136 lines
3.8 KiB
Plaintext
136 lines
3.8 KiB
Plaintext
|
Desc: NUT Powersaving features and using outlet collection
|
||
|
File: powersaving.txt
|
||
|
Date: 14 June 2003
|
||
|
Auth: Arnaud Quette <arnaud.quette@free.fr>
|
||
|
|
||
|
This document introduces NUT PowerSaving features, and Smart
|
||
|
Outlet Management using Network UPS Tools.
|
||
|
|
||
|
This feature is sponsored by MGE UPS SYSTEMS.
|
||
|
|
||
|
Introduction
|
||
|
------------
|
||
|
|
||
|
This feature, which is supported by various manufacturers,
|
||
|
under various names, allows to manage separately the outlets
|
||
|
of an UPS, or a Power Distrubition Unit (PDU). This allows to
|
||
|
program a limited backup time to non-critical loads in order
|
||
|
to keep the maximum of the battery reserve for critical
|
||
|
equipment. This also allows a remote electrical management of
|
||
|
devices, which is very useful in DataCenters for example.
|
||
|
|
||
|
On small setup, you can plug printers, hubs, (...) on
|
||
|
PowerSave'd outlets. During a power outage, the UPS will
|
||
|
turn off those after X minutes of back-up time (or when
|
||
|
passing below X % of battery charge) depending on your
|
||
|
UPS model and settings. This will ensure that all
|
||
|
remaining battery power is available for the computer.
|
||
|
|
||
|
On huger setup (with a huger UPS), this is about the
|
||
|
same with the ability to (power and) control servers in
|
||
|
a smart way (need to notify those to shutdown first !).
|
||
|
|
||
|
Manufacturers Powersaving technologies presentation
|
||
|
===================================================
|
||
|
|
||
|
1) MGE UPS SYSTEMS and MGE Office Protection Systems
|
||
|
----------------------------------------------------
|
||
|
|
||
|
This feature is called "PowerShare" and is available
|
||
|
on lots of models, with different behaviours.
|
||
|
|
||
|
Features will vary according to your exact model.
|
||
|
For example:
|
||
|
|
||
|
- on Pulsar Ellipse Premium 650/800/1200, you can
|
||
|
only set a low battery level which triggers a power
|
||
|
off of the PowerShare outlet(s).
|
||
|
Check http://www.mgeups.com/products/pdt230/smallups/ellipsep/ellipsep1.htm
|
||
|
|
||
|
- on Pulsar Evolution (all models), you can either
|
||
|
do the same as above, or set a timer to shutdown
|
||
|
the outlet when expired. This latter needs to be
|
||
|
used in conjonction with upsmon/upssched to act
|
||
|
upon a power outage, and cancel the timer when
|
||
|
the power is back...
|
||
|
|
||
|
2) Eaton | Powerware ePDU
|
||
|
|
||
|
Depending on the exact model, you can see various measurements
|
||
|
(like current, voltage, power, ...) of the various outlets. You may
|
||
|
also have the hability to start, stop and cycle these.
|
||
|
|
||
|
For more information: http://www.epdu.com
|
||
|
|
||
|
3) Other manufacturers (Belkin, ...)
|
||
|
|
||
|
To be completed...
|
||
|
|
||
|
|
||
|
Integration into the new NUT naming scheme
|
||
|
==========================================
|
||
|
|
||
|
Have a look at new-names.txt, "outlet" section.
|
||
|
|
||
|
|
||
|
Note on outlet collection usage
|
||
|
===============================
|
||
|
|
||
|
1) outlet.{id, desc, ...} represents the
|
||
|
whole outlets (includes all outlet.x.*),
|
||
|
also called Main Outlet.
|
||
|
|
||
|
An interesting fact is that _ALL_ models
|
||
|
have at least that outlet, which is always
|
||
|
considered as the UPS itself. Some values
|
||
|
from the "ups" collection are linked to
|
||
|
the outlet.*, ie:
|
||
|
- outlet.load is mapped from ups.load
|
||
|
- outlet.delay.* is mapped from ups.delay.*
|
||
|
|
||
|
2) Indexes for other outlets begin by 1. So
|
||
|
the first outlet is "outlet.1.*".
|
||
|
|
||
|
|
||
|
Examples of upsc tree
|
||
|
=====================
|
||
|
|
||
|
1) Here is an MGE Evolution tree with the
|
||
|
main and 2 outlets.
|
||
|
|
||
|
...
|
||
|
outlet.desc: Main Outlet
|
||
|
outlet.id: 0
|
||
|
outlet.switchable: 0
|
||
|
outlet.1.autoswitch.charge.low: 0
|
||
|
outlet.1.delay.shutdown: -1
|
||
|
outlet.1.delay.start: -1
|
||
|
outlet.1.desc: PowerShare Outlet 1
|
||
|
outlet.1.id: 1
|
||
|
outlet.1.switch: 1
|
||
|
outlet.1.switchable: 1
|
||
|
outlet.2.autoswitch.charge.low: 0
|
||
|
outlet.2.delay.shutdown: -1
|
||
|
outlet.2.delay.start: -1
|
||
|
outlet.2.desc: PowerShare Outlet 2
|
||
|
outlet.2.id: 2
|
||
|
outlet.2.switch: 1
|
||
|
outlet.2.switchable: 1
|
||
|
...
|
||
|
|
||
|
|
||
|
2) Here is another MGE Ellipse Premium
|
||
|
tree with the main and 1 PowerSaving
|
||
|
outlets.
|
||
|
|
||
|
...
|
||
|
outlet.desc: Main Outlet
|
||
|
outlet.id: 0
|
||
|
outlet.switchable: 0
|
||
|
outlet.1.autoswitch.charge.low: 0
|
||
|
outlet.1.desc: PowerShare Outlet 1
|
||
|
outlet.1.id: 1
|
||
|
outlet.1.switch: 1
|
||
|
outlet.1.switchable: 1
|
||
|
...
|