your system
|
|
|
|
(re-)starts the `nut-server` service, so that it runs against an up-to-date
|
|
|
|
list of NUT driver processes.
|
|
|
|
|
|
|
|
A service-oriented solution also allows to consider that different drivers
|
|
|
|
have different dependencies -- such as that networked drivers should begin
|
|
|
|
startup after IP addresses have been assigned, while directly-connected
|
|
|
|
devices might need nothing beside a mounted filesystem (or an activated
|
|
|
|
USB stack service or device rule, in case of Linux). Likewise, systems
|
|
|
|
administrators can define further local dependencies between services and
|
|
|
|
their instances as needed on particular deployments.
|
|
|
|
|
|
|
|
This solution also adds the `upsdrvsvcctl` script to manage NUT drivers as
|
|
|
|
system service instances, whose CLI mimics that of `upsdrvctl` program.
|
|
|
|
One addition is the `resync` argument to trigger `nut-driver-enumerator`,
|
|
|
|
another is a `list` argument to display current mappings of service
|
|
|
|
instances to NUT driver sections. Also, original tool's arguments such
|
|
|
|
as the `-u` (user to run the driver as) or `-D` (debug of the driver)
|
|
|
|
do not make sense in the service context -- the accounts to use and
|
|
|
|
other arguments to the driver process are part of service setup (and
|
|
|
|
an administrator can manage it there).
|
|
|
|
|
|
|
|
Note that while this solution tries to register service instances with same
|
|
|
|
names as NUT configuration sections for the devices, this can not always be
|
|
|
|
possible due to constraints such as syntax supported by a particular service
|
|
|
|
management framework. In this case, the enumerator falls back to MD5 hashes
|
|
|
|
of such section names, and the `upsdrvsvcctl` script supports this to map
|
|
|
|
the user-friendly NUT configuration section names to actual service names
|
|
|
|
that it would manage.
|
|
|
|
|
|
|
|
References: man pages: linkman:nutupsdrv[8], linkman:upsdrvctl[8],
|
|
|
|
linkman:upsdrvsvcctl[8]
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
|
|
|
|
Data server configuration (upsd)
|
|
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Configure `upsd`, which serves data from the drivers to the clients.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
First, edit 'upsd.conf' to allow access to your client systems. By
|
|
|
|
default, `upsd` will only listen to `localhost` port 3493/tcp. If you want
|
2011-01-26 11:35:08 +02:00
|
|
|
to connect to it from other machines, you must specify each interface you
|
2022-07-10 10:23:45 +03:00
|
|
|
want `upsd` to listen on for connections, optionally with a port number.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
LISTEN 127.0.0.1 3493
|
|
|
|
LISTEN ::1 3493
|
|
|
|
|
|
|
|
NOTE: Refer to the NUT user manual <<NUT_Security,security chapter>> for
|
|
|
|
information on how to access and secure upsd clients connections.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Next, create 'upsd.users'. For now, this can be an empty file.
|
2016-07-18 03:11:41 +03:00
|
|
|
You can come back and add more to it later when it's time to
|
2022-07-10 10:23:45 +03:00
|
|
|
configure `upsmon` or run one of the management tools.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Do not make either file world-readable, since they both hold
|
|
|
|
access control data and passwords. They just need to be readable by
|
|
|
|
the user you created in the preparation process.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
The suggested configuration is to `chown` it to `root`, `chgrp` it to the
|
2011-01-26 11:35:08 +02:00
|
|
|
group you created, then make it readable by the group.
|
|
|
|
|
|
|
|
chown root:nut upsd.conf upsd.users
|
|
|
|
chmod 0640 upsd.conf upsd.users
|
|
|
|
|
|
|
|
References: man pages: linkman:upsd.conf[5],
|
|
|
|
linkman:upsd.users[5],
|
|
|
|
linkman:upsd[8]
|
|
|
|
|
|
|
|
[[Starting_upsd]]
|
|
|
|
Starting the data server
|
|
|
|
~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
|
|
|
|
Start the network data server:
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsd
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Make sure it is able to connect to the driver(s) on your system.
|
|
|
|
A successful run looks like this:
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
# upsd
|
2011-01-26 11:35:08 +02:00
|
|
|
Network UPS Tools upsd 2.4.1
|
|
|
|
listening on 127.0.0.1 port 3493
|
|
|
|
listening on ::1 port 3493
|
|
|
|
Connected to UPS [eaton]: usbhid-ups-eaton
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
`upsd` prints dots while it waits for the driver to respond. Your
|
2011-01-26 11:35:08 +02:00
|
|
|
system may print more or less depending on how many drivers you
|
|
|
|
have and how fast they are.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
NOTE: If `upsd` says that it can't connect to a UPS or that the data
|
|
|
|
is stale, then your 'ups.conf' is not configured correctly, or you
|
2011-01-26 11:35:08 +02:00
|
|
|
have a driver that isn't working properly. You must fix this before
|
|
|
|
going on to the next step.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
NOTE: Normally `upsd` requires that at least one driver section is
|
|
|
|
defined in the 'ups.conf' file, and refuses to start otherwise.
|
|
|
|
If you intentionally do not have any driver sections defined (yet)
|
|
|
|
but still want the data server to run, respond and report zero devices
|
|
|
|
(e.g. on an automatically managed monitoring deployment), you can enable
|
|
|
|
the `ALLOW_NO_DEVICE true` option in the 'upsd.conf' file.
|
|
|
|
|
|
|
|
On operating systems with service management frameworks, the data server
|
|
|
|
life-cycle is managed by `nut-server` service.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
Reference: man page: linkman:upsd[8]
|
|
|
|
|
|
|
|
Check the UPS data
|
|
|
|
~~~~~~~~~~~~~~~~~~
|
|
|
|
|
|
|
|
Status data
|
|
|
|
^^^^^^^^^^^
|
|
|
|
|
|
|
|
Make sure that the UPS is providing good status data.
|
2022-07-10 10:23:45 +03:00
|
|
|
You can use the `upsc` command-line client for this:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsc myupsname@localhost ups.status
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
You should see just one line in response:
|
|
|
|
|
|
|
|
OL
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
`OL` means your system is running on line power. If it says something
|
|
|
|
else (like `OB` -- on battery, or `LB` -- low battery), your driver was
|
2011-01-26 11:35:08 +02:00
|
|
|
probably misconfigured during the <<Driver_configuration, Driver configuration>>
|
2016-07-18 03:11:41 +03:00
|
|
|
step. If you reconfigure the driver, use `upsdrvctl stop` to stop it, then
|
2011-01-26 11:35:08 +02:00
|
|
|
start it again as shown in the <<Starting_drivers, Starting driver(s)>> step.
|
|
|
|
|
|
|
|
Reference: man page: linkman:upsc[8]
|
|
|
|
|
|
|
|
|
|
|
|
All data
|
|
|
|
^^^^^^^^
|
|
|
|
|
|
|
|
Look at all of the status data which is being monitored.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsc myupsname@localhost
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
What happens now depends on the kind of device and driver you have.
|
2022-07-10 10:23:45 +03:00
|
|
|
In the list, you should see `ups.status` with the same value you got
|
|
|
|
above. A sample run on an UPS (Eaton Ellipse MAX 1100) looks like this:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
battery.charge: 100
|
|
|
|
battery.charge.low: 20
|
|
|
|
battery.runtime: 2525
|
|
|
|
battery.type: PbAc
|
|
|
|
device.mfr: EATON
|
|
|
|
device.model: Ellipse MAX 1100
|
|
|
|
device.serial: ADKK22008
|
|
|
|
device.type: ups
|
|
|
|
driver.name: usbhid-ups
|
|
|
|
driver.parameter.pollfreq: 30
|
|
|
|
driver.parameter.pollinterval: 2
|
|
|
|
driver.parameter.port: auto
|
|
|
|
driver.version: 2.4.1-1988:1990M
|
|
|
|
driver.version.data: MGE HID 1.12
|
|
|
|
driver.version.internal: 0.34
|
|
|
|
input.sensitivity: normal
|
|
|
|
input.transfer.boost.low: 185
|
|
|
|
input.transfer.high: 285
|
|
|
|
input.transfer.low: 165
|
|
|
|
input.transfer.trim.high: 265
|
|
|
|
input.voltage.extended: no
|
|
|
|
outlet.1.desc: PowerShare Outlet 1
|
|
|
|
outlet.1.id: 2
|
|
|
|
outlet.1.status: on
|
|
|
|
outlet.1.switchable: no
|
|
|
|
outlet.desc: Main Outlet
|
|
|
|
outlet.id: 1
|
|
|
|
outlet.switchable: no
|
|
|
|
output.frequency.nominal: 50
|
|
|
|
output.voltage: 230.0
|
|
|
|
output.voltage.nominal: 230
|
|
|
|
ups.beeper.status: enabled
|
|
|
|
ups.delay.shutdown: 20
|
|
|
|
ups.delay.start: 30
|
|
|
|
ups.firmware: 5102AH
|
|
|
|
ups.load: 0
|
|
|
|
ups.mfr: EATON
|
|
|
|
ups.model: Ellipse MAX 1100
|
|
|
|
ups.power.nominal: 1100
|
|
|
|
ups.productid: ffff
|
|
|
|
ups.serial: ADKK22008
|
|
|
|
ups.status: OL CHRG
|
|
|
|
ups.timer.shutdown: -1
|
|
|
|
ups.timer.start: -1
|
|
|
|
ups.vendorid: 0463
|
|
|
|
|
|
|
|
Reference: man page: linkman:upsc[8],
|
|
|
|
<<nut-names,NUT command and variable naming scheme>>
|
|
|
|
|
|
|
|
Startup scripts
|
|
|
|
~~~~~~~~~~~~~~~
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
NOTE: This step is not necessary if you installed from packages.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Edit your startup scripts, and make sure `upsdrvctl` and `upsd` are run
|
|
|
|
every time your system starts. In newer versions of NUT, you may have a
|
|
|
|
'nut.conf' file which sets the `MODE` variable for bundled init-scripts,
|
|
|
|
to facilitate enabling of certain features in the specific end-user
|
|
|
|
deployments.
|
|
|
|
|
|
|
|
If you installed from source, check the `scripts` directory for reference
|
|
|
|
init-scripts, as well as systemd or SMF service methods and manifests.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
[[UPS_shutdown]]
|
|
|
|
Configuring automatic shutdowns for low battery events
|
|
|
|
------------------------------------------------------
|
|
|
|
|
|
|
|
The whole point of UPS software is to bring down the OS cleanly when you
|
|
|
|
run out of battery power. Everything else is roughly eye candy.
|
|
|
|
|
2016-07-18 03:11:41 +03:00
|
|
|
To make sure your system shuts down properly, you will need to perform some
|
2011-01-26 11:35:08 +02:00
|
|
|
additional configuration and run upsmon. Here are the basics.
|
|
|
|
|
|
|
|
[[Shutdown_design]]
|
|
|
|
Shutdown design
|
|
|
|
~~~~~~~~~~~~~~~
|
|
|
|
|
|
|
|
When your UPS batteries get low, the operating system needs to be brought
|
|
|
|
down cleanly. Also, the UPS load should be turned off so that all devices
|
2022-07-10 10:23:45 +03:00
|
|
|
that are attached to it are forcibly rebooted, and subsequently start in
|
|
|
|
the predictable order and state suitable for your data center.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Here are the steps that occur when a critical power event happens,
|
|
|
|
for the simpler case of one UPS device feeding one or several systems:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
1. The UPS goes on battery
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
2. The UPS reaches low battery (a "critical" UPS), that is to say,
|
|
|
|
`upsc` displays:
|
2011-09-29 21:14:46 +03:00
|
|
|
+
|
|
|
|
ups.status: OB LB
|
|
|
|
+
|
2022-07-10 10:23:45 +03:00
|
|
|
The exact behavior depends on the specific device, and is related to
|
|
|
|
such settings and readings as:
|
2011-09-29 21:14:46 +03:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
- `battery.charge` and `battery.charge.low`
|
|
|
|
- `battery.runtime` and `battery.runtime.low`
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
3. The `upsmon` primary notices the "critical UPS" situation and sets
|
|
|
|
"FSD" -- the "forced shutdown" flag to tell all secondary systems
|
|
|
|
that it will soon power down the load.
|
|
|
|
+
|
|
|
|
[WARNING]
|
|
|
|
=========
|
|
|
|
By design, since we require power-cycling the load and don't
|
|
|
|
want some systems to be powered off while others remain running
|
|
|
|
if the "wall power" returns at the wrong moment as usual, the "FSD"
|
|
|
|
flag can not be removed from the data server unless its daemon is
|
|
|
|
restarted. If we do take the first step in critical mode, then we
|
|
|
|
intend to go all the way -- shut down all the servers gracefully,
|
|
|
|
and power down the UPS.
|
|
|
|
|
|
|
|
Keep in mind that some UPS devices and corresponding drivers would
|
|
|
|
latch the "FSD" again even if "wall power" is available, but the
|
|
|
|
remaining battery charge is below a threshold configured as "safe"
|
|
|
|
in the device (usually if you manually power on the UPS after a long
|
|
|
|
power outage). This is by design of respective UPS vendors, since
|
|
|
|
in such situation they can not guarantee that if a new power outage
|
|
|
|
happens, their UPS would safely shut down your systems again.
|
|
|
|
So it is deemed better and safer to stay dark until batteries
|
|
|
|
become sufficiently charged.
|
|
|
|
=========
|
2011-01-26 11:35:08 +02:00
|
|
|
+
|
2022-07-10 10:23:45 +03:00
|
|
|
(If you have no secondary systems, skip to step 6)
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
4. `upsmon` secondary systems see "FSD" and:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
- generate a `NOTIFY_SHUTDOWN` event
|
|
|
|
- wait `FINALDELAY` seconds -- typically `5`
|
|
|
|
- call their `SHUTDOWNCMD`
|
|
|
|
- disconnect from `upsd`
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
5. The `upsmon` primary system waits up to `HOSTSYNC` seconds (typically `15`)
|
|
|
|
for the secondary systems to disconnect from `upsd`. If any are still
|
|
|
|
connected after this time, `upsmon` primary stops waiting and proceeds
|
|
|
|
with the shutdown process.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
6. The `upsmon` primary:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
- generates a `NOTIFY_SHUTDOWN` event
|
|
|
|
- waits `FINALDELAY` seconds -- typically `5`
|
|
|
|
- creates the `POWERDOWNFLAG` file in its local filesystem --
|
|
|
|
usually `/etc/killpower`
|
|
|
|
- calls the `SHUTDOWNCMD`
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
7. On most systems, `init` takes over, kills your processes, syncs and
|
2011-01-26 11:35:08 +02:00
|
|
|
unmounts some filesystems, and remounts some read-only.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
8. `init` then runs your shutdown script. This checks for the
|
|
|
|
`POWERDOWNFLAG`, finds it, and tells the UPS driver(s) to power off
|
|
|
|
the load by sending commands to the connected UPS device(s) they manage.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
9. All the systems lose power.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
10. Time passes. The power returns, and the UPS switches back on.
|
|
|
|
|
|
|
|
11. All systems reboot and go back to work.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
///////////////////////////////////
|
|
|
|
https://github.com/networkupstools/nut/issues/1370
|
|
|
|
|
|
|
|
TODO: Check other docs and code to spell out expected behavior with
|
|
|
|
multiple UPS devices (when not all of them go critical or even on battery)
|
|
|
|
and servers with multiple inputs.
|
|
|
|
|
|
|
|
Does the `upsmon` primary system power-cycle a "critical" UPS if that
|
|
|
|
is not the only one feeding it, so it is not shutting down now?
|
|
|
|
///////////////////////////////////
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
How you set it up
|
|
|
|
~~~~~~~~~~~~~~~~~
|
|
|
|
|
|
|
|
[[NUT_user_creation]]
|
|
|
|
NUT user creation
|
|
|
|
^^^^^^^^^^^^^^^^^
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Create a `upsd` user for `upsmon` to use while monitoring this UPS.
|
|
|
|
|
|
|
|
Edit 'upsd.users' and create a new section. The `upsmon` will connect
|
|
|
|
to `upsd` and use these user name (in brackets) and password to
|
|
|
|
authenticate (as specified in its configuration via `MONITOR` line).
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
This example is for defining a user called "monuser":
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
[monuser]
|
|
|
|
password = mypass
|
2022-07-10 10:23:45 +03:00
|
|
|
upsmon primary
|
|
|
|
# or upsmon secondary
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
References: linkman:upsd[8], linkman:upsd.users[5]
|
|
|
|
|
|
|
|
Reloading the data server
|
|
|
|
^^^^^^^^^^^^^^^^^^^^^^^^^
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Reload `upsd`. Depending on your configuration, you may be able to
|
|
|
|
do this without stopping the `upsd` daemon process:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsd -c reload
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
If that doesn't work (check the syslog), just restart it:
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsd -c stop
|
|
|
|
upsd
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
For systems with integrated service management (Linux systemd,
|
|
|
|
illumos/Solaris SMF) their corresponding `reload` or `refresh`
|
|
|
|
service actions should handle this as well.
|
|
|
|
|
|
|
|
NOTE: If you want to make reloading work later, see the entry in the
|
|
|
|
link:FAQ.html[FAQ] about starting `upsd` as a different user.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Power Off flag file
|
|
|
|
^^^^^^^^^^^^^^^^^^^
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Set the `POWERDOWNFLAG` location for `upsmon`.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
In 'upsmon.conf', add a `POWERDOWNFLAG` directive with a filename.
|
|
|
|
The `upsmon` will create this file when the UPS needs to be powered off
|
2011-01-26 11:35:08 +02:00
|
|
|
during a power failure when low battery is reached.
|
|
|
|
|
|
|
|
We will test for the presence of this file in a later step.
|
|
|
|
|
|
|
|
POWERDOWNFLAG /etc/killpower
|
|
|
|
|
|
|
|
References: man pages: linkman:upsmon[8],
|
|
|
|
linkman:upsmon.conf[5]
|
|
|
|
|
|
|
|
Securing upsmon.conf
|
|
|
|
^^^^^^^^^^^^^^^^^^^^
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
The recommended setting is to have it owned by `root:nut`, then make it
|
|
|
|
readable by the group and not by the world. This file contains passwords
|
|
|
|
that could be used by an attacker to start a shutdown, so keep it secure.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
chown root:nut upsmon.conf
|
|
|
|
chmod 0640 upsmon.conf
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
This step has been placed early in the process so you secure this file
|
|
|
|
before adding sensitive data in the next step.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
|
|
|
|
Create a MONITOR directive for upsmon
|
|
|
|
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Edit 'upsmon.conf' and create a `MONITOR` line with the UPS definition
|
|
|
|
(<upsname>@<hostname>), username and password from the
|
|
|
|
<<NUT_user_creation, NUT user creation>> step, and the
|
|
|
|
"primary" or "secondary" setting.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
If this system is the UPS manager (i.e. it's connected to this UPS directly
|
|
|
|
and can manage it using a suitable NUT driver), its `upsmon` is the primary:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
MONITOR myupsname@mybox 1 monuser mypass primary
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
If it's just monitoring this UPS over the network, and some other
|
|
|
|
system is the primary, then this one is a secondary:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
MONITOR myupsname@mybox 1 monuser mypass secondary
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
The number `1` here is the "power value". This should always be set
|
|
|
|
to 1, unless you have a very special (read: expensive) system with
|
|
|
|
redundant power supplies. In such cases, refer to the User Manual:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
- <<BigServers,typical setups for big servers>>,
|
|
|
|
- <<DataRoom,typical setups for data rooms>>.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Note that the "power value" may also be 0 for a monitoring (administrative)
|
|
|
|
system which only observes the remote UPS status but is not impacted by its
|
|
|
|
power events, and so does not shut down when the UPS does.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
References: linkman:upsmon[8], linkman:upsmon.conf[5]
|
|
|
|
|
|
|
|
Define a SHUTDOWNCMD for upsmon
|
|
|
|
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Still in 'upsmon.conf', add a directive that tells `upsmon` how to
|
|
|
|
shut down your system. This example seems to work on most systems:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
SHUTDOWNCMD "/sbin/shutdown -h +0"
|
|
|
|
|
|
|
|
Notice the presence of "quotes" here to keep it together.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
If your system has special needs (e.g. system-provided shutdown handler
|
|
|
|
is ungracefully time constrained), you may want to set this to a script
|
|
|
|
which does customized local shutdown tasks before calling `init` or
|
|
|
|
`shutdown` programs to handle the system side of this operation.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
|
|
|
|
Start upsmon
|
|
|
|
^^^^^^^^^^^^
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsmon
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
If it complains about something, then check your configuration.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
On operating systems with service management frameworks, the monitoring client
|
|
|
|
life-cycle is managed by `nut-monitor` service.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
Checking upsmon
|
|
|
|
^^^^^^^^^^^^^^^
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Look for messages in the `syslog` to indicate success.
|
|
|
|
It should look something like this:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
May 29 01:11:27 mybox upsmon[102]: Startup successful
|
|
|
|
May 29 01:11:28 mybox upsd[100]: Client monuser@192.168.50.1
|
|
|
|
logged into UPS [myupsname]
|
|
|
|
|
|
|
|
Any errors seen here are probably due to an error in the config files of either
|
|
|
|
`upsmon` or `upsd`. You should fix them before continuing.
|
|
|
|
|
|
|
|
|
|
|
|
Startup scripts
|
|
|
|
^^^^^^^^^^^^^^^
|
|
|
|
|
|
|
|
NOTE: This step is not need if you installed from packages.
|
|
|
|
|
|
|
|
Edit your startup scripts, and add a call to `upsmon`.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Make sure `upsmon` starts when your system comes up.
|
|
|
|
On systems with `upsmon` primary (also running the data server),
|
|
|
|
do it after `upsdrvctl` and `upsd`, or it will complain about not
|
|
|
|
being able to contact the server.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
You may delete the `POWERDOWNFLAG` in the startup scripts, but it is not
|
2011-01-26 11:35:08 +02:00
|
|
|
necessary. `upsmon` will clear that file for you when it starts.
|
|
|
|
|
|
|
|
NOTE: Init script examples are provide in the 'scripts' directory of
|
|
|
|
the NUT source tree, and in the various <<_binary_packages,packages>>
|
|
|
|
that exist.
|
|
|
|
|
|
|
|
Shutdown scripts
|
|
|
|
^^^^^^^^^^^^^^^^
|
|
|
|
|
|
|
|
NOTE: This step is not need if you installed from packages.
|
|
|
|
|
|
|
|
Edit your shutdown scripts, and add `upsdrvctl shutdown`.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
You should configure your system to power down the UPS after the
|
|
|
|
filesystems are remounted read-only. Have it look for the presence
|
|
|
|
of the `POWERDOWNFLAG` (from linkman:upsmon.conf[5]), using this
|
|
|
|
as an example:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
------------------------------------------------------------------------------
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
if (/sbin/upsmon -K)
|
2011-01-26 11:35:08 +02:00
|
|
|
then
|
|
|
|
echo "Killing the power, bye!"
|
2022-07-10 10:23:45 +03:00
|
|
|
/sbin/upsdrvctl shutdown
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
sleep 120
|
|
|
|
|
|
|
|
# uh oh... the UPS power-off failed
|
|
|
|
# you probably want to reboot here so you don't get stuck!
|
|
|
|
# *** see also the section on power races in the FAQ! ***
|
|
|
|
fi
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
------------------------------------------------------------------------------
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
[WARNING]
|
2022-07-10 10:23:45 +03:00
|
|
|
==============================================================================
|
|
|
|
- Be careful that `upsdrvctl shutdown` command will probably power off
|
|
|
|
your machine and others fed by the UPS(es) which it manages.
|
2011-01-26 11:35:08 +02:00
|
|
|
Don't use it unless your system is ready to be halted by force.
|
|
|
|
If you run RAID, read the <<_raid_warning,RAID warning>> below!
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
- Make sure the filesystem(s) containing `upsdrvctl`, `upsmon`,
|
|
|
|
the `POWERDOWNFLAG` file, 'ups.conf' and your UPS driver(s) are
|
|
|
|
mounted (possibly in read-only mode) when the system gets to
|
|
|
|
this point. Otherwise it won't be able to figure out what to do.
|
|
|
|
|
|
|
|
- If for some reason you can not ensure `upsmon` program is executable
|
|
|
|
at this point, your script can `(test -f /etc/killpower)` in a somewhat
|
|
|
|
non-portable manner, instead of asking `upsmon -K` for the verdict
|
|
|
|
according to its current configuration.
|
|
|
|
==============================================================================
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
|
|
|
|
[[Testing_shutdowns]]
|
|
|
|
Testing shutdowns
|
|
|
|
^^^^^^^^^^^^^^^^^
|
|
|
|
|
|
|
|
UPS equipment varies from manufacturer to manufacturer and even within
|
2011-09-29 21:14:46 +03:00
|
|
|
model lines. You should test the <<Shutdown_design,shutdown sequence>>
|
|
|
|
on your systems before leaving them unattended. A successful sequence
|
|
|
|
is one where the OS halts before the battery runs out, and the system
|
|
|
|
restarts when power returns.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
The first step is to see how `upsdrvctl` will behave without actually
|
|
|
|
turning off the power. To do so, use the `-t` argument:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsdrvctl -t shutdown
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
It will display the sequence without actually calling the drivers.
|
|
|
|
|
|
|
|
|
|
|
|
You can finally test a forced shutdown sequence (FSD) using:
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsmon -c fsd
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
This will execute a full shutdown sequence, as presented in
|
|
|
|
<<Shutdown_design,Shutdown design>>, starting from the 3rd step.
|
|
|
|
|
|
|
|
If everything works correctly, the computer will be forcibly powered
|
|
|
|
off, may remain off for a few seconds to a few minutes (depending on
|
|
|
|
the driver and UPS type), then will power on again.
|
|
|
|
|
|
|
|
If your UPS just sits there and never resets the load, you are vulnerable
|
|
|
|
to a power race and should add the "reboot after timeout" hack at the very
|
|
|
|
least.
|
|
|
|
|
|
|
|
Also refer to the section on power races in the link:FAQ.html[FAQ].
|
|
|
|
|
|
|
|
Using suspend to disk
|
|
|
|
~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
|
|
|
|
Support for suspend to RAM and suspend to disk has been available in
|
|
|
|
the Linux kernel for a while now. For obvious reasons, suspending to
|
|
|
|
RAM isn't particularly useful when the UPS battery is getting low,
|
|
|
|
but suspend to disk may be an interesting concept.
|
|
|
|
|
|
|
|
This approach minimizes the amount of disruption which would be caused
|
|
|
|
by an extended outage. The UPS goes on battery, then reaches low
|
|
|
|
battery, and the system takes a snapshot of itself and halts. Then it
|
|
|
|
is turned off and waits for the power to return.
|
|
|
|
|
|
|
|
Once the power is back, the system reboots, pulls the snapshot back in,
|
|
|
|
and keeps going from there. If the user happened to be away when it
|
|
|
|
happened, they may return and have no idea that their system actually
|
2022-07-10 10:23:45 +03:00
|
|
|
shut down completely in the middle (although network connections will drop).
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
In order for this to work, you need to shutdown NUT (UPS driver, `upsd`
|
|
|
|
server and `upsmon` client) in the `suspend` script and start them again in
|
|
|
|
the `resume` script. Don't try to keep them running. The `upsd` server
|
2015-04-30 16:53:36 +03:00
|
|
|
will latch the FSD state (so it won't be usable after resuming) and so
|
2022-07-10 10:23:45 +03:00
|
|
|
will the `upsmon` client. Some drivers may work after resuming, but many
|
|
|
|
don't and some UPS devices will require re-initialization, so it's best not
|
|
|
|
to keep them running either.
|
|
|
|
|
|
|
|
After stopping NUT driver, server and client you'll have to send the UPS
|
|
|
|
the command to shutdown only if the `POWERDOWNFLAG` is present. Note
|
|
|
|
that most likely you'll have to allow for a grace period after calling
|
|
|
|
`upsdrvctl shutdown` since the system will still have to take a
|
|
|
|
snapshot of itself after that. Not all drivers and devices support this,
|
|
|
|
so before going down this road, make sure that the one you're using does.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
- see if you can query or configure settings named like `load.off.delay`,
|
|
|
|
`ups.delay.shutdown`, `offdelay` and/or `shutdown_delay`
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
RAID warning
|
|
|
|
~~~~~~~~~~~~
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
If you run any sort of RAID equipment, make sure your arrays are
|
|
|
|
either halted (if possible) or switched to "read-only" mode.
|
|
|
|
Otherwise you may suffer a long resync once the system comes back up.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
The kernel may not ever run its final shutdown procedure, so you must take
|
|
|
|
care of all array shutdowns in userspace before `upsdrvctl shutdown` runs.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
If you use software RAID (md) on Linux, get `mdadm` and try using
|
|
|
|
`mdadm --readonly` to put your arrays in a safe state. This has to
|
2011-01-26 11:35:08 +02:00
|
|
|
happen after your shutdown scripts have remounted the filesystems.
|
|
|
|
|
|
|
|
On hardware RAID or other kernels, you have to do some detective work. It may
|
|
|
|
be necessary to contact the vendor or the author of your driver to find out
|
|
|
|
how to put the array in a state where a power loss won't leave it "dirty".
|
|
|
|
|
|
|
|
Our understanding is that most if not all RAID devices on Linux will be fine
|
|
|
|
unless there are pending writes. Make sure your filesystems are remounted
|
|
|
|
read-only and you should be covered.
|
|
|
|
|
|
|
|
|
|
|
|
[[DataRoom]]
|
|
|
|
Typical setups for enterprise networks and data rooms
|
|
|
|
-----------------------------------------------------
|
|
|
|
|
|
|
|
The split nature of this UPS monitoring software allows a wide variety of
|
|
|
|
power connections. This chapter will help you identify how things should
|
|
|
|
be configured using some general descriptions.
|
|
|
|
|
|
|
|
There are two main elements:
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
1. There's a UPS attached to a communication (serial, USB or network) port
|
|
|
|
on this system.
|
2011-01-26 11:35:08 +02:00
|
|
|
2. This system depends on a UPS for power.
|
|
|
|
|
|
|
|
You can play "mix and match" with those two to arrive at these descriptions
|
|
|
|
for individual hosts:
|
|
|
|
|
|
|
|
- A: 1 but not 2
|
|
|
|
- B: 2 but not 1
|
|
|
|
- C: 1 and 2
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
A small to medium sized data room usually has one 'C' and a bunch of 'Bs'.
|
|
|
|
This means that there's a system (type 'C') hooked to the UPS which depends
|
|
|
|
on it for power. There are also some other systems in there (type 'B')
|
2011-01-26 11:35:08 +02:00
|
|
|
which depend on that same UPS for power, but aren't directly connected to
|
2022-07-10 10:23:45 +03:00
|
|
|
it communications-wise.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Larger data rooms or those with multiple UPSes may have several "clusters"
|
2022-07-10 10:23:45 +03:00
|
|
|
of the "single 'C', many 'Bs'" depending on how it's all wired.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Finally, there's a special case. Type 'A' systems are connected to
|
|
|
|
an UPS's communication port, but don't depend on it for power.
|
|
|
|
This usually happens when an UPS is physically close to a box and can
|
|
|
|
reach the serial port, but the power wiring is such that it doesn't
|
|
|
|
actually feed that box.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
Once you identify a system's type, use this list to decide which of the
|
|
|
|
programs need to be run for monitoring:
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
- A: driver and `upsd`
|
|
|
|
- B: `upsmon` (in secondary mode)
|
|
|
|
- C: driver, `upsd`, and `upsmon` (in primary mode, as the UPS manager)
|
|
|
|
|
|
|
|
image:images/advanced.png[]
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
To further complicate things, you can have a system that is hooked to
|
|
|
|
multiple UPSes, but only depends on one for power. This particular
|
2022-07-10 10:23:45 +03:00
|
|
|
situation makes it an `A` relative to one UPS, and a `C` relative to the
|
|
|
|
other. The software can handle this -- you just have to tell it what to do.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
NOTE: NUT can also serve as a data proxy to increase the number of clients,
|
2022-07-10 10:23:45 +03:00
|
|
|
or share the communication load between several `upsd` instances.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
If you are running large server-class systems that have more than one
|
|
|
|
power feed, see the next section for information on how to handle it
|
|
|
|
properly.
|
|
|
|
|
|
|
|
[[BigServers]]
|
|
|
|
Typical setups for big servers with UPS redundancy
|
|
|
|
--------------------------------------------------
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
By using multiple `MONITOR` statements in 'upsmon.conf', you can configure
|
|
|
|
an environment where a large machine with redundant power monitors multiple
|
2011-01-26 11:35:08 +02:00
|
|
|
separate UPSes.
|
|
|
|
|
|
|
|
image:images/bigbox.png[]
|
|
|
|
|
|
|
|
Example configuration
|
|
|
|
~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
For the examples in this section, we will use a server with four power
|
|
|
|
supplies installed and locally running the full NUT stack, including
|
|
|
|
`upsmon` in primary mode -- as the UPS manager.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Two UPSes, 'Alpha' and 'Beta', are each driving two of the power supplies
|
|
|
|
(by adding up, we know about the four power supplies of the current system).
|
2011-01-26 11:35:08 +02:00
|
|
|
This means that either 'Alpha' *or* 'Beta' can totally shut down and the
|
|
|
|
server will be able to keep running.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
The 'upsmon.conf' configuration which reflects this is the following:
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
MONITOR ups-alpha@myhost 2 monuser mypass primary
|
|
|
|
MONITOR ups-beta@myhost 2 monuser mypass primary
|
2011-01-26 11:35:08 +02:00
|
|
|
MINSUPPLIES 2
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
With such configuration, `upsmon` on this system will only shut down when
|
|
|
|
both UPS devices reach a critical (on battery + low battery) condition,
|
|
|
|
since 'Alpha' and 'Beta' each provide the same power value.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
As an added bonus, this means you can move a running server from one UPS
|
2022-07-10 10:23:45 +03:00
|
|
|
to another (for maintenance purpose for example) without bringing it down
|
|
|
|
since the minimum sufficient power will be provided at all times.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
The `MINSUPPLIES` line tells `upsmon` that we need at least 2 power supplies
|
2011-01-26 11:35:08 +02:00
|
|
|
to be receiving power from a good UPS (on line or on battery, just not
|
2022-07-10 10:23:45 +03:00
|
|
|
on battery *and* low battery).
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
NOTE: We could have used a 'Power Value' of `1` for both UPS, and have
|
|
|
|
`MINSUPPLIES` set to `1` too. These values are purely arbitrary, so
|
|
|
|
you are free to use your own rules. Here, we have linked these values
|
|
|
|
to the number of power supplies that each UPS is feeding (2) since this
|
|
|
|
maps better to physical topology and allows to throw a third or fourth
|
|
|
|
UPS into the mix without much configuration headache.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
|
|
|
|
Multiple UPS shutdowns ordering
|
|
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
|
|
|
|
If you have multiple UPSes connected to your system, chances are that you
|
|
|
|
need to shut them down in a specific order. The goal is to shut down
|
2022-07-10 10:23:45 +03:00
|
|
|
everything but the one keeping `upsmon` alive at first, then you do that
|
|
|
|
one last.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
To set the order in which your UPSes receive the shutdown commands, define
|
2022-07-10 10:23:45 +03:00
|
|
|
the `sdorder` value in your 'ups.conf' device sections.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
[bigone]
|
|
|
|
driver = usbhid-ups
|
|
|
|
port = auto
|
|
|
|
sdorder = 2
|
|
|
|
|
|
|
|
[littleguy]
|
|
|
|
driver = mge-shut
|
|
|
|
port = /dev/ttyS0
|
|
|
|
sdorder = 1
|
|
|
|
|
|
|
|
[misc]
|
|
|
|
driver = blazer_ser
|
|
|
|
port = /dev/ttyS1
|
|
|
|
sdorder = 0
|
|
|
|
|
|
|
|
The order runs from 0 to the highest number available. So, for this
|
2022-07-10 10:23:45 +03:00
|
|
|
configuration, the order of shutdowns would be 'misc', 'littleguy',
|
|
|
|
and then 'bigone'.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
NOTE: If you have a UPS that shouldn't be powered off when running
|
|
|
|
`upsdrvctl shutdown`, set its `sdorder` to `-1`.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
|
|
|
|
Other redundancy configurations
|
|
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
|
|
|
|
There are a lot of ways to handle redundancy and they all come down to how many
|
|
|
|
power supplies, power cords and independent UPS connections you have. A
|
|
|
|
system with a 1:1 cord:supply ratio has more wires stuffed behind it, but
|
|
|
|
it's much easier to move things around since any given UPS drives a smaller
|
|
|
|
percentage of the overall power.
|
|
|
|
|
|
|
|
More information can be found in the linkdoc:user-manual[NUT user manual],
|
|
|
|
and the various link:man/index.html[user manual pages].
|