2011-01-26 11:35:08 +02:00
|
|
|
UPSMON(8)
|
|
|
|
=========
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
NAME
|
|
|
|
----
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
upsmon - UPS monitor and shutdown controller
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
SYNOPSIS
|
|
|
|
--------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*upsmon* -h
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
*upsmon* -c 'command' [-P 'pid']
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
*upsmon* [-D] [-F | -B] [-K] [-p] [-u 'user']
|
2011-01-26 11:35:08 +02:00
|
|
|
|
|
|
|
DESCRIPTION
|
|
|
|
-----------
|
|
|
|
|
|
|
|
*upsmon* is the client process that is responsible for the most important part
|
|
|
|
of UPS monitoring--shutting down the system when the power goes out. It
|
2010-03-26 01:20:59 +02:00
|
|
|
can call out to other helper programs for notification purposes during
|
|
|
|
power events.
|
|
|
|
|
|
|
|
upsmon can monitor multiple systems using a single process. Every UPS
|
2011-01-26 11:35:08 +02:00
|
|
|
that is defined in the linkman:upsmon.conf[5] configuration file is assigned
|
2022-07-10 10:23:45 +03:00
|
|
|
a power value and a type (*primary* or *secondary*).
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
OPTIONS
|
|
|
|
-------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*-h*::
|
2010-03-26 01:20:59 +02:00
|
|
|
Display the help message.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*-c* 'command'::
|
|
|
|
Send the command 'command' to the existing upsmon process. Valid
|
2010-03-26 01:20:59 +02:00
|
|
|
commands are:
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
*fsd*;; shutdown all primary-mode UPSes (use with caution)
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*stop*;; stop monitoring and exit
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*reload*;; reread linkman:upsmon.conf[5] configuration file. See
|
2010-03-26 01:20:59 +02:00
|
|
|
"reloading nuances" below if this doesn't work.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
*-P* 'pid'::
|
|
|
|
Send the command signal above using specified PID number, rather than
|
|
|
|
consulting the PID file. This can help define service units which
|
|
|
|
start main `upsmon` as a foreground process so it does not have to
|
|
|
|
rely on a PID file.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*-D*::
|
2022-07-10 10:23:45 +03:00
|
|
|
Raise the debugging level. upsmon will run in the foreground by default,
|
|
|
|
and will print information on stdout about the monitoring process.
|
|
|
|
Use this option multiple times for more details.
|
|
|
|
|
|
|
|
*-F*::
|
|
|
|
upsmon will run in the foreground, regardless of debugging settings.
|
|
|
|
|
|
|
|
*-B*::
|
|
|
|
upsmon will run in the background, regardless of debugging settings.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*-K*::
|
2010-03-26 01:20:59 +02:00
|
|
|
Test for the shutdown flag. If it exists and contains the magic string
|
2011-01-26 11:35:08 +02:00
|
|
|
from upsmon, then upsmon will exit with `EXIT_SUCCESS`. Any other condition
|
2022-07-10 10:23:45 +03:00
|
|
|
will make upsmon exit with `EXIT_FAILURE`.
|
2011-01-26 11:35:08 +02:00
|
|
|
+
|
|
|
|
You can test for a successful exit from `upsmon -K` in your shutdown
|
|
|
|
scripts to know when to call linkman:upsdrvctl[8] to shut down the UPS.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*-p*::
|
2010-03-26 01:20:59 +02:00
|
|
|
Run privileged all the time. Normally upsmon will split into two
|
|
|
|
processes. The majority of the code runs as an unprivileged user, and
|
|
|
|
only a tiny stub runs as root. This switch will disable that mode, and
|
|
|
|
run the old "all root all the time" system.
|
2011-01-26 11:35:08 +02:00
|
|
|
+
|
2010-03-26 01:20:59 +02:00
|
|
|
This is not the recommended mode, and you should not use this unless you
|
|
|
|
have a very good reason.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*-u* 'user'::
|
2010-03-26 01:20:59 +02:00
|
|
|
Set the user for the unprivileged monitoring process. This has no effect
|
2011-01-26 11:35:08 +02:00
|
|
|
when using -p.
|
|
|
|
+
|
2010-03-26 01:20:59 +02:00
|
|
|
The default user is set at configure time with 'configure
|
2011-01-26 11:35:08 +02:00
|
|
|
--with-user=...'. Typically this is 'nobody', but other distributions
|
2010-03-26 01:20:59 +02:00
|
|
|
will probably have a specific 'nut' user for this task. If your
|
|
|
|
notification scripts need to run as a specific user, set it here.
|
2011-01-26 11:35:08 +02:00
|
|
|
+
|
|
|
|
You can also set this in the linkman:upsmon.conf[5] file with the
|
2010-03-26 01:20:59 +02:00
|
|
|
RUN_AS_USER directive.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
UPS DEFINITIONS
|
|
|
|
---------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
In the linkman:upsmon.conf[5], you must specify at least one UPS that will
|
2010-03-26 01:20:59 +02:00
|
|
|
be monitored. Use the MONITOR directive.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
MONITOR 'system' 'powervalue' 'username' 'password' 'type'
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
The 'system' refers to a linkman:upsd[8] server, in the form
|
|
|
|
+upsname[@hostname[:port]]+. The default hostname is "localhost". Some
|
2010-03-26 01:20:59 +02:00
|
|
|
examples follow:
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
- "su700@mybox" means a UPS called "su700" on a system called "mybox".
|
2010-03-26 01:20:59 +02:00
|
|
|
This is the normal form.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
- "fenton@bigbox:5678" is a UPS called "fenton" on a system called
|
2011-01-26 11:35:08 +02:00
|
|
|
"bigbox" which runs linkman:upsd[8] on port "5678".
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
The 'powervalue' refers to how many power supplies on this system are
|
2010-03-26 01:20:59 +02:00
|
|
|
being driven this UPS. This is typically set to 1, but see the section
|
|
|
|
on power values below.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
The 'username' is a section in your linkman:upsd.users[5] file.
|
|
|
|
Whatever password you set in that section must match the 'password'
|
2022-07-10 10:23:45 +03:00
|
|
|
set in this file.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
The type set in that section must also match the 'type' here --
|
|
|
|
*primary* or *secondary*. In general, a primary process is one
|
2010-03-26 01:20:59 +02:00
|
|
|
running on the system with the UPS actually plugged into a serial
|
2022-07-10 10:23:45 +03:00
|
|
|
port, and a secondary is drawing power from the UPS but can't
|
|
|
|
talk to it directly. See the section on UPS types for more.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
NOTIFY EVENTS
|
|
|
|
-------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*upsmon* senses several events as it monitors each UPS. They are called
|
2010-03-26 01:20:59 +02:00
|
|
|
notify events as they can be used to tell the users and admins about the
|
2011-01-26 11:35:08 +02:00
|
|
|
change in status. See the additional NOTIFY-related sections below for
|
2010-03-26 01:20:59 +02:00
|
|
|
information on customizing the delivery of these messages.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*ONLINE*::
|
2010-03-26 01:20:59 +02:00
|
|
|
The UPS is back on line.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*ONBATT*::
|
2010-03-26 01:20:59 +02:00
|
|
|
The UPS is on battery.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*LOWBATT*::
|
2010-03-26 01:20:59 +02:00
|
|
|
The UPS battery is low (as determined by the driver).
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*FSD*::
|
2010-03-26 01:20:59 +02:00
|
|
|
The UPS has been commanded into the "forced shutdown" mode.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*COMMOK*::
|
2010-03-26 01:20:59 +02:00
|
|
|
Communication with the UPS has been established.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*COMMBAD*::
|
2010-03-26 01:20:59 +02:00
|
|
|
Communication with the UPS was just lost.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*SHUTDOWN*::
|
2010-03-26 01:20:59 +02:00
|
|
|
The local system is being shut down.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*REPLBATT*::
|
2010-03-26 01:20:59 +02:00
|
|
|
The UPS needs to have its battery replaced.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*NOCOMM*::
|
2010-03-26 01:20:59 +02:00
|
|
|
The UPS can't be contacted for monitoring.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
NOTIFY COMMAND
|
|
|
|
--------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
In linkman:upsmon.conf[5], you can configure a program called the NOTIFYCMD
|
2022-07-10 10:23:45 +03:00
|
|
|
that will handle events that occur.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
+NOTIFYCMD+ "'path to program'"
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
+NOTIFYCMD "/usr/local/bin/notifyme"+
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
Remember to wrap the path in "quotes" if it contains any spaces.
|
|
|
|
|
|
|
|
The program you run as your NOTIFYCMD can use the environment variables
|
|
|
|
NOTIFYTYPE and UPSNAME to know what has happened and on which UPS. It
|
|
|
|
also receives the notification message (see below) as the first (and
|
2022-07-10 10:23:45 +03:00
|
|
|
only) argument, so you can deliver a pre-formatted message too.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
Note that the NOTIFYCMD will only be called for a given event when you set
|
2022-07-10 10:23:45 +03:00
|
|
|
the EXEC flag by using the notify flags, as detailed below.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
NOTIFY FLAGS
|
|
|
|
------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
By default, all notify events (see above) generate a global message
|
|
|
|
(wall) to all users, plus they are logged via the syslog. You can change
|
|
|
|
this with the NOTIFYFLAG directive in the configuration file:
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
+NOTIFYFLAG+ 'notifytype' 'flags'
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
Examples:
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
- `NOTIFYFLAG ONLINE SYSLOG`
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
- `NOTIFYFLAG ONBATT SYSLOG+WALL`
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
- `NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC`
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
The flags that can be set on a given notify event are:
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*SYSLOG*::
|
2010-03-26 01:20:59 +02:00
|
|
|
Write this message to the syslog.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*WALL*::
|
|
|
|
Send this message to all users on the system via *wall*(1).
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*EXEC*::
|
2010-03-26 01:20:59 +02:00
|
|
|
Execute the NOTIFYCMD.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*IGNORE*::
|
2010-03-26 01:20:59 +02:00
|
|
|
Don't do anything. If you use this, don't use any of the other flags.
|
2011-01-26 11:35:08 +02:00
|
|
|
|
2010-03-26 01:20:59 +02:00
|
|
|
You can mix these flags. "SYSLOG+WALL+EXEC" does all three for a given
|
|
|
|
event.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
NOTIFY MESSAGES
|
|
|
|
---------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
upsmon comes with default messages for each of the NOTIFY events. These
|
|
|
|
can be changed with the NOTIFYMSG directive.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
+NOTIFYMSG+ 'type' "'message'"
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
Examples:
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
- `NOTIFYMSG ONLINE "UPS %s is getting line power"`
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
- ` NOTIFYMSG ONBATT "Someone pulled the plug on %s"`
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
The first instance of %s is replaced with the identifier of the UPS that
|
|
|
|
generated the event. These messages are used when sending walls to the
|
|
|
|
users directly from upsmon, and are also passed to the NOTIFYCMD.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
POWER VALUES
|
|
|
|
------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
The "current overall power value" is the sum of all UPSes that are
|
|
|
|
currently able to supply power to the system hosting upsmon. Any
|
|
|
|
UPS that is either on line or just on battery contributes to this
|
|
|
|
number. If a UPS is critical (on battery and low battery) or has been
|
|
|
|
put into "forced shutdown" mode, it no longer contributes.
|
|
|
|
|
|
|
|
A "power value" on a MONITOR line in the config file is the number of
|
2022-07-10 10:23:45 +03:00
|
|
|
power supplies that the UPS runs on the current system.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
+MONITOR+ 'upsname' 'powervalue' 'username' 'password' 'type'
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Normally, you only have one power supply, so it will be set to 1.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
+MONITOR myups@myhost 1 username mypassword primary+
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
On a large server with redundant power supplies, the power value for a UPS
|
|
|
|
may be greater than 1. You may also have more than one of them defined.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
+MONITOR ups-alpha@myhost 2 username mypassword primary+
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
+MONITOR ups-beta@myhost 2 username mypassword primary+
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
You can also set the power value for a UPS to 0 if it does not supply any
|
|
|
|
power to that system. This is generally used when you want to use the
|
|
|
|
upsmon notification features for a UPS even though it's not actually
|
2022-07-10 10:23:45 +03:00
|
|
|
running the system that hosts upsmon. Don't set this to "primary" unless
|
2010-03-26 01:20:59 +02:00
|
|
|
you really want to power this UPS off when this instance of upsmon needs
|
|
|
|
to shut down for its own reasons.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
+MONITOR faraway@anotherbox 0 username mypassword secondary+
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
The "minimum power value" is the number of power supplies that must be
|
2022-07-10 10:23:45 +03:00
|
|
|
receiving power in order to keep the computer running.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
+MINSUPPLIES+ 'value'
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
Typical PCs only have 1, so most users will leave this at the default.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
+MINSUPPLIES 1+
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
If you have a server or similar system with redundant power, then this
|
|
|
|
value will usually be set higher. One that requires three power supplies
|
|
|
|
to be running at all times would simply set it to 3.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
+MINSUPPLIES 3+
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
When the current overall power value drops below the minimum power value,
|
|
|
|
upsmon starts the shutdown sequence. This design allows you to lose some
|
|
|
|
of your power supplies in a redundant power environment without bringing
|
|
|
|
down the entire system while still working properly for smaller systems.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
UPS TYPES
|
|
|
|
---------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
*upsmon* and linkman:upsd[8] don't always run on the same system. When they
|
2010-03-26 01:20:59 +02:00
|
|
|
do, any UPSes that are directly attached to the upsmon host should be
|
2022-07-10 10:23:45 +03:00
|
|
|
monitored in "primary" mode. This makes upsmon take charge of that equipment,
|
|
|
|
and it will wait for the "secondary" systems to disconnect before shutting
|
2010-03-26 01:20:59 +02:00
|
|
|
down the local system. This allows the distant systems (monitoring over
|
2011-01-26 11:35:08 +02:00
|
|
|
the network) to shut down cleanly before `upsdrvctl shutdown` runs
|
2010-03-26 01:20:59 +02:00
|
|
|
and turns them all off.
|
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
When upsmon runs as a secondary, it is relying on the distant system to tell
|
2010-03-26 01:20:59 +02:00
|
|
|
it about the state of the UPS. When that UPS goes critical (on battery
|
|
|
|
and low battery), it immediately invokes the local shutdown command. This
|
2022-07-10 10:23:45 +03:00
|
|
|
needs to happen quickly. Once all secondaries disconnect from the distant
|
|
|
|
linkman:upsd[8] server, its primary-mode upsmon will start its own shutdown
|
|
|
|
process. Your secondary systems must all quiesce and shut down before the
|
|
|
|
primary turns off the shared power source, or filesystem damage may result.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
upsmon deals with secondaries that get wedged, hang, or otherwise fail to
|
2011-01-26 11:35:08 +02:00
|
|
|
disconnect from linkman:upsd[8] in a timely manner with the HOSTSYNC
|
2022-07-10 10:23:45 +03:00
|
|
|
timer. During a shutdown situation, the primary upsmon will give up after
|
|
|
|
this interval and it will shut down anyway. This keeps the primary from
|
|
|
|
sitting there forever (which would endanger that host) if a secondary
|
|
|
|
should break somehow. This defaults to 15 seconds.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
If your primary system is shutting down too quickly, set the FINALDELAY
|
2010-03-26 01:20:59 +02:00
|
|
|
interval to something greater than the default 15 seconds. Don't set
|
|
|
|
this too high, or your UPS battery may run out of power before the
|
2022-07-10 10:23:45 +03:00
|
|
|
primary upsmon process shuts down that system.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
TIMED SHUTDOWNS
|
|
|
|
---------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
For those rare situations where the shutdown process can't be completed
|
|
|
|
between the time that low battery is signalled and the UPS actually powers
|
2011-01-26 11:35:08 +02:00
|
|
|
off the load, use the linkman:upssched[8] helper program. You can use it
|
2010-03-26 01:20:59 +02:00
|
|
|
along with upsmon to schedule a shutdown based on the "on battery" event.
|
2011-01-26 11:35:08 +02:00
|
|
|
upssched can then come back to upsmon to initiate the shutdown once it has
|
2010-03-26 01:20:59 +02:00
|
|
|
run on battery too long.
|
|
|
|
|
|
|
|
This can be complicated and messy, so stick to the default critical UPS
|
|
|
|
handling if you can.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
REDUNDANT POWER SUPPLIES
|
|
|
|
------------------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
If you have more than one power supply for redundant power, you may also
|
|
|
|
have more than one UPS feeding your computer. upsmon can handle this. Be
|
|
|
|
sure to set the UPS power values appropriately and the MINSUPPLIES value
|
|
|
|
high enough so that it keeps running until it really does need to shut
|
|
|
|
down.
|
|
|
|
|
|
|
|
For example, the HP NetServer LH4 by default has 3 power supplies
|
|
|
|
installed, with one bay empty. It has two power cords, one per side of
|
|
|
|
the box. This means that one power cord powers two power supply bays,
|
|
|
|
and that you can only have two UPSes supplying power.
|
|
|
|
|
|
|
|
Connect UPS "alpha" to the cord feeding two power supplies, and UPS
|
|
|
|
"beta" to the cord that feeds the third and the empty slot. Define alpha
|
|
|
|
as a powervalue of 2, and beta as a powervalue of 1. Set the MINSUPPLIES
|
|
|
|
to 2.
|
|
|
|
|
|
|
|
When alpha goes on battery, your current overall power value will stay
|
|
|
|
at 3, as it's still supplying power. However, once it goes critical (on
|
|
|
|
battery and low battery), it will stop contributing to the current overall
|
|
|
|
power value. That means the value will be 1 (beta alone), which is less
|
|
|
|
than 2. That is insufficient to run the system, and upsmon will invoke
|
|
|
|
the shutdown sequence.
|
|
|
|
|
|
|
|
However, if beta goes critical, subtracting its contribution will take the
|
|
|
|
current overall value from 3 to 2. This is just high enough to satisfy
|
|
|
|
the minimum, so the system will continue running as before. If beta
|
2011-01-26 11:35:08 +02:00
|
|
|
returns later, it will be re-added and the current value will go back to
|
2010-03-26 01:20:59 +02:00
|
|
|
3. This allows you to swap out UPSes, change a power configuration, or
|
|
|
|
whatever, as long as you maintain the minimum power value at all times.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
MIXED OPERATIONS
|
|
|
|
----------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
Besides being able to monitor multiple UPSes, upsmon can also monitor them
|
|
|
|
as different roles. If you have a system with multiple power supplies
|
2022-07-10 10:23:45 +03:00
|
|
|
serviced by separate UPS batteries, it's possible to be a primary on one
|
|
|
|
UPS and a secondary on the other. This usually happens when you run
|
|
|
|
out of serial or USB ports and need to do the monitoring through another
|
|
|
|
system nearby.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
This is also complicated, especially when it comes time to power down a
|
|
|
|
UPS that has gone critical but doesn't supply the local system. You can
|
|
|
|
do this with some scripting magic in your notify command script, but it's
|
|
|
|
beyond the scope of this manual.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
FORCED SHUTDOWNS
|
|
|
|
----------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
When upsmon is forced to bring down the local system, it sets the
|
2022-07-10 10:23:45 +03:00
|
|
|
"FSD" (forced shutdown) flag on any UPSes that it is running in primary
|
|
|
|
mode. This is used to synchronize secondary systems in the event that
|
|
|
|
a primary which is otherwise OK needs to be brought down due to some
|
|
|
|
pressing event on the UPS manager system.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
You can manually invoke this mode on the system with primary-mode upsmon
|
|
|
|
by starting another copy of the program with `-c fsd` command line argument.
|
|
|
|
This is useful when you want to initiate a shutdown before the critical
|
|
|
|
stage through some external means, such as linkman:upssched[8].
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
DEAD UPSES
|
|
|
|
----------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
In the event that upsmon can't reach linkman:upsd[8], it declares that UPS
|
2010-03-26 01:20:59 +02:00
|
|
|
"dead" after some interval controlled by DEADTIME in the
|
2011-01-26 11:35:08 +02:00
|
|
|
linkman:upsmon.conf[5]. If this happens while that UPS was last known to be
|
2010-03-26 01:20:59 +02:00
|
|
|
on battery, it is assumed to have gone critical and no longer contributes
|
|
|
|
to the overall power value.
|
|
|
|
|
|
|
|
upsmon will alert you to a UPS that can't be contacted for monitoring
|
|
|
|
with a "NOCOMM" notifier by default every 300 seconds. This can be
|
|
|
|
changed with the NOCOMMWARNTIME setting.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
RELOADING NUANCES
|
|
|
|
-----------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
upsmon usually gives up root powers for the process that does most of
|
|
|
|
the work, including handling signals like SIGHUP to reload the configuration
|
2011-01-26 11:35:08 +02:00
|
|
|
file. This means your linkman:upsmon.conf[8] file must be readable by
|
|
|
|
the non-root account that upsmon switches to.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
If you want reloads to work, upsmon must run as some user that has
|
|
|
|
permissions to read the configuration file. I recommend making a new
|
|
|
|
user just for this purpose, as making the file readable by "nobody"
|
|
|
|
(the default user) would be a bad idea.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
See the RUN_AS_USER section in linkman:upsmon.conf[8] for more on this topic.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
Additionally, you can't change the SHUTDOWNCMD or POWERDOWNFLAG
|
2011-01-26 11:35:08 +02:00
|
|
|
definitions with a reload due to the split-process model. If you change
|
|
|
|
those values, you *must* stop upsmon and start it back up. upsmon
|
2010-03-26 01:20:59 +02:00
|
|
|
will warn you in the syslog if you make changes to either of those
|
|
|
|
values during a reload.
|
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
SIMULATING POWER FAILURES
|
|
|
|
-------------------------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
|
|
|
To test a synchronized shutdown without pulling the plug on your UPS(es),
|
|
|
|
you need only set the forced shutdown (FSD) flag on them. You can do this
|
2011-01-26 11:35:08 +02:00
|
|
|
by calling upsmon again to set the flag, i.e.:
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
+upsmon -c fsd+
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2022-07-10 10:23:45 +03:00
|
|
|
After that, the primary and the secondary will do their usual shutdown
|
|
|
|
sequence as if the battery had gone critical, while you can time how long
|
|
|
|
it takes for them. This is much easier on your UPS equipment, and it beats
|
|
|
|
crawling under a desk to find the plug.
|
|
|
|
|
|
|
|
Note you can also use a dummy SHUTDOWNCMD setting to just report that the
|
|
|
|
systems would shut down at this point, without actually disrupting their work.
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
FILES
|
|
|
|
-----
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
linkman:upsmon.conf[5]
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
SEE ALSO
|
|
|
|
--------
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
Server:
|
|
|
|
~~~~~~~
|
2022-07-10 10:23:45 +03:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
linkman:upsd[8]
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
Clients:
|
|
|
|
~~~~~~~~
|
2022-07-10 10:23:45 +03:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
linkman:upsc[8], linkman:upscmd[8],
|
|
|
|
linkman:upsrw[8], linkman:upsmon[8]
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
CGI programs:
|
|
|
|
~~~~~~~~~~~~~
|
2022-07-10 10:23:45 +03:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
linkman:upsset.cgi[8], linkman:upsstats.cgi[8], linkman:upsimage.cgi[8]
|
2010-03-26 01:20:59 +02:00
|
|
|
|
2011-01-26 11:35:08 +02:00
|
|
|
Internet resources:
|
|
|
|
~~~~~~~~~~~~~~~~~~~
|
2022-07-10 10:23:45 +03:00
|
|
|
|
2010-03-26 01:20:59 +02:00
|
|
|
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|