300 lines
12 KiB
Plaintext
300 lines
12 KiB
Plaintext
|
# Network UPS Tools: example upsmon configuration
|
||
|
#
|
||
|
# This file contains passwords, so keep it secure.
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# RUN_AS_USER <userid>
|
||
|
#
|
||
|
# By default, upsmon splits into two processes. One stays as root and
|
||
|
# waits to run the SHUTDOWNCMD. The other one switches to another userid
|
||
|
# and does everything else.
|
||
|
#
|
||
|
# The default nonprivileged user is set at compile-time with
|
||
|
# 'configure --with-user=...'.
|
||
|
#
|
||
|
# You can override it with '-u <user>' when starting upsmon, or just
|
||
|
# define it here for convenience.
|
||
|
#
|
||
|
# Note: if you plan to use the reload feature, this file (upsmon.conf)
|
||
|
# must be readable by this user! Since it contains passwords, DO NOT
|
||
|
# make it world-readable. Also, do not make it writable by the upsmon
|
||
|
# user, since it creates an opportunity for an attack by changing the
|
||
|
# SHUTDOWNCMD to something malicious.
|
||
|
#
|
||
|
# For best results, you should create a new normal user like "nutmon",
|
||
|
# and make it a member of a "nut" group or similar. Then specify it
|
||
|
# here and grant read access to the upsmon.conf for that group.
|
||
|
#
|
||
|
# This user should not have write access to upsmon.conf.
|
||
|
#
|
||
|
# RUN_AS_USER nutmon
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# MONITOR <system> <powervalue> <username> <password> ("master"|"slave")
|
||
|
#
|
||
|
# List systems you want to monitor. Not all of these may supply power
|
||
|
# to the system running upsmon, but if you want to watch it, it has to
|
||
|
# be in this section.
|
||
|
#
|
||
|
# You must have at least one of these declared.
|
||
|
#
|
||
|
# <system> is a UPS identifier in the form <upsname>@<hostname>[:<port>]
|
||
|
# like ups@localhost, su700@mybox, etc.
|
||
|
#
|
||
|
# Examples:
|
||
|
#
|
||
|
# - "su700@mybox" means a UPS called "su700" on a system called "mybox"
|
||
|
#
|
||
|
# - "fenton@bigbox:5678" is a UPS called "fenton" on a system called
|
||
|
# "bigbox" which runs upsd on port "5678".
|
||
|
#
|
||
|
# The UPS names like "su700" and "fenton" are set in your ups.conf
|
||
|
# in [brackets] which identify a section for a particular driver.
|
||
|
#
|
||
|
# If the ups.conf on host "doghouse" has a section called "snoopy", the
|
||
|
# identifier for it would be "snoopy@doghouse".
|
||
|
#
|
||
|
# <powervalue> is an integer - the number of power supplies that this UPS
|
||
|
# feeds on this system. Most computers only have one power supply, so this
|
||
|
# is normally set to 1. You need a pretty big or special box to have any
|
||
|
# other value here.
|
||
|
#
|
||
|
# You can also set this to 0 for a system that doesn't supply any power,
|
||
|
# but you still want to monitor. Use this when you want to hear about
|
||
|
# changes for a given UPS without shutting down when it goes critical,
|
||
|
# unless <powervalue> is 0.
|
||
|
#
|
||
|
# <username> and <password> must match an entry in that system's
|
||
|
# upsd.users. If your username is "monmaster" and your password is
|
||
|
# "blah", the upsd.users would look like this:
|
||
|
#
|
||
|
# [monmaster]
|
||
|
# password = blah
|
||
|
# upsmon master (or slave)
|
||
|
#
|
||
|
# "master" means this system will shutdown last, allowing the slaves
|
||
|
# time to shutdown first.
|
||
|
#
|
||
|
# "slave" means this system shuts down immediately when power goes critical.
|
||
|
#
|
||
|
# Examples:
|
||
|
#
|
||
|
# MONITOR myups@bigserver 1 monmaster blah master
|
||
|
# MONITOR su700@server.example.com 1 upsmon secretpass slave
|
||
|
# MONITOR myups@localhost 1 upsmon pass master (or slave)
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# MINSUPPLIES <num>
|
||
|
#
|
||
|
# Give the number of power supplies that must be receiving power to keep
|
||
|
# this system running. Most systems have one power supply, so you would
|
||
|
# put "1" in this field.
|
||
|
#
|
||
|
# Large/expensive server type systems usually have more, and can run with
|
||
|
# a few missing. The HP NetServer LH4 can run with 2 out of 4, for example,
|
||
|
# so you'd set that to 2. The idea is to keep the box running as long
|
||
|
# as possible, right?
|
||
|
#
|
||
|
# Obviously you have to put the redundant supplies on different UPS circuits
|
||
|
# for this to make sense! See big-servers.txt in the docs subdirectory
|
||
|
# for more information and ideas on how to use this feature.
|
||
|
|
||
|
MINSUPPLIES 1
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# SHUTDOWNCMD "<command>"
|
||
|
#
|
||
|
# upsmon runs this command when the system needs to be brought down.
|
||
|
#
|
||
|
# This should work just about everywhere ... if it doesn't, well, change it.
|
||
|
|
||
|
SHUTDOWNCMD "/sbin/shutdown -h +0"
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# NOTIFYCMD <command>
|
||
|
#
|
||
|
# upsmon calls this to send messages when things happen
|
||
|
#
|
||
|
# This command is called with the full text of the message as one argument.
|
||
|
# The environment string NOTIFYTYPE will contain the type string of
|
||
|
# whatever caused this event to happen.
|
||
|
#
|
||
|
# Note that this is only called for NOTIFY events that have EXEC set with
|
||
|
# NOTIFYFLAG. See NOTIFYFLAG below for more details.
|
||
|
#
|
||
|
# Making this some sort of shell script might not be a bad idea. For more
|
||
|
# information and ideas, see pager.txt in the docs directory.
|
||
|
#
|
||
|
# Example:
|
||
|
# NOTIFYCMD /usr/local/ups/bin/notifyme
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# POLLFREQ <n>
|
||
|
#
|
||
|
# Polling frequency for normal activities, measured in seconds.
|
||
|
#
|
||
|
# Adjust this to keep upsmon from flooding your network, but don't make
|
||
|
# it too high or it may miss certain short-lived power events.
|
||
|
|
||
|
POLLFREQ 5
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# POLLFREQALERT <n>
|
||
|
#
|
||
|
# Polling frequency in seconds while UPS on battery.
|
||
|
#
|
||
|
# You can make this number lower than POLLFREQ, which will make updates
|
||
|
# faster when any UPS is running on battery. This is a good way to tune
|
||
|
# network load if you have a lot of these things running.
|
||
|
#
|
||
|
# The default is 5 seconds for both this and POLLFREQ.
|
||
|
|
||
|
POLLFREQALERT 5
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# HOSTSYNC - How long upsmon will wait before giving up on another upsmon
|
||
|
#
|
||
|
# The master upsmon process uses this number when waiting for slaves to
|
||
|
# disconnect once it has set the forced shutdown (FSD) flag. If they
|
||
|
# don't disconnect after this many seconds, it goes on without them.
|
||
|
#
|
||
|
# Similarly, upsmon slave processes wait up to this interval for the
|
||
|
# master upsmon to set FSD when a UPS they are monitoring goes critical -
|
||
|
# that is, on battery and low battery. If the master doesn't do its job,
|
||
|
# the slaves will shut down anyway to avoid damage to the file systems.
|
||
|
#
|
||
|
# This "wait for FSD" is done to avoid races where the status changes
|
||
|
# to critical and back between polls by the master.
|
||
|
|
||
|
HOSTSYNC 15
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# DEADTIME - Interval to wait before declaring a stale ups "dead"
|
||
|
#
|
||
|
# upsmon requires a UPS to provide status information every few seconds
|
||
|
# (see POLLFREQ and POLLFREQALERT) to keep things updated. If the status
|
||
|
# fetch fails, the UPS is marked stale. If it stays stale for more than
|
||
|
# DEADTIME seconds, the UPS is marked dead.
|
||
|
#
|
||
|
# A dead UPS that was last known to be on battery is assumed to have gone
|
||
|
# to a low battery condition. This may force a shutdown if it is providing
|
||
|
# a critical amount of power to your system.
|
||
|
#
|
||
|
# Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT.
|
||
|
# Otherwise you'll have "dead" UPSes simply because upsmon isn't polling
|
||
|
# them quickly enough. Rule of thumb: take the larger of the two
|
||
|
# POLLFREQ values, and multiply by 3.
|
||
|
|
||
|
DEADTIME 15
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# POWERDOWNFLAG - Flag file for forcing UPS shutdown on the master system
|
||
|
#
|
||
|
# upsmon will create a file with this name in master mode when it's time
|
||
|
# to shut down the load. You should check for this file's existence in
|
||
|
# your shutdown scripts and run 'upsdrvctl shutdown' if it exists.
|
||
|
#
|
||
|
# See the shutdown.txt file in the docs subdirectory for more information.
|
||
|
|
||
|
POWERDOWNFLAG /etc/killpower
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# NOTIFYMSG - change messages sent by upsmon when certain events occur
|
||
|
#
|
||
|
# You can change the default messages to something else if you like.
|
||
|
#
|
||
|
# NOTIFYMSG <notify type> "message"
|
||
|
#
|
||
|
# NOTIFYMSG ONLINE "UPS %s on line power"
|
||
|
# NOTIFYMSG ONBATT "UPS %s on battery"
|
||
|
# NOTIFYMSG LOWBATT "UPS %s battery is low"
|
||
|
# NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
|
||
|
# NOTIFYMSG COMMOK "Communications with UPS %s established"
|
||
|
# NOTIFYMSG COMMBAD "Communications with UPS %s lost"
|
||
|
# NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
|
||
|
# NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
|
||
|
# NOTIFYMSG NOCOMM "UPS %s is unavailable"
|
||
|
# NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
|
||
|
#
|
||
|
# Note that %s is replaced with the identifier of the UPS in question.
|
||
|
#
|
||
|
# Possible values for <notify type>:
|
||
|
#
|
||
|
# ONLINE : UPS is back online
|
||
|
# ONBATT : UPS is on battery
|
||
|
# LOWBATT : UPS has a low battery (if also on battery, it's "critical")
|
||
|
# FSD : UPS is being shutdown by the master (FSD = "Forced Shutdown")
|
||
|
# COMMOK : Communications established with the UPS
|
||
|
# COMMBAD : Communications lost to the UPS
|
||
|
# SHUTDOWN : The system is being shutdown
|
||
|
# REPLBATT : The UPS battery is bad and needs to be replaced
|
||
|
# NOCOMM : A UPS is unavailable (can't be contacted for monitoring)
|
||
|
# NOPARENT : The process that shuts down the system has died (shutdown impossible)
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# NOTIFYFLAG - change behavior of upsmon when NOTIFY events occur
|
||
|
#
|
||
|
# By default, upsmon sends walls (global messages to all logged in users)
|
||
|
# and writes to the syslog when things happen. You can change this.
|
||
|
#
|
||
|
# NOTIFYFLAG <notify type> <flag>[+<flag>][+<flag>] ...
|
||
|
#
|
||
|
# NOTIFYFLAG ONLINE SYSLOG+WALL
|
||
|
# NOTIFYFLAG ONBATT SYSLOG+WALL
|
||
|
# NOTIFYFLAG LOWBATT SYSLOG+WALL
|
||
|
# NOTIFYFLAG FSD SYSLOG+WALL
|
||
|
# NOTIFYFLAG COMMOK SYSLOG+WALL
|
||
|
# NOTIFYFLAG COMMBAD SYSLOG+WALL
|
||
|
# NOTIFYFLAG SHUTDOWN SYSLOG+WALL
|
||
|
# NOTIFYFLAG REPLBATT SYSLOG+WALL
|
||
|
# NOTIFYFLAG NOCOMM SYSLOG+WALL
|
||
|
# NOTIFYFLAG NOPARENT SYSLOG+WALL
|
||
|
#
|
||
|
# Possible values for the flags:
|
||
|
#
|
||
|
# SYSLOG - Write the message in the syslog
|
||
|
# WALL - Write the message to all users on the system
|
||
|
# EXEC - Execute NOTIFYCMD (see above) with the message
|
||
|
# IGNORE - Don't do anything
|
||
|
#
|
||
|
# If you use IGNORE, don't use any other flags on the same line.
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# RBWARNTIME - replace battery warning time in seconds
|
||
|
#
|
||
|
# upsmon will normally warn you about a battery that needs to be replaced
|
||
|
# every 43200 seconds, which is 12 hours. It does this by triggering a
|
||
|
# NOTIFY_REPLBATT which is then handled by the usual notify structure
|
||
|
# you've defined above.
|
||
|
#
|
||
|
# If this number is not to your liking, override it here.
|
||
|
|
||
|
RBWARNTIME 43200
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# NOCOMMWARNTIME - no communications warning time in seconds
|
||
|
#
|
||
|
# upsmon will let you know through the usual notify system if it can't
|
||
|
# talk to any of the UPS entries that are defined in this file. It will
|
||
|
# trigger a NOTIFY_NOCOMM by default every 300 seconds unless you
|
||
|
# change the interval with this directive.
|
||
|
|
||
|
NOCOMMWARNTIME 300
|
||
|
|
||
|
# --------------------------------------------------------------------------
|
||
|
# FINALDELAY - last sleep interval before shutting down the system
|
||
|
#
|
||
|
# On a master, upsmon will wait this long after sending the NOTIFY_SHUTDOWN
|
||
|
# before executing your SHUTDOWNCMD. If you need to do something in between
|
||
|
# those events, increase this number. Remember, at this point your UPS is
|
||
|
# almost depleted, so don't make this too high.
|
||
|
#
|
||
|
# Alternatively, you can set this very low so you don't wait around when
|
||
|
# it's time to shut down. Some UPSes don't give much warning for low
|
||
|
# battery and will require a value of 0 here for a safe shutdown.
|
||
|
#
|
||
|
# Note: If FINALDELAY on the slave is greater than HOSTSYNC on the master,
|
||
|
# the master will give up waiting for the slave to disconnect.
|
||
|
|
||
|
FINALDELAY 5
|